36
NIC Setup and Testing
RTU Framing Examples
READ REGISTERS (FUNCTION CODE 0X03 &
0X04)
Query:
for reading holding /input registers (requested by a client)
Server
Addres
s
Function
Code
(0x3/0x4)
Index of
starting register
Number of
registers to be read
16 bit
CRC
1 byte
1 byte
2 bytes
2 bytes
2
bytes
Response:
for reading holding/input registers (response by the server)
Server
Addres
s
Function
Code
(0x3/0x4)
Byte
Count
Data from registers
16 bit
CRC
1 byte
1 byte
1
bytes
2*m bytes (= Byte Count)
2 bytes
WRITE SINGLE HOLDING REGISTER
(FUNCTION CODE 0X06)
Query:
for writing a single holding register (requested by a client)
Server
Addres
s
Function
Code
(0x06)
Index of the
register
16 bit value to
be written
16 bit CRC
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Response:
for writing a holding registers (response by the server)
Server
Addres
s
Function
Code
(0x06)
Index of the
register
16 bit value
been written
16 bit CRC
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Содержание OpenComms
Страница 1: ...1 LIEBERT MONITORING GROUP INSTALLATION USER MANUAL Network Interface Card OpenComms...
Страница 2: ......
Страница 10: ...Installation 9 Figure 2 Deluxe System 3 Control Cavity Figure 3 Deluxe System 3 Chilled Water Control Cavity...
Страница 11: ...10 Installation Figure 4 ICS Control Cavity...
Страница 17: ...16 Installation Figure 7 Npower UPS Installation...
Страница 28: ...NIC Setup and Testing 27 DS13 IGM Port Transmit DS14 19 Not used Figure 8 LED Locations...