Installation
6
3.0
I
NSTALLATION
3.1
Preparation
Inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Emer-
son representative.
The Liebert PSI may be installed in either a tower or rack configuration. Determine the method that
suits the application and proceed.
Decide where to install the Liebert PSI. The UPS must be installed indoors in a controlled environ-
ment. Place it in an area with unrestricted airflow around the unit, away from water, flammable liq-
uids, gases, corrosives and conductive contaminants (see
Figure 5
).
Maintain a minimum clearance of 305mm (12 inches) in the front and rear of the UPS. Maintain an
ambient temperature range of 0°C to 40°C (32°F to 104°F) (see
Figure 5
).
Figure 5
Placing the Liebert PSI
!
CAUTION
Risk of injury from heavy unit. May cause equipment damage or personal injury.
The UPS is heavy (see
Table 5
). Take proper precautions when lifting or moving the UPS.
0°C (32°F)
Relative humidity
(non-condensing)
40°C (104°F)
0% ~ 90%
305mm/12
inch
AIR
AIR
AIR