Specifications

31

Static Switch

Nominal frequency

50/60 Hz auto selection

Frequency tolerance

±3.5 Hz

Voltage tolerance

100V - 280V

Out-of-phase switching time (ms) in case of inverter 
fault and bypass is out of tolerance

No transfer

Overload

Overload > 100%

Audible alarm

In-phase switching time - direct/conditioned (ms)

4

Zero break

Condition/direct

Zero break

105% to 130%

1 minute

131% to 150%

10 seconds

151% to 200%

1 second

>200% (impact load)

At least 5 cycles

Maximum noise level at 1 meter front-side normal 
mode and battery mode

 50dBA

Degree of protection

IP20

Physical Characteristics

Dimensions, W x D x H, mm (in)

300 x 675 x 800 (11.8 x 26.6 x 31.5)

Color

Black

Weight with integrated batteries, kg (lb)

105 (231.5)

Battery

Optimum battery temperature, °C (°F)

15 - 25 (59-77)

Power output

8.5kW

Recommended number of cells

120

End of discharge

200VDC

Battery type

HR 1234W F2 12V / 8.5Ah

Battery number

20

Discharging time

5 minutes

Auto battery missing detection

Yes

External Battery Cabinet

1Set / 2Set

Battery type

HR 1234W F2 12V / 8.5Ah

Battery number, pcs.

40 / 80

Dimensions, W x D x H, mm (in)

300 x 675 x 800 (11.8 x 26.6 x 31.5)

Color

Black

Weight with integrated batteries, kg (lb)

162 (357)

Performance EN 62040-3

Dynamic characteristics

VFI - S S - 1 1 1

Step load response

Load 0% to 100% to 0%

±5% maximum, returns to static regulation within 200 ms.

Load 20% to 100% to 20%

±3% maximum, returns to static regulation within 200 ms.

Startup Operation

Input AC < 100VAC or greater than 280VAC

UPS will not start

Input >176 or less than 276

UPS start enabled

Load 0% to 100% to 0%

±5% maximum, returns to static regulation within 200 ms.

1. Maximum input power (normal V, R full load)

float (kVA) = [Pout (KW) / efficiency] / input_power_factor
Example for the 10kVA: float (kVA) = (7,0 / 0,91) / 0,95 = 8100VA

2. Recharge (kVA) = [(Pout (KW) / efficiency) + Pbattchargerinput] / input_power_factor

Example for the 10kVA: Pbattchargerinput = (2.5*268) / efficiency = (2.5*268) / 0,9 = 744W recharge (kVA) = 
[(7,0 (KW) / 0,91) + 744] / 0,95 = 8880VA

3. THDi measure method is applied to EN61000-3-2, 1995
4. In-phase switching time direct / conditioned means time line (bypass) transferring to inverter
5. The expected battery life is defined at 20°C. For every increment of 10°C, above 20°C, the expected life is halved

Table 10

UPS specifications (continued)

Specification

Value

Содержание GXT3-10000T230

Страница 1: ...AC Power For Business Critical Continuity Liebert GXT3 10000T230 User Manual 10kVA 50 60 Hz 230V...

Страница 2: ......

Страница 3: ...2 10 Clearance 7 2 11 Repacking the UPS 7 3 0 INSTALLATION 8 3 1 Electrical preparations 8 3 2 Current Table and Suggested Cable Sizes 8 3 3 Neutral Connection 9 3 4 External Protection and Isolating...

Страница 4: ...unctional Test 21 4 9 Remote Emergency Power Off 22 4 10 Self Tests 22 4 10 1 Lamp Test 22 4 10 2 Battery Test 22 5 0 MAINTENANCE 23 5 1 Testing Replacing and Disposing of Batteries 23 5 2 Easy Batter...

Страница 5: ...net 13 Figure 12 Overview of UPS tower 15 Figure 13 Control panel 16 Figure 14 System block menu structure 17 Figure 15 REPO connections 22 Figure 16 Removing front panel and unlocking battery trays 2...

Страница 6: ...iv...

Страница 7: ...e connected These battery extensions may be connected only to the compatible basic UPS unit WARNING Opening or removing the cover may expose you to lethal voltages within this unit even when it is app...

Страница 8: ...cted or disconnected during a thunderstorm Remote Emergency Power Off REPO input is located on the rear of the unit see 3 8 Ter minal Blocks for UPS When this connection is open the logic circuit will...

Страница 9: ...formity If required the EU Declaration of Conformity may be requested from Liebert NOTICE TO EUROPEAN UNION CUSTOMERS DISPOSAL OF OLD APPLIANCES This product has been supplied from an environmentally...

Страница 10: ...c equipment operates best from sinewave power For ease of use the Liebert GXT3 10000T230 features an LCD display for comprehensive user indica tions and programmable controls It also provides self dia...

Страница 11: ...0 For technical data about external battery cabinets see Table 10 UPS specifications For connection notices see Table 2 Connection data 1 2 2 Optional Interfaces Refer to 6 0 Communication for details...

Страница 12: ...d damaging the UPS Do not dispose of the packing material The original packaging material should be used if the UPS needs to be repackaged such as for shipping Check all packaging to ensure that no it...

Страница 13: ...ed will support the unit s weight see Table 10 for the unit s weight 2 9 Inventory List The Liebert GXT3 10000T230 comes with CD containing Liebert MultiLink Shutdown Software Configuration Software U...

Страница 14: ...bles WARNING Installation may be carried out only by qualified technicians conforming to applicable safety standards Electric shock hazard Even when the unit is disconnected from the mains hazardous v...

Страница 15: ...ed for the protection of both the cables and the equipment WARNING The following label must be displayed on all switching devices installed in the same electrical system as the UPS even when they are...

Страница 16: ...ove the protective panel on the rear of the UPS to access the external electrical connections see figure below Once the cables have been connected they must be passed through the cable clamps that wil...

Страница 17: ...t share a common conduit with input circuits or any other wiring The utility may be derived from a single phase or three phase source Figure 6 Input and output connections with single source single ph...

Страница 18: ...Figure 3 5 If the reserve input is to be supplied separately connect reserve line to the Mains 2 terminals If the UPS is supplied by a common mains connect the supplied jumper in the accessory kit ma...

Страница 19: ...d battery a compensating current may occur during connection Figure 11 Liebert GXT3 10000T230 with External Battery Cabinet 3 11 Connecting an External Battery Extension The unit checks the battery vo...

Страница 20: ...four months Since new batteries often do not provide full capacity after the initial charge it may be necessary to carry out a number of discharge recharge cycles before optimum performance is reache...

Страница 21: ...booster inverter and charger Internal electronic bypass 2 input breakers Maintenance bypass breaker TVSS filter Integrated battery expandable Figure 12 Overview of UPS tower L2 L3 at 10kVA device only...

Страница 22: ...u Press Enter to choose an entry Table 4 Lighted LEDs LED Indicator LED Color Description UPS ON Green UPS is online and operating normally BYPASS Amber Load is supplied by the mains via automatic byp...

Страница 23: ...Menu Setup Menu Status Menu Parallel Menu Language Tag Number UPS ID No DC Start Test Intvl Batt Pack Audible Alarm Output Volt No of Unit Control Menu Contrast Batt Test Alarm Ctrl UPS ON OFF Test Re...

Страница 24: ...ENU SysOutI A SysOutV V SysOutF Hz SysOutW W SysOutVA VA SysLoadPer SETUP MENU Setting item Setting level 1 Audible Alarm Disable Enable Output Volt 220V 230V 240V Batt Pack 1 4 Test intvl DC Start Di...

Страница 25: ...is window All fault displays include The nature of the event The time of the event The fault indicators are Table 6 Warning indicators Warning Cause Corrective Steps 1 No Redundancy 2 InvASynFault 3 P...

Страница 26: ...y external switches connecting the load if present 7 Press the Menu button select Control and press OK 8 Select Turn UPS ON OFF and press OK The LCD will display Turn ON 9 Press OK to switch On the in...

Страница 27: ...Before beginning ensure that the batteries are fully charged Simulate a mains failure by interrupting the mains supply to the UPS You can do this by switching Off the input power circuit breaker on t...

Страница 28: ...s mode A system confirmation beep will sound 4 10 2 Battery Test 1 Press the Menu button 2 Select Control and press OK 3 Select BATT TEST and press OK A system confirmation beep will sound and the loa...

Страница 29: ...al regulations and laws Exhausted accumulator batteries are classified as harmful toxic waste and as such the law demands that they be disposed of by an authorized recycling centre The Liebert power p...

Страница 30: ...Open the battery tray DC connectors as shown 2 Remove the battery trays from the cabinet 3 Replace the old batteries with a new set Replacement batteries must be the same type installed at the factory...

Страница 31: ...rcuit breaker of the UPS Then remove the UPS connections in the opposite sequence to that described in 3 0 Instal lation Record the battery charging date in the vicinity of the UPS for example on its...

Страница 32: ...Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the event history l...

Страница 33: ...d The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the net work The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applicati...

Страница 34: ...e on four comput ers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support fo...

Страница 35: ...t intervals No mains voltage present UPS operation control panel UPS on LED does not illuminate when mains voltage present audible alarm active at intervals Input fuse defective or input circuit break...

Страница 36: ...y nominal voltage VDC 240 Battery charger input voltage range VDC 100 276 Output voltage V Multi stage charging method Charging time to 90 capacity in inverter mode hr 3 Charger output current ADCaver...

Страница 37: ...ttery number pcs 40 80 Dimensions W x D x H mm in 300 x 675 x 800 11 8 x 26 6 x 31 5 Color Black Weight with integrated batteries kg lb 162 357 Performance EN 62040 3 Dynamic characteristics VFI S S 1...

Страница 38: ...Level 3 Criteria A Electrical Fast Transient EN61000 4 4 Level 4 Criteria A Surge Immunity EN61000 4 5 Level 3 Criteria A Transportation ISTA Procedure 1A Table 13 Operating temperature parameters Am...

Страница 39: ......

Страница 40: ...ive owners Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upst...

Отзывы: