Hinet UPS User Manual
Page 22
(06/01)
WARNING
The operations described in the paragraphs that follow must be carried out by authorised electricians or trained
personnel
5.2.1
UPS Start-Up instructions
This procedure should be followed when turning on the UPS from a fully powered down condition - i.e. where the load
is not being initially supplied at all. It is assumed that the installation is complete, the system has been commissioned by
authorised personnel and the external power switches are closed. Refer to Fig. 5-1 for corresponding switches
?
to
?
.
Before activating the UPS check that the lever of the MANUAL BY-PASS switch has been lowered and mechanically
locked (a safety padlock can be eventually used).
ENSURE CORRECT PHASE ROTATION.
Before activating the UPS operate the switches following the order given below:
1. Open the UPS door to have access to the main power switches.
2. Switch ON RESERVE INPUT switch
?
;
3. Switch ON the UPS OUTPUT switch
?
;
- wait the fan running, so the voltage is present to the output
4. Switch ON the INPUT MAINS switch
?
;
5. Switch ON the BATTERY switch
?
.
5.2.2
Inverter Turn-on and LCD panel LEDs activation
When switching ON, the UPS will set to the automatic By-pass condition (yellow LED BYPASS
ON
) thus producing a
generic alarm (red LED ALARM
ON
and buzzer alarm activated).
-
Press the key to mute the buzzer.
-
The LCD displays the alarm INVERTER OFF .
-
To start the inverter press the MENU button then, when the COMMAND MODE appears, press both next & back
buttons (ENTER) and than press ENTER again to turn-on the inverter.
LED status when switching ON the UPS
a) green NORMAL ON
b) green LOAD ON INVERTER ON (Inverter running)
c) yellow LOAD ON BYPASS OFF
d) red ALARM OFF
5.2.3
Load insertion test
Dummy loads are suggested to be used till reaching the maximum UPS power.
The LCD panel will display the corresponding current and output power in the STATUS ALARM MENU .
WARNING
The ALARM MESSAGE “ INVERTER OVERLOAD” means that the UPS is overloaded (the load connected
exceeds the rated value: disconnect the load in excess, restart the inverter (point 5.22) and reset the alarm.
WARNING
Wait at least 5 minutes after Shutting Down the Hinet before proceeding with the Starting Up procedure.
The UPS is operating normally and the inverter is supplying the load.
Содержание Hinet 10kVA
Страница 2: ......
Страница 7: ...USER MANUAL Hinet UPS System 12 01 Page V...
Страница 10: ......
Страница 14: ...Hinet UPS User Manual Page 4 12 01...
Страница 22: ...Hinet UPS User Manual Page 12 12 01...
Страница 30: ...Hinet UPS User Manual Page 20 12 01...
Страница 37: ...Hinet UPS User Manual Chapter 6 Optional Equipment 01 Page 27...