The List of possible Alarm and the associate help messages is displayed below. 

 

ALARM MESSAGE 

CAUSE 

ACTION 

INVERTER OFF 

Initial Start Up  
Permanent Overload has been 
detected  

Start the Inverter 
Check Output 

INVERTER OVERLOAD 

Continuos Overload on UPS Output 
 

Check Output Load and Restart 
Inverter 
Check for Output Short-Circuit 

BYPASS SWITCH LOCKED 

High Transient Loads on UPS 
Output. Inrush Load Current 
After 3 times  

Check Output Load and Restart 
Inverter 
 

BATTERY FAILURE 

Battery Test not OK 

Check Battery  
Check Battery fuses 

INVERTER SHUT-DOWN  
IMMINENT 

Battery almost  flat, next to  
Shut-Down of inverter 

Make shut-down to the connected 
Loads 

BYPASS SWITCH FAILURE 

One or more Phases in the Output 
are missing 

Check SCR of Bypass 
Check Bypass external connections 

MANUAL BYPASS ON 

UPS on Maintenance 

 

MAIN OUT OF LIMITS 

Breaker is Open 
Main Input is missing 

Check Main line Voltage and 
Breaker position 

BYPASS LINE OUT OF 
LIMITS 

The input phase rotation is not 
correct 
Input Voltage Missing 

Check Bypass line Voltage 
Check Phase Rotation 

EMERGENCY POWER OFF 

The Command EPO has been 
selected 

Restart the UPS 
Fully switch-off the Breakers and 
the Battery Fuse, wait till the LCD 
is complete switch-off then restart 
the UPS 

BATTERY NOT CONNECTED 

Battery Switch Open 
Battery Test Failed 

 

BATTERY CHARGER FAULT 

 

Call Service Office, to replace the 
Battery Charger 

HIGH BATTERY VOLTAGE 
LEVEL 

Battery Charger in Fault 

Call Service Office, to replace the 
Battery Charger 

END OF BATTERY DISCHARGE 

Main is missing for long time 

 

 

4.2.3 

COMMAND MODE MENU 

In this menu is possible to give some operative command to the UPS. 

 

MESSAGE 

INTERPRETATION 

BATTERY TEST 

With this message displayed by pressing ENTER an automatic test on the Battery 
will be performed instantaneously  

SWITCH LOAD 

With this message displayed by pressing ENTER the load is switched from inverter 
to the Bypass Line. This command is also used for reset the alarm conditions on the 
bypass line. For instance when the Alarm Bypass Switch Locked is present because 
for three consecutive times the load has been connected to Bypass for transient 
overload. To reconnect the load on inverter is necessary to activate this command by 
ENTER 

INVERTER ON/OFF 

With this message displayed by pressing ENTER the User can Turn-on or Turn-off 
the Inverter in a permanent way and connect it to the Load.  
It is necessary Turn-on the Inverter at the start-up and after a permanent overload.  

 

 

Содержание Hinet 10kVA

Страница 1: ...Manual Reference number 6390001 H 2 12 01 RevENPAu07 2002 H HI IN NE ET T U UP PS S S SY YS ST TE EM M 1 10 0 3 30 0 k kV VA A 3 3x x1 1 U Us se er r M Ma an nu ua al l...

Страница 2: ......

Страница 3: ...rter 1 Frequency Converter 3 Harmonic Filter 0 No 3 Harmonic Filter 1 3 Harmonic Filter THDi Reduction Filter 0 No THDi Reduction Filter 1 THDi filter for 10kVA Unit 2 THDi filter for 15 20kVA Unit 3...

Страница 4: ...HNBATTCAB 38Ah 5 Years Batteries for External Battery Cabinet 32 Bloks x 12V HN38AH5Y 65Ah 5 Years Batteries for External Battery Cabinet 32 Bloks x 12V HN65AH5Y Hinet Additional Communications Card K...

Страница 5: ...must be protected from rain or excessive moisture and installed in a clean environment free from flammable liquids gasses or corrosive substances Do not put drinks plants or any other containers holdi...

Страница 6: ...service batteries e Eye protection must be worn to prevent injury from accidental electrical arcs f Remove rings watches necklace s bracelets and all metal objects g Only use tools with insulated hand...

Страница 7: ...USER MANUAL Hinet UPS System 12 01 Page V...

Страница 8: ...ting options on the standard Relay Card 9 3 2 2 Remote EPO Emergency Power Off 10 3 2 3 Emergency Power Off E P O push button connection 10 3 2 4 Connection to Personal Computer 10 3 2 5 UPS Monitorin...

Страница 9: ...NPUT FILTER FOR CURRENT THD REDUCTION INTERNAL OPTION 28 7 6 INPUT 3 HARMONICS FILTER INTERNAL OPTION 28 7 7 INTERNAL EXTENDED BATTERY KIT 28 7 8 BATTERY CONNECTING KIT 28 7 9 EXTENDED BATTERY CABINET...

Страница 10: ......

Страница 11: ...steel frame with removable panels The door can be open to give easy access to the input bypass output reserve line circuit breakers and battery C B fused switch while protecting them from accidental...

Страница 12: ...d UPS fault In the event of an inverter failure the automatic by pass will automatically transfer the load onto the mains with no interruption In such an event request qualified technical assistance T...

Страница 13: ...the Common Bypass configuration In the Split Bypass configuration the static bypass line is connected by a separate power switch to a dedicated bypass power source that also feeds the maintenance byp...

Страница 14: ...Hinet UPS User Manual Page 4 12 01...

Страница 15: ...emove the extruded elements utilised as packing protection Use the extractor to remove all lateral sides of the crate Slide the forks of the lift truck under the UPS and after having lifted it a few c...

Страница 16: ...nce around the front of the equipment should be sufficient to enable free passage of personnel with the door fully opened 2 1 7 Raised floor installation If the equipment is to be located on a raised...

Страница 17: ...arthed in accordance with local regulations WARNING FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC SHOCK HAZARD TO PERSONNEL OR THE RISK OF FIRE SHOULD AN EARTH FAULT OCCUR BEFO...

Страница 18: ...ut Mains phase V1 4 Input Mains phase W1 5 Input Mains Neutral N1 6 Input Reserve Bypass phase U3 7 Input Reserve Bypass Neutral N3 8 Battery Positive ext Battery input 9 Battery Negative ext Battery...

Страница 19: ...side of the rear panel This card is typically supplied and is factory pre set to operate with the PC When the operation is through the Remote Alarm Panel the factory will deliver the card already pre...

Страница 20: ...nnel must remove protection panel held in place with screws 3 2 3 Emergency Power Off E P O push button connection Refer to figure 3 2 to make a push button connection to the standard Relay Card 1 Get...

Страница 21: ...ntellislot communications port for the optional internal Ethernet SNMP card The Intellislot SNMP Card provides SNMP based management to your UPS The card gives you the power to monitor and control you...

Страница 22: ...Hinet UPS User Manual Page 12 12 01...

Страница 23: ...sists in a LCD display that indicates the operational and alarm status of the UPS and the EPO push button that is located at the left side The LCD Display Panel displays textual messages and operating...

Страница 24: ...menu the User may have access to different menu pressing the MENU Button second level Once in this level the first row will show menu choice and the NEXT and BACK push Button enable the User to move f...

Страница 25: ...BACK CLOCK NEXT UPS CONFIGURATION NEXT BACK BATTERY TEST NEXT BACK SWITCH LOAD NEXT INVERTER ON OFF NEXT BACK DISPLAY EVENTS NEXT DELETE EVENTS ENTER NEXT BACK ITALIAN NEXT BACK ENGLISH NEXT FRENCH NE...

Страница 26: ...he inverter LOAD ON BYPASS The load is supplied from the bypass line This can be a temporary condition lasting for 20 sec when a fast overload occurs UPS in Alarm In case of a failure in the UPS the d...

Страница 27: ...estart the UPS Fully switch off the Breakers and the Battery Fuse wait till the LCD is complete switch off then restart the UPS BATTERY NOT CONNECTED Battery Switch Open Battery Test Failed BATTERY CH...

Страница 28: ...ENTER CLEAR ENTER CLEAR DATE TIME LAST EVENT EVENT CANCELLED BACK CLEAR DATE TIME PREVIOUS EVENT N 1 BACK CLEAR DATE TIME PREVIOUS EVENT N 2 MENU MENU ENTER EVENT CANCELLED ENTER EVENT CANCELLED ENTER...

Страница 29: ...scroll consecutive numbers use BACK and NEXT buttons to move on the left use MENU button Then type the whole Date and press ENTER to confirm If something is wrong in the Date or Time the message ERRO...

Страница 30: ...Hinet UPS User Manual Page 20 12 01...

Страница 31: ...net The location of the UPS power switches is shown in Figure 5 1 The UPS power switches are INPUT MAINS SWITCH connects the UPS to the mains input supply RESERVE SWITCH Bypass connects the UPS to the...

Страница 32: ...T MAINS switch 5 Switch ON the BATTERY switch 5 2 2 Inverter Turn on and LCD panel LEDs activation When switching ON the UPS will set to the automatic By pass condition yellow LED BYPASS ON thus produ...

Страница 33: ...the load from the UPS inverter output to the maintenance bypass system This may be required during UPS maintenance procedures The manual bypass allows to exclude the UPS while still keeping the load...

Страница 34: ...ff MAINTENANCE BYPASS switch manual 6 switch on the inverter pressing ENTER in the INVERTER ON OFF display The load is once again powered from Hinet Place the mechanical lock and eventually the pad lo...

Страница 35: ...Voltage Adjustment Range Nominal 5 Output Voltage Stability Static Balanced Load Dynamic 50 Load Step Dynamic 100 Load Step 1 3 5 Output Voltage Transient Recovery Time 30ms to 3 RMS Output Voltage Di...

Страница 36: ...luding Battery Charging 50 Linear Load 100 Linear Load 88 91 88 91 89 92 90 92 Full Load Inverter Efficiency 94 94 94 94 Operating Temperature Range 0 40 C 20 C for optimal battery life time Storage T...

Страница 37: ...Hinet UPS User Manual Chapter 6 Optional Equipment 01 Page 27...

Страница 38: ...installation unit configuration 7 4 Isolation Transformer Internal Option The isolation transformer in a star star configuration can be connected either in the input or output side This Item is place...

Страница 39: ...ttery harness Frontal cover metallic plates to protect internal connections fixed by screw 8 mm size The total weight of the cabinet full of battery 65Ah is 900 kg Battery Assembling Instruction 1 Pla...

Страница 40: ...V Dimensions mm L 197 W 165 H 170 over Terminals Weight 13 9 kg Terminal D 5 5mm or M5 To Terminal blocks UPS Position Length Quantity Type 1 150 mm 16 Connection 1 2 800mm 12 Connection 2 3 1400mm 3...

Страница 41: ...S UPS On Green On Off Inverter operating Off On Inverter not operating On Bypass Amber On Off Load is being supplied through the bypass Off Off Load is not being supplied through the bypass On Battery...

Страница 42: ...ngement as shown below PIN ASSIGNMENT DESCRIPTION 1 NC Low Battery 2 NO UPS Run 3 NO Bypass ON 4 NC Main Status 5 COM 7 12 Frequency Converter Allow to have 50Hz Input and 60Hz Output or vice versa No...

Страница 43: ...ed modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanying instruc...

Отзывы: