Specifications
30
8.0
S
PECIFICATIONS
Table 10
UPS specifications
Specification
Value
Rectifier
GXT3-10000T230
Nominal input voltage, VAC
230VAC Single Phase (L,N,G)
230/400 Three Phase (L1,L2,L3,N,G)
Input phases, VAC
Single phase or three phase, automatic detection
Input voltage
176-280V for 1x1
304-485V for 3x1
Nominal frequency, Hz
50/60 Auto selection
Frequency tolerance
Output frequency equals input frequency. When the input
is nominal 50 or 60Hz ±3.5Hz. Beyond ±3.5Hz range,
inverter free runs at nominal frequency.
Maximum Input Power (Nominal Input Voltage, R Full Load)
Float (kVA)
1
9900VA for 1x1; 10100VA for 3x1
Recharge (kVA)
2
10460 VA for 1x1; 10900 VA for 3x1
Power factor (at nominal V, with R full load)
Single Phase Input: not less than 0.99
Three Phase Input: not less than 0.95
Input current distortion (with R full load) THDi
3
Single Phase Input: < 5%
Three Phase Input: < 31%
Inrush current (A) (typical)
67.5
Battery Charger
Battery nominal voltage, VDC
240
Battery charger input voltage range, VDC
100-276
Output voltage, V
Multi-stage charging method
Charging time to 90% capacity in inverter mode, hr.
3
Charger output current (A
DC
aver) (Amps)
Standard: 1.2A (1 Charger Board With Internal Batteries)
Option: 4.0A (internal option)
Inverter
Nominal power rating @40°C, kVA
10
Nominal active power rating, kW
9
Power factor
0.9
Overload - Inverter Mode
for 1 minute
for 10 seconds
for 1 second
At least 5 cycles
105 - 130%
131 - 150%
151 - 200%
> 200%
Overload - Bypass Mode
20- seconds
2 seconds or breaker capacity
130 - 150%
> 150%
Overload - Battery Mode
for 30-60 seconds
At least 5 cycles
105 - 125%
> 125%
Short-circuit current for 5 cycles, typical
160A
Output voltage rating, VAC
220, 230, 240
Output frequency, Hz
50/60, auto selection
Voltage regulation over input voltage and battery
voltage range with load between 0% and 100% of rating
±2%
Output frequency stability with mains synchronism (%)
±3.5 Hz
Stability with internal quartz oscillator
0.1 Hz
Frequency Variation Rate
< 1 Hz/sec
Output Voltage Distortion THD-V
Full Resistive load < 3%
Full RCD load < 5%
Load peak factor without derating
≤
3 lpk/lrms