Vertiv | Liebert® GXT5™ | Installer/User Guide
39
PORT
NO.
PORT
NAME
PIN
NO.
PIN NAME
DESCRIPTION
2
Input 2
3
Remote Comms 2
User configurable dry-contact input that can be set to trigger
the events below. The user can also select the dry-contact as
either NO or NC. (See
) When NO, Pins 3 and 4 are shorted to trigger the event.
When NC, Pins 3 and 4 are opened to trigger the event.
Options are:
•
Disable (default)
•
Battery mode shutdown - If the UPS is running on batteries
and this input is triggered, the UPS shuts down
•
Any mode shutdown - If this input is triggered, the UPS
shuts down regardless of current operating mode
•
Maintenance mode-For
16 & 20 kVA
model, If this input is
triggered, it means the UPS is in maintenance mode.
4
Signal Ground
Signal Ground
3
Battery
5
EBC Detection
Automatically detects number of external- battery cabinets
when pins 5 and 6 are connected to the detection port, see
Installing External Battery Cabinets
6
EBC Detection
Automatically detects number of external- battery cabinets
when pins 5 and 6 are connected to the detection port, see
Installing External Battery Cabinets on page 26
REPO
REPO
Input
7
+5V
REPO power supply, 5-Vdc 100-mA
8
REPO Coil -NC
NC, activated when Pin 7 and Pin 8 is open
NOTE: For details on REPO connection and operation, see
Connecting a Remote Emergency Power-off (REPO) Switch
5
Output 5
9, 10
Remote Fault Alert 5
User configurable dry-contact output that can be set to alert
the user to the faults below.
The user can also select the dry-contact as either NO or NC.
(See
Pins 9 and 10 are shorted when the fault occurs. When NC, Pins
9 and 10 are opened when the fault occurs.
Options are:
•
Low battery (default)
•
On battery
•
On bypass
• UPS fault
6
Output 6
11, 12
Remote Fault Alert 6
User configurable dry-contact output that can be set to alert
the user to the faults below.
The user can also select the dry-contact as either NO or NC.
(See
Pins 11 and 12 are shorted when the fault occurs. When NC, Pins
11 and 12 are opened when the fault occurs.
Options are:
•
Low battery
•
On battery
•
On bypass
•
UPS fault (default)
Содержание Vertiv GXT5
Страница 1: ...VertivTM Liebert GXT5 UPS 230 V Input 230 V Output Installer User Guide ...
Страница 8: ...Important Safety Information 2 This page is intentionally left blank ...
Страница 30: ...GXT5 Description 24 This page is intentionally left blank ...
Страница 56: ...Operating the UPS 48 Start up Guidance 1 4 Start up Guidance 2 4 Start up Guidance 3 4 ...
Страница 60: ... 52 This page is intentionally left blank ...
Страница 88: ...Operation and Display Panel 80 This page is intentionally left blank ...
Страница 108: ...Maintenance 100 This page is intentionally left blank ...
Страница 112: ...Troubleshooting 104 This page is intentionally left blank ...
Страница 132: ...Specifications 124 This page is intentionally left blank ...
Страница 134: ... 126 This page is intentionally left blank ...