Operation
19
4.2.2 Warning Indicators
If a warning indicator appears, the UPS continues to operate. The warning message alternates with
UPS mode once a second (see
Table 6
)
The warning indicators are described below:
4.2.3 Fault Indicators
If a fault occurs, the UPS automatically switches to BYPASS mode. Only in the case of a battery dis-
connection fault will the original operating mode be maintained. The fault message alternates with
UPS mode once a second, the red fault LED on the control panel lights up and the alarm sounds con-
tinuously. If a fault occurs, proceed as follows:
Alarm operation
—The alarm can be switched On or Off.
Clear Fault
—Present fault condition can be reset if fault condition is cleared, either automatically or
by the user.
Fault information
—A maximum of four faults can be displayed in this window. All fault displays
include:
• The nature of the event
• The time of the event
The fault indicators are:
Table 6
Warning indicators
Warning
Cause
Corrective Steps
1
No Redundancy
2
InvASynFault
3
ParaCommuErr
4
CurShareFault
5
ParaFreqErr
6
Byo Reminder
7
L2 or L# Fail
Check L2, L3 input fuse
8
UtilFail
N/A
9
BattUnderVolt
N/A
Table 7
Display faults
Fault
Cause
Corrective Steps
1
Comm Shutdown
Call customer service
2
Inv Fault
Call customer service
3
Over Temp
Reduce load
4
Batt Test Fail
Call customer service
5
PFC Failure
Call customer service
6
Over load
Reduce load
7
DCDC Failure
Call customer service
8
DC BUS Fault
Call customer service
9
Charger Fault
Call customer service
10
REPO
N/A
11
Byp Feedback
Call customer service
12
Startup No Batt
Check battery
13
Mnt Byo Swt On
Call customer service
14
Fan Fault
Call customer service
15
Batt Disconnect
Check battery connector
16
ParaCableFault
Call customer service
17
ParaAddOverlap
Call customer service
18
Turn On Fail
Call customer service