Configuring Your Neutral and Ground Connections
17
6.4
Alternate Grounding Configuration, Non-Isolated
A few applications in this power range have 208 VAC input and output, and a connected load consist-
ing of multiple Power Distribution Units (PDUs), panelboards, switchboards or other items of load
equipment which do not have isolation transformers.
Notice in
Figure 7
that the UPS system main input and bypass input are connected to a grounded-
wye service. In this configuration, the UPS system is not considered a separately derived source.
The UPS module output neutral and the load neutral are solidly connected to the building service
neutral, which is bonded to the grounding conductor at the service entrance equipment.
Figure 7
Alternate grounding configuration, non-isolated
This arrangement may be used for systems with 208 VAC input and output. However, it does not pro-
vide any isolation or common-mode noise attenuation for sensitive loads. For this reason, this config-
uration is not a preferred installation method.
NOTE
If there is a 4-pole Automatic Transfer Switch (ATS) between the service entrance and the UPS,
this configuration cannot be used. Refer to
6.3 - Preferred Grounding Configuration With
Isolated Bypass
to determine a suitable configuration.
Содержание SERIES 610
Страница 6: ...iv...
Страница 42: ...Installation Drawings 36 Figure 17 Outline drawing Multi Module System Standard 88 797606 05 Rev 02...
Страница 43: ...Installation Drawings 37 Figure 18 Terminal details Multi Module System 100 125kVA 88 797606 16 Rev 05...
Страница 44: ...Installation Drawings 38 Figure 19 Terminal details Multi Module System 150 225kVA 88 797606 12 Rev 03...
Страница 45: ...Installation Drawings 39 Figure 20 Battery power pack system 88 797616 03 Rev 08...
Страница 46: ...Installation Drawings 40 Figure 21 Battery power pack Size A 88 797616 01 Rev 10...
Страница 49: ...Installation Drawings 43 Figure 24 Outline drawing System Control Cabinet SCCT 200 1200A 88 797614 01 Rev 08...
Страница 51: ...Installation Drawings 45 Figure 26 Outline drawing System Control Cabinet SCCT 1600 2000A 88 797614 02 Rev 07...
Страница 53: ...Installation Drawings 47 Figure 28 Outline drawing System Control Cabinet SCCT 2500 3000A 88 797614 03 Rev 08...
Страница 57: ...Installation Drawings 51 Figure 32 Control connection location diagram SCCT 96 797619 88A Rev 04...
Страница 79: ...Installation Drawings 73 Figure 54 Outline drawing Remote Status Panel surface mount 88 791617 01 Rev 05...
Страница 80: ...Installation Drawings 74...
Страница 85: ...Site Planning Data Series 610 100 225kVA Multi Module Systems 79 NOTES...
Страница 86: ...Site Planning Data Series 610 100 225kVA Multi Module Systems 80...
Страница 87: ......