Hinet UPS User Manual
(12/01)
Page 17
The List of possible Alarm and the associate help messages is displayed below.
ALARM MESSAGE
CAUSE
ACTION
INVERTER OFF
Initial Start Up
Permanent Overload has been
detected
Start the Inverter
Check Output
INVERTER OVERLOAD
Continuos Overload on UPS Output
Check Output Load and Restart
Inverter
Check for Output Short-Circuit
BYPASS SWITCH LOCKED
High Transient Loads on UPS
Output. Inrush Load Current
After 3 times
Check Output Load and Restart
Inverter
BATTERY FAILURE
Battery Test not OK
Check Battery
Check Battery fuses
INVERTER SHUT-DOWN
IMMINENT
Battery almost flat, next to
Shut-Down of inverter
Make shut-down to the connected
Loads
BYPASS SWITCH FAILURE
One or more Phases in the Output
are missing
Check SCR of Bypass
Check Bypass external connections
MANUAL BYPASS ON
UPS on Maintenance
MAIN OUT OF LIMITS
Breaker is Open
Main Input is missing
Check Main line Voltage and
Breaker position
BYPASS LINE OUT OF
LIMITS
The input phase rotation is not
correct
Input Voltage Missing
Check Bypass line Voltage
Check Phase Rotation
EMERGENCY POWER OFF
The Command EPO has been
selected
Restart the UPS
Fully switch-off the Breakers and
the Battery Fuse, wait till the LCD
is complete switch-off then restart
the UPS
BATTERY NOT CONNECTED
Battery Switch Open
Battery Test Failed
BATTERY CHARGER FAULT
Call Service Office, to replace the
Battery Charger
HIGH BATTERY VOLTAGE
LEVEL
Battery Charger in Fault
Call Service Office, to replace the
Battery Charger
END OF BATTERY DISCHARGE
Main is missing for long time
4.2.3
COMMAND MODE MENU
In this menu is possible to give some operative command to the UPS.
MESSAGE
INTERPRETATION
BATTERY TEST
With this message displayed by pressing ENTER an automatic test on the Battery
will be performed instantaneously
SWITCH LOAD
With this message displayed by pressing ENTER the load is switched from inverter
to the Bypass Line. This command is also used for reset the alarm conditions on the
bypass line. For instance when the Alarm Bypass Switch Locked is present because
for three consecutive times the load has been connected to Bypass for transient
overload. To reconnect the load on inverter is necessary to activate this command by
ENTER
INVERTER ON/OFF
With this message displayed by pressing ENTER the User can Turn-on or Turn-off
the Inverter in a permanent way and connect it to the Load.
It is necessary Turn-on the Inverter at the start-up and after a permanent overload.
Содержание Hinet 10kVA
Страница 2: ......
Страница 7: ...USER MANUAL Hinet UPS System 12 01 Page V...
Страница 10: ......
Страница 14: ...Hinet UPS User Manual Page 4 12 01...
Страница 22: ...Hinet UPS User Manual Page 12 12 01...
Страница 30: ...Hinet UPS User Manual Page 20 12 01...
Страница 37: ...Hinet UPS User Manual Chapter 6 Optional Equipment 01 Page 27...