17
06: Voltage range for ECO mode
Interface
Setting
Parameter 2:
Low voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
Parameter 3:
High voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
07: Frequency range for ECO mode
Interface
Setting
Parameter 2:
Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3:
Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN
: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting.
FBD
: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is activated.
DIS
: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
09: Battery backup time setting
Interface
Setting
Parameter 3:
000~999:
Set the maximum backup time from 0min to 999min.
UPS will shut down to protect battery after backup time arrives.
The default value is 990min.
DIS:
Disable battery discharge protection and backup time will
depend on battery capacity.
Содержание Adapt BX 10K
Страница 1: ...Single Phase Online UPS Liebert Adapt BX User Manual 6k 10kVA...
Страница 27: ...25...