FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER)
AIRFLOW (w/Filter)
SOUND LEVEL
INPUT POWER (1PH)
FLA / WSA / OPD
MODEL #
# FANS
HIGH
SPEED
LOW
SPEED
HIGH
SPEED
LOW
SPEED
120V/60Hz
220V/50Hz
FAC-190
1
190 CMF
112 CMH
90 CMF
53 CMH
61 dBa
47 dBa
0.5/15/15
0.5/15/15
FAC-360
2
360 CMF
212 CMH
175 CMF
103 CMH
59 dBa
49 dBa
1.0/15/15
1.0/15/15
ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA
RATED
CAPACITY
SUPPORT
LOAD
RATED/MAX
AMBIENT
HEIGHT
DIMENSIONS
WIDTH
DEPTH
TOTAL
HEAT REJ.
INPUT POWER (1PH)
WEIGHT
MODEL
NUMBER
BTUH/Watt
BTUH/Watt
60Hz
50Hz
U
In/mm
In/mm
Rack
In/mm
BTUH/Watt
120V/60Hz
220V/50Hz
(lbs/Kg)
ECM-42
4200/1230
2730/800
105F
41C
100F
38C
6
10.5/
265
17.5/
445
19
27/
685
7625/
2235
8/15/15
7/15/15
95/43
ECM-62
6200/1815
4095/1200
105F
41C
100F
38C
7
12.3/
310
22/
560
24
27/
685
11310/
3315
12/20/20
9/15/15
115/52
ECM-80
8000/2345
5800/1700
105F
41C
100F
38C
9
15.8/
400
22/
560
24
29/
735
14605/
4280
16/20/20
16/20/20
167/76
ECM Notes:
Standard Offerings - All Systems
1. 60Hz: R-22 refrigerant / 50Hz: R-134A refrigerant
2. Two-Speed Operation - Switch low-high speed on ambient temperature external to LGH enclosure
3. Automatic Load Matching: Hot gas by-pass factor set for minimum capacity; by-pass will adjust to
match supported loads
4. Condensate Re-evaporation & Removal: Drain connection only required if enclosure seal is violated.
Содержание Integrated Secured Protection
Страница 1: ...USER MANUAL English Integrated Secured Protection for Network Equipment Little Glass House ...
Страница 13: ...13 DRAWINGS ...
Страница 14: ...14 ...
Страница 15: ...15 ...
Страница 16: ...16 ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 ...
Страница 20: ...20 ...
Страница 22: ...22 INTEGRATOR POWER UPS TERMINAL CONNECTIONS ...