Specifications

30

8.0

S

PECIFICATIONS

Table 10

UPS specifications

Specification

Value

Rectifier

GXT3-10000T230

Nominal input voltage, VAC

230VAC Single Phase (L,N,G)
230/400 Three Phase (L1,L2,L3,N,G)

Input phases, VAC

Single phase or three phase, automatic detection

Input voltage

176-280V for 1x1
304-485V for 3x1

Nominal frequency, Hz

50/60 Auto selection

Frequency tolerance

Output frequency equals input frequency. When the input 
is nominal 50 or 60Hz ±3.5Hz. Beyond ±3.5Hz range, 
inverter free runs at nominal frequency.

Maximum Input Power (Nominal Input Voltage, R Full Load)

Float (kVA)

1

9900VA for 1x1; 10100VA for 3x1

Recharge (kVA)

2

10460 VA for 1x1; 10900 VA for 3x1

Power factor (at nominal V, with R full load)

Single Phase Input: not less than 0.99
Three Phase Input: not less than 0.95

Input current distortion (with R full load) THDi

3

Single Phase Input: < 5%
Three Phase Input: < 31%

Inrush current (A) (typical)

67.5

Battery Charger

Battery nominal voltage, VDC

240

Battery charger input voltage range, VDC

100-276

Output voltage, V

Multi-stage charging method

Charging time to 90% capacity in inverter mode, hr.

3

Charger output current (A

DC

aver) (Amps)

Standard: 1.2A (1 Charger Board With Internal Batteries)
Option: 4.0A (internal option)

Inverter

Nominal power rating @40°C, kVA

10

Nominal active power rating, kW

9

Power factor

0.9

Overload - Inverter Mode

for 1 minute
for 10 seconds
for 1 second
At least 5 cycles

105 - 130%
131 - 150%
151 - 200%
> 200%

Overload - Bypass Mode

20- seconds
2 seconds or breaker capacity

130 - 150%
> 150%

Overload - Battery Mode

for 30-60 seconds
At least 5 cycles

105 - 125%
> 125%

Short-circuit current for 5 cycles, typical

160A

Output voltage rating, VAC

220, 230, 240

Output frequency, Hz

50/60, auto selection

Voltage regulation over input voltage and battery 
voltage range with load between 0% and 100% of rating

±2%

Output frequency stability with mains synchronism (%)

±3.5 Hz

Stability with internal quartz oscillator

0.1 Hz

Frequency Variation Rate

< 1 Hz/sec

Output Voltage Distortion THD-V

Full Resistive load < 3%
Full RCD load < 5%

Load peak factor without derating

 3 lpk/lrms

Содержание GXT3-10000T230

Страница 1: ...AC Power For Business Critical Continuity Liebert GXT3 10000T230 User Manual 10kVA 50 60 Hz 230V...

Страница 2: ......

Страница 3: ...2 10 Clearance 7 2 11 Repacking the UPS 7 3 0 INSTALLATION 8 3 1 Electrical preparations 8 3 2 Current Table and Suggested Cable Sizes 8 3 3 Neutral Connection 9 3 4 External Protection and Isolating...

Страница 4: ...unctional Test 21 4 9 Remote Emergency Power Off 22 4 10 Self Tests 22 4 10 1 Lamp Test 22 4 10 2 Battery Test 22 5 0 MAINTENANCE 23 5 1 Testing Replacing and Disposing of Batteries 23 5 2 Easy Batter...

Страница 5: ...net 13 Figure 12 Overview of UPS tower 15 Figure 13 Control panel 16 Figure 14 System block menu structure 17 Figure 15 REPO connections 22 Figure 16 Removing front panel and unlocking battery trays 2...

Страница 6: ...iv...

Страница 7: ...e connected These battery extensions may be connected only to the compatible basic UPS unit WARNING Opening or removing the cover may expose you to lethal voltages within this unit even when it is app...

Страница 8: ...cted or disconnected during a thunderstorm Remote Emergency Power Off REPO input is located on the rear of the unit see 3 8 Ter minal Blocks for UPS When this connection is open the logic circuit will...

Страница 9: ...formity If required the EU Declaration of Conformity may be requested from Liebert NOTICE TO EUROPEAN UNION CUSTOMERS DISPOSAL OF OLD APPLIANCES This product has been supplied from an environmentally...

Страница 10: ...c equipment operates best from sinewave power For ease of use the Liebert GXT3 10000T230 features an LCD display for comprehensive user indica tions and programmable controls It also provides self dia...

Страница 11: ...0 For technical data about external battery cabinets see Table 10 UPS specifications For connection notices see Table 2 Connection data 1 2 2 Optional Interfaces Refer to 6 0 Communication for details...

Страница 12: ...d damaging the UPS Do not dispose of the packing material The original packaging material should be used if the UPS needs to be repackaged such as for shipping Check all packaging to ensure that no it...

Страница 13: ...ed will support the unit s weight see Table 10 for the unit s weight 2 9 Inventory List The Liebert GXT3 10000T230 comes with CD containing Liebert MultiLink Shutdown Software Configuration Software U...

Страница 14: ...bles WARNING Installation may be carried out only by qualified technicians conforming to applicable safety standards Electric shock hazard Even when the unit is disconnected from the mains hazardous v...

Страница 15: ...ed for the protection of both the cables and the equipment WARNING The following label must be displayed on all switching devices installed in the same electrical system as the UPS even when they are...

Страница 16: ...ove the protective panel on the rear of the UPS to access the external electrical connections see figure below Once the cables have been connected they must be passed through the cable clamps that wil...

Страница 17: ...t share a common conduit with input circuits or any other wiring The utility may be derived from a single phase or three phase source Figure 6 Input and output connections with single source single ph...

Страница 18: ...Figure 3 5 If the reserve input is to be supplied separately connect reserve line to the Mains 2 terminals If the UPS is supplied by a common mains connect the supplied jumper in the accessory kit ma...

Страница 19: ...d battery a compensating current may occur during connection Figure 11 Liebert GXT3 10000T230 with External Battery Cabinet 3 11 Connecting an External Battery Extension The unit checks the battery vo...

Страница 20: ...four months Since new batteries often do not provide full capacity after the initial charge it may be necessary to carry out a number of discharge recharge cycles before optimum performance is reache...

Страница 21: ...booster inverter and charger Internal electronic bypass 2 input breakers Maintenance bypass breaker TVSS filter Integrated battery expandable Figure 12 Overview of UPS tower L2 L3 at 10kVA device only...

Страница 22: ...u Press Enter to choose an entry Table 4 Lighted LEDs LED Indicator LED Color Description UPS ON Green UPS is online and operating normally BYPASS Amber Load is supplied by the mains via automatic byp...

Страница 23: ...Menu Setup Menu Status Menu Parallel Menu Language Tag Number UPS ID No DC Start Test Intvl Batt Pack Audible Alarm Output Volt No of Unit Control Menu Contrast Batt Test Alarm Ctrl UPS ON OFF Test Re...

Страница 24: ...ENU SysOutI A SysOutV V SysOutF Hz SysOutW W SysOutVA VA SysLoadPer SETUP MENU Setting item Setting level 1 Audible Alarm Disable Enable Output Volt 220V 230V 240V Batt Pack 1 4 Test intvl DC Start Di...

Страница 25: ...is window All fault displays include The nature of the event The time of the event The fault indicators are Table 6 Warning indicators Warning Cause Corrective Steps 1 No Redundancy 2 InvASynFault 3 P...

Страница 26: ...y external switches connecting the load if present 7 Press the Menu button select Control and press OK 8 Select Turn UPS ON OFF and press OK The LCD will display Turn ON 9 Press OK to switch On the in...

Страница 27: ...Before beginning ensure that the batteries are fully charged Simulate a mains failure by interrupting the mains supply to the UPS You can do this by switching Off the input power circuit breaker on t...

Страница 28: ...s mode A system confirmation beep will sound 4 10 2 Battery Test 1 Press the Menu button 2 Select Control and press OK 3 Select BATT TEST and press OK A system confirmation beep will sound and the loa...

Страница 29: ...al regulations and laws Exhausted accumulator batteries are classified as harmful toxic waste and as such the law demands that they be disposed of by an authorized recycling centre The Liebert power p...

Страница 30: ...Open the battery tray DC connectors as shown 2 Remove the battery trays from the cabinet 3 Replace the old batteries with a new set Replacement batteries must be the same type installed at the factory...

Страница 31: ...rcuit breaker of the UPS Then remove the UPS connections in the opposite sequence to that described in 3 0 Instal lation Record the battery charging date in the vicinity of the UPS for example on its...

Страница 32: ...Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the event history l...

Страница 33: ...d The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the net work The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applicati...

Страница 34: ...e on four comput ers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support fo...

Страница 35: ...t intervals No mains voltage present UPS operation control panel UPS on LED does not illuminate when mains voltage present audible alarm active at intervals Input fuse defective or input circuit break...

Страница 36: ...y nominal voltage VDC 240 Battery charger input voltage range VDC 100 276 Output voltage V Multi stage charging method Charging time to 90 capacity in inverter mode hr 3 Charger output current ADCaver...

Страница 37: ...ttery number pcs 40 80 Dimensions W x D x H mm in 300 x 675 x 800 11 8 x 26 6 x 31 5 Color Black Weight with integrated batteries kg lb 162 357 Performance EN 62040 3 Dynamic characteristics VFI S S 1...

Страница 38: ...Level 3 Criteria A Electrical Fast Transient EN61000 4 4 Level 4 Criteria A Surge Immunity EN61000 4 5 Level 3 Criteria A Transportation ISTA Procedure 1A Table 13 Operating temperature parameters Am...

Страница 39: ......

Страница 40: ...ive owners Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upst...

Отзывы: