background image

12 

 

buzzer is muted, the buzzer will beep again. 

2)    Some  warning  alarms 

can’t  be  muted  unless  the  error  is  fixed.  Please  refer  to  section  3-3  for  the 

details.   

10. Operation in warning status 

1)    When  Fault  LED  flashes  and  the  buzzer  beeps  once  every  second,  it  means  that  there  are  some 

problems for UPS operation. Users can get the fault code from LCD panel. Please check the trouble 

shooting table in chapter 4 for details.   

2)    Some  warning  alarms 

can’t  be  muted  unless  the  error  is  fixed.  Please  refer  to  section  3-3  for  the 

details. 

11. Operation in Fault mode 

1)    When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in 

the UPS.    Users can get the fault code from display panel. Please check the trouble shooting table in 

chapter 4 for details. 

2)    Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to 

turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact the 
distributor or service people immediately. 

3)    For  emergency  case,  please  cut  off  the  connection  from  utility,  external  battery,  and  output 

immediately to avoid more risk or danger. 

12. Operation of changing battery numbers 

1)    This operation is only available for professional or qualified technicians. 

2)    Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance bypass 

switch on the rear panel and turn the maintenance switch to “BPS” position first. 

3)    Switch off the input breaker, and switch off the battery breaker (only available for long-run model).   

4)    Remove the cabinet, and then modify the jumper on the control board to set the battery numbers (refer 

to  NOTE  below).  Then  disconnect  battery  wire  for  standard  model  and  modify  the  battery  pack 

carefully. After complete the changes, put the cabinet back.   

NOTE: 

JP1 setting on the control board: please shorts the Pin5 & Pin6 and Pin7 & Pin8 for 20 pcs batteries; 

shorts the Pin5 & Pin6 or Pin7 & Pin8 for 19 pcs batteries; and keeps every pin open for 18 pcs batteries. 

It

’s also necessary to adjust output voltage on charger. Please refer to setting SOP for battery numbers. 

5)    Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance Bypass 

mode, turn the maintenance switch to “UPS” position and then turn on the UPS. 

3-5. Parallel Operation 

1. Parallel system connection 

1)    Make sure all of the UPSs are parallel models, and follow the wiring refer to section 2-4.   

2)  Turn  off  the  input  and  output  breakers  of  each  UPS,  and  turn  off  the  battery  breaker  if  the  UPS  is 

long-run model. 

3)  Turn on the input breaker of the each UPS and measure the voltage difference between the output 

line1 of each UPS with multimeter. If the voltage difference is less than 1V, it means all connections 

are correct. If the difference is larger than 1V, check if the wirings are connected correctly.   

Содержание Adapt BX 10K

Страница 1: ...Single Phase Online UPS Liebert Adapt BX User Manual 6k 10kVA...

Страница 2: ...4 UPS Installation for Parallel System 6 2 5 Software Installation 6 3 Operations 7 3 1 Button Operation 7 3 2 LED Indicators and LCD Panel 7 3 3 Audible Alarm 9 3 4 Single UPS Operation 10 3 5 Parall...

Страница 3: ...for ventilation UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualifie...

Страница 4: ...000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 3 Low Frequency Signals IEC EN 61000 2 2 W...

Страница 5: ...lug One parallel cable only available for parallel model One share current cable only available for parallel model NOTE Before installation please inspect the unit Be sure that nothing inside the pack...

Страница 6: ...as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all...

Страница 7: ...ry The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for long run model Make sure a DC breaker or other prote...

Страница 8: ...g to the section 2 3 2 Connect the output wires of each UPS to an output breaker 3 Connect all output breakers to a major output breaker Then this major output breaker will directly connect to the loa...

Страница 9: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press t...

Страница 10: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Страница 11: ...lt mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO enable Fan failure Over temperature Charger failur...

Страница 12: ...rned on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel...

Страница 13: ...7 LCD setting section 6 Test the batteries 1 If you need to check the battery status when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery se...

Страница 14: ...t off you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the input breaker and switch off the battery breaker...

Страница 15: ...the parallel models and follow the wiring refer to section 2 3 3 Install the new parallel system refers to the previous section 3 Remove one unit from the parallel system 1 If the bypass is abnormal...

Страница 16: ...B Subtract ADD Add ON On OFF Off FBD Not allowed OPN Allow RES Reserved 3 7 LCD Setting There are three parameters to set up the UPS Refer to following diagram Parameter 1 It s for program alternative...

Страница 17: ...tput voltage in parameter 3 208 Presents output voltage is 208Vac 220 Presents output voltage is 220Vac 230 Presents output voltage is 230Vac 240 Presents output voltage is 240Vac 02 Output frequency...

Страница 18: ...e default value is 110V Parameter 3 Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V 04 Frequency range for bypass Interface Setting Paramete...

Страница 19: ...Hz 08 Bypass mode setting Interface Setting Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected i...

Страница 20: ...battery 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage range is from 0V to 5 7V the default va...

Страница 21: ...output for energy saving LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery...

Страница 22: ...ages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon Bus start failure 01 None Negative power fault 1A None Bus over 02 None Battery SCR short circuited...

Страница 23: ...ing twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beepi...

Страница 24: ...oads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then U...

Страница 25: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 26: ...2 A 10 max Charging Voltage 13 65 V 1 Long run Model Type Depending on applications Numbers 16 20 Charging Current 4 A 10 max 4 A 10 max Charging Voltage 13 65 V 1 PHYSICAL Standard Model Dimension DX...

Страница 27: ...25...

Отзывы: