Alarm and Faults
74
11.4 List of Messages
Table 9
lists available event messages, a definition of the event, and the functions that are activated
with the event by default. The functions are indicated as follows:
D
— The indicated event initiates the
Auto-Dial
sequence through the optional modem.
A
— The indicated event activates the
Audible
alarm.
F
— The indicated event triggers a
Freeze
of the History Log.
L
— The indicated event
Latches
. A latched alarm remains displayed until the alarm condition
has cleared and the RESET (ALRMRST) button has been pressed.
E
— By default, all faults and alarms are written to the Event Log. Changing this setting is only
available for the LED units and is set through the RS-232 port. See
Setting Event Masks with
the Terminal on page 83
All of these functions, except Freeze, can be reconfigured to trigger for each event, using the Event
Mask option. See
11.1 - Event Mask
on page 71. The Freeze function is hard-coded and cannot be
changed for a event.
If the front panel of your STS2 contains LEDs and push buttons instead of the touch screen interface,
you can view these messages via the RS-232 port. See
12.1.1 - Connecting and Using a
Terminal
on page 77 for the commands to view the event messages on a PC terminal.
An LED is used to indicate the presence of any active fault or alarm. Refer to
14.0 - Operating the
LED Display STS2
for more information about the LEDs.
.
Table 9
Event Messages
ID
Alarm Message
Description/Cause
Action
001
S1 SCR SHORT
One or more of the SCRs for Source 1 have shorted and
failed.
D, F, A, E
002
S2 SCR SHORT
One or more of the SCRs for Source 2 have shorted and
failed.
D, F, A, E
003
S1 SCR OPEN
One or more of the SCRs for Source 1 is open.
D, F, A, E
004
S2 SCR OPEN
One or more of the SCRs for Source 2 is open.
D, F, A, E
005
PRIMARY FAN FAIL
A primary cooling fan has failed and the unit is now being
cooled by a secondary fan, which is not monitored.
D, A, E
006
CONTROL MODULE FAIL
Control logic module has failed.
D, A, E
007
PWR SPLY DC A FAIL
Power supply DC bus A has failed.
D, A, E
008
PWR SPLY DC B FAIL
Power supply DC bus B has failed.
D, A, E
009
PWR SPLY S1 AC FAIL
Power supply Source 1 AC has failed.
D, A, E
010
PWR SPLY S2 AC FAIL
Power supply Source 2 AC has failed.
D, A, E
011
PWR SPLY LOGIC FAIL
A power supply module has failed.
D, A, E
012
OUT VOLT SENSE FAIL
The output volt sense module failed
D, A, E
013
S1 VOLT SENSE FAIL
The Source 1 volt sense module failed.
D, A, E
014
S2 VOLT SENSE FAIL
The Source 2 volt sense module failed.
D, A, E
015
S1 SCR SENSE FAIL
The Source 1 SCR sense module failed.
D, A, E
016
S2 SCR SENSE FAIL
The Source 2 SCR sense module failed.
D, A, E
017
S1 CURR SENSE FAIL
The Source 1 SCR current module failed.
D, A, E
018
S2 CURR SENSE FAIL
The Source 2 SCR current module failed.
D, A, E
019
S1 GATE DRIVE FAIL
The Source 1 gate drive module failed.
D, A, E
020
S2 GATE DRIVE FAIL
The Source 2 gate drive module failed.
D, A, E
021
INTERNAL COMM FAIL
Internal CAN communications failed.
D, A, E
022
EXTERNAL COMM FAIL
Options CAN communications failed.
A, E
023
CB1 SHUNT TRIP FAIL
CB1 shunt trip failed.
A, E