3.2.5 UPS Monitoring
UPS intelligent communication
The HINET UPS has the capability to communicate intelligently with stand alone computers, network workstations,
network servers, or UNIX hosts via the DB-9 female connector located at the rear of the UPS. With the RS-232
Liebert cable and the software Multlink 3.0 the following features will be available:
??
Quantitative monitoring of mains and UPS power
??
Quantitative monitoring of internal UPS parameters
??
Periodic tests of battery quality and replacement notification
??
Timed and delayed shutdown of the UPS
??
Logging of power disturbances and anomalies
Consult your local Liebert sales representative for more information about Multilink 3 software.
UPS intellislot™ Communication
The HINET UPS contains an Intellislot™ communications port for the optional internal Ethernet SNMP card.
The Intellislot SNMP Card provides SNMP-based management to your UPS. The card gives you the power to monitor
and control your Liebert UPS from your Network Management Station or Multilink 1.5.
The Intellislot SNMP card allows you to monitor the power and the operating state of your UPS.
The Intellislot SNMP card integrates into your SNMP implementation and supports the UPS open standard MIB that is
distributed with most Network Management Systems. Starting with our support of open standards as a baseline, the
Intellislot SNMP card goes a step further and extends with the Liebert Global Products MIB, which provides you
Liebert-specific advanced SNMP monitoring and control capabilities.
CAUTION:
TO MAINTAIN SAFETY (SELV) BARRIERS AND FOR ELECTROMAGNETIC COMPATABILITY, SIGNAL
CABLES SHOULD BE SEGREGATED AND RUN SEPARATE FROM ALL OTHER POWER CABLES, WHERE APPLICABLE.
Intellislot
DB9 Relay Card 1
DB9 Relay Card 2
Содержание Hinet 10kVA
Страница 2: ......
Страница 7: ...USER MANUAL Hinet UPS System 12 01 Page V...
Страница 10: ......
Страница 14: ...Hinet UPS User Manual Page 4 12 01...
Страница 22: ...Hinet UPS User Manual Page 12 12 01...
Страница 30: ...Hinet UPS User Manual Page 20 12 01...
Страница 37: ...Hinet UPS User Manual Chapter 6 Optional Equipment 01 Page 27...