INTRODUCTION

Your Liebert Little Glass House™ (LGH) will
provide a secure controlled environment in a
single factory assembled enclosure.  The
integrated/matched models are designed to
control the environment and provide smooth
reliable power so that your sensitive computer
and network equipment will provide the reliable
performance you depend upon for your business
operations.

The Little Glass House is completely factory
assembled and tested, ready for you to install
your equipment and plug the unit into a 120 V~/
60 Hz or 230 V~/ 50 Hz dedicated outlet.  For 60
Hz models, the required power
receptacle/socket may be 15, 20, or 30 Amps,
depending on your selected LGH.  Models with
60 Hz ECM-80 uses two input power
connections, with one 20 Amp plug for the ECM-
80 and the other plug either 15 or 20 Amps
depending on the UPS model.  For 50 Hz
models, a power cord is included for connection
to a customer supplied plug.

Refer to drawings and tables in this manual for
dimensions, environmental performance data,
and input power requirements.  Refer to the
separate UPS manual for UPS performance
details.

ENCLOSURE

The enclosure can accommodate shelf mounted
or rack mounted equipment, on either 19 or 24
inch punched rails (per EIA-310).  The 19 inch
rack cabinets are 25 inches (635 mm) wide.
Cabinets with 24 inch racks are 30 inches (765
mm) wide.  The enclosures can be nominal 72
or 78 inches (1830 or 1980 mm) high, and 34 or
38 inches (865 or 965 mm) deep.  The unit is
mounted on casters and leveling feet.  Interior
insulation is provided in models with
Environmental Control Module (ECM) cooling.

A solid panel (metal) front door is standard.  A
smoked plastic front window is available to
maintain enclosure security while allowing you to
monitor equipment status.  The rear door
provides convenient access to customer wiring.
Two horizontal cable entrance raceways are
provided.  An optional internal cable
management raceway (vertical) is available.
Both doors have a key lock and a four point
latch.

ENVIRONMENTAL CONTROL

The Uninterruptible Air Supply™ (UAS) consists
of an Environmental Control Module (ECM) and
a Back-up Cooling Fan.  The ECM is normally
sized to match the capacity of the UPS module
plus heat transmitted into the LGH.  Three ECM
modules, ECM-42, ECM-62, and ECM-80 are
available.  Air is controlled and circulated within
the enclosure.  Outside (ambient) air is used to
remove heat from the enclosure through the air
cooled condenser.  Two-speed fans are used to
provide quiet operation.  At rated maximum
ambient conditions, the temperature inside the
enclosure will be from 70° to 95°F (21 to 35°C),
depending on the electronics load.  If the internal
cabinet temperature reaches 100°F (38°C) -- for
example, during a power failure -- the Back-up
Cooling Fan operated on UPS battery power will
flow filtered ambient air through the enclosure.

The Back-up Cooling Fan is standard on UAS
models.  All UAS or ECM models require a
clearance of 12 inches (305 mm) both on top
and rear of the LGH for proper airflow.  The 50
Hz back-up cooling options have an On/Off (O/I)
switch located in the inlet channel to the ECM
condenser coil.  This switch should be on during
normal operation.

If environmental control as previously described
is not required, Forced Air Cooling (FAC) is
available.  Filtered ambient air is drawn through
the enclosure from the bottom front to the top
rear.  A two-speed fan is controlled by a
thermostat factory set at 80°F (27°C), which
measures air entering the unit.  The two-speed
fan design provides quiet low-speed operation
below the thermostat set point.  A single fan
(nominally rated at 190 CFM - 323 CMH) or dual
fans (nominally rated at 360 CFM - 611 CMH)
can be provided.  A clearance of 12 inches (305
mm) is required both on top and rear of the LGH
for FAC models.

Содержание Integrated Secured Protection

Страница 1: ...USER MANUAL English Integrated Secured Protection for Network Equipment Little Glass House ...

Страница 2: ... AIR COOLING FAC PERFORMANCE DATA WITH 30PPI FILTER 11 ENVIRONMENTAL COOLING MODULE ECM PERFORMANCE DATA 11 FIXED SERVICE CONNECTION AMPS 12 MAX AVAILABLE CUSTOMER EQUIPMENT AMPS 12 FULL LOAD AMP DRAW 230V 50HZ 12 DRAWINGS 13 TROUBLESHOOTING 23 Model Number Breakdown RD 78 38 M D E K Enclosure Rack Width Enclosure Height Depth Main or Cluster Primary Cooling System UPS Rack Mount Input Power RD 24...

Страница 3: ...lies with the requirements of the EMC Directive 89 336 EEC and the published technical standards Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories with output cables not exceeding 10 meters 30 ft in length Use a shielded cable for the external communications interface 7 Route power supply cords so they are not walked o...

Страница 4: ...convenient access to customer wiring Two horizontal cable entrance raceways are provided An optional internal cable management raceway vertical is available Both doors have a key lock and a four point latch ENVIRONMENTAL CONTROL The Uninterruptible Air Supply UAS consists of an Environmental Control Module ECM and a Back up Cooling Fan The ECM is normally sized to match the capacity of the UPS mod...

Страница 5: ...and connection locations for your model Carefully unload your new Little Glass House LGH from the box and from the pallet Note the unit weight for your model Use at least two people for safe handling Unloading Procedure 1 Cut bands Use caution 2 Remove cardboard and plastic 3 Remove two 2 X 4 s from sides of unit 4 Remove one 2 X 6 from rear of unit 5 Remove four lag bolts from front of skid 6 Rem...

Страница 6: ...larms High Temperature 100 F 38 C internal Back up Cooling Fan operating and Dirty Air Filter filter is clogged and requires cleaning Customer connection is two compression lug terminals inside the rear of the unit These normally open contacts are rated for 40 milliAmps at 30 volts maximum Class 2 wiring A contact is provided on the rear of the ECM to indicate power to the compressor Compressor on...

Страница 7: ...lation Route customer wiring through the two horizontal cable entrance raceways An optional internal cable management raceway vertical is available START UP Before applying power make sure the computer equipment and power switches are in the OFF position Plug the Little Glass House power cable into the customer provided receptacles sockets Be certain there are no obstructions such as wires conduit...

Страница 8: ...ugh a louver and filter at the bottom front of the unit and is discharged at the rear near the top FORCED AIR COOLING FAC Forced Air Cooling can be provided by a single fan nominally rated at 190 CFM 323 CMH or by dual fans nominally rated at 360 CFM 611 CMH The two speed fans are activated by a temperature switch Ambient air is drawn through the filter at the bottom front of the unit and discharg...

Страница 9: ... normally open contacts and the ECM power terminal strip terminals 37 38 in the rear of the ECM A two conductor control cable is connected between the power supply terminal strips marked Close to Energize Relay R1 and the Relay Output K1 terminal strip on the rear of the SiteNet Integrator When the relay output contacts on the SiteNet Integrator close the relay in the power supply is energized clo...

Страница 10: ...ntil after ECM has been removed Models containing a 60 Hz ECM80 require the removal of the plug from the ECM power cord Once removed the power cord strain relief may be loosened to allow the power cord to slide through when the ECM is withdrawn from the cabinet Observe wiring polarity when reinstalling the plug on the replacement unit If connected remove customer wiring to ECM compressor power con...

Страница 11: ... Rack In mm BTUH Watt 120V 60Hz 220V 50Hz lbs Kg ECM 42 4200 1230 2730 800 105F 41C 100F 38C 6 10 5 265 17 5 445 19 27 685 7625 2235 8 15 15 7 15 15 95 43 ECM 62 6200 1815 4095 1200 105F 41C 100F 38C 7 12 3 310 22 560 24 27 685 11310 3315 12 20 20 9 15 15 115 52 ECM 80 8000 2345 5800 1700 105F 41C 100F 38C 9 15 8 400 22 560 24 29 735 14605 4280 16 20 20 16 20 20 167 76 ECM Notes Standard Offerings...

Страница 12: ...based on the Cooling System and customer Amp load MAX AVAILABLE CUSTOMER EQUIPMENT AMPS based on customer selected Service Connection SERVICE CONNECTION Cooling System 15 Amp 20 Amp 30 Amp FAC 190 11 5 15 5 23 5 FAC 360 11 15 23 ECM 42 only 8 16 UAS 42 7 15 ECM 62 only 12 UAS 62 10 UAS ECM 80 Power strip is rated for 15 Amp service 50 Hz Systems with NO UPS or WITH UPS Full Load Amp Draw The 50 Hz...

Страница 13: ...13 DRAWINGS ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...16 ...

Страница 17: ...17 ...

Страница 18: ...18 ...

Страница 19: ...19 ...

Страница 20: ...20 ...

Страница 21: ...TERNAL LOAD PER CABINET WATTS MINIMUM SPEED SET AT 2000 RPM LGH RD HD FORCED AIR CABINET TEMP RISE AT STANDARD AIR CONDITIONS TEMP RISE PER CABINET DEG F FAC 360 2 FAN HIGH SPEED FAC 190 1 FAN HIGH SPEED FAC 360 2 FAN LOW SPEED FAC 190 1 FAN LOW SPEED ...

Страница 22: ...22 INTEGRATOR POWER UPS TERMINAL CONNECTIONS ...

Страница 23: ...led Replace ECM If electrical component has failed causing compressor not to run replace component Excessive opening of doors Reduce the amount of opening Suggest external keyboard tray Turn ECM off when opening door Enclosure not properly sealed Verify leak and fix or replace gasket Condensate draining continuously Evaporator drain kinked or clogged Remove ECM and verify plastic tubing is attache...

Страница 24: ...rged every 4 to 6 months if not in use Circuit breaker resetting is not covered by this warranty and may indicate use beyond capability of the product No warranty applies to products which have been abused mishandled modified damaged by act of God or source external to the product repaired by others or which have product serial numbers removed or altered There are no warranties other than that des...

Страница 25: ...VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service and support through more than 100 service centers around the world and a 24 hour Customer Response Center Integrated Secured Protection for Network Equipment Little Glass House While every...