STS2 Touch Screen Display
100
4 Pole Transfer Switch
This selection is set at the factory to indicate whether the system is a 3 pole or 4 pole unit.
Shunt
This selection is set at the factory.
Wye Output Transformer
The Wye Output Transformer controls the firing of the SCRs on startup, which minimizes the inrush
into PDU transformers. Output breakers and PDU input breakers have to be closed when you start
up the system. Based on whether the input side of the PDU transformer is configured as a Wye or
Delta changes the firing sequence of the SCRs.
If the STS2 is connected to a PDU configured as a Wye:
• Select YES for the Wye Output Transformer choice in the System Options dialog box.
Remote Source Selection
If your system is configured with the optional Remote Source Selection, it must be enabled from the
System Options menu. See
5.5 - Remote Source Selection Wiring
for more information.
If the system is utilizing Remote Source Selection:
• Select YES for the Remote Source Selection choice in the System Options dialog box to activate
the option.
System ID
Most of the settings for System ID are set by Liebert either at the factory or when the unit is
installed.
Order No., System Tag No., System ID No. and Model No. are the numbers used to identify and track
the system.
Language, Time and Date are synchronized with the location of the unit.
The only configurable field is the Password. See
Using the Password on page 87
for more informa-
tion on configuring and using the password.