Liberty Pumps ProVore PRG101A Скачать руководство пользователя страница 7

 

      ©Copyright 2013 Liberty Pumps Inc.    All rights reserved  

- 7 - 

 

           

STEPS TO BE TAKEN BEFORE ENERGIZING

 

 

1.  Retighten  all  field-made  connections.    Retighten  all  factory-made  connections.    These may  have  loosened 

due to shipping and handling vibrations. 

2.  Check the security of mounting hardware. 

3.  Check the enclosure to see that it has not been damaged in such a manner as to reduce electrical spacing. 

4.  Rotate the cutter wheel with the hex socket head cap screw to verify movement and lubricate the seals. 

5.  Ensure that no wires or other obstacles are in the way of the pump cutter. 

6.  MOTOR OVERLOAD PROTECTION: The pump motor is protected from locked rotor and running overloads 

by a thermal overload integrally mounted to the motor.  No adjustments are required. 

7.  Check to determine that all grounding connections are made properly 

 

If a panel is used, remove all debris, scrap wire, etc., from the control panel interior before closing the 

doors.  Install covers, close doors making certain that no wires are pinched and that all enclosure parts 

are properly aligned and tightened. 

 

ENERGIZING  THE  CONTROL  PANEL  OR  BREAKER  FOR  THE  FIRST  TIME  IS 

POTENTIALLY  DANGEROUS.    LICENSED  ELECTRICAL  PERSONNEL  SHOULD  BE 

PRESENT WHEN THE PANEL OR BREAKER IS  ENERGIZED FOR THE FIRST TIME.  IF 

FAULTS CAUSED BY DAMAGE OR POOR INSTALLATION PRACTICES HAVE NOT BEEN 

DETECTED,  SERIOUS  DAMAGE  CAN  RESULT  WHEN  POWER  IS  APPLIED

 

(REFER  TO 

SECTION 5).

 

 

FLOAT SWITCHES 

1.  The pump's on and off cycles are normally controlled by a "piggy back" float switch attached to the side of the 

pump,  or  by  hanging  switches  in  the  wet  well.    Refer  to  panel  or  switch  instructions  for  proper  electrical 

connection 

 

 

FLOAT SEQUENCE- PIGGY BACK SWITCH

    

  (AUTOMATIC MODELS) 

1.  As the liquid level in the wet well rises, the float tilts, closing the switch.  This starts the pump. 

2.  The pump runs until the liquid level falls to the “PUMP OFF” level of the float (Factory set - 6" minimum). 

 

FLOAT SEQUENCE- SIMPLEX CONTROL PANEL   (MANUAL MODELS) 

1.  As the liquid level in the wet well rises, the “PUMP OFF” float tilts, closing the switch (This level must be set at 

a minimum of 6").  As the liquid level continues to rise, the “PUMP ON” float tilts.  This switch closes, starting 

the pump. 

2.  The pump runs until the liquid level falls below the “PUMP OFF” float, emptying the wet well. 

3.  In the event of a malfunctioning float switch, control relay or pump, the liquid level rises and tilts the “HIGH 

LEVEL ALARM” float.  The alarm system will activate. 

 

FLOAT SEQUENCE-DUPLEX CONTROL PANEL  (MANUAL MODELS) 

1.  As the liquid level in the wet well rises, the “PUMP OFF” tilts, closing the switch.  As the liquid level continues 

to rise, the “LEAD PUMP ON” float tilts.  This switch closes, starting the lead pump.  The pump runs until the 

liquid level falls below the “PUMP OFF” float (6” minimum), emptying the wet well. 

2.  On the next rise of the liquid level, the other pump will start on the “LEAD PUMP ON” signal.  The pumps will 

continue to alternate their cycles. 

NOTE: 

The ON/OFF float switch differential should be set as to not exceed 12 starts per hour. 

3.  If the liquid level rises to the “LAG PUMP ON" float, the second pump will start.  Both pumps will run until the 

liquid falls below the “PUMP OFF” float, emptying the wet well.

 

4.  In the event of a malfunctioning float switch, control relay or pump, the liquid  level rises and tilts the “HIGH 

LEVEL ALARM” float.  The alarm system will activate.

 

 

 

Содержание ProVore PRG101A

Страница 1: ...r cord PRG102M 2 1 hp 230V 1 phase 25 Power cord Do not throw away or lose this manual Contents General Information Introduction Mechanical Installation Electrical Connection Operation Troubleshooting...

Страница 2: ...adequate protective clothing when working on a used pump or piping Never enter a pump basin after it has been used Sewage and effluent can emit several gases which are poisonous Keep clear of suction...

Страница 3: ...l type cartridge seal with two silicon carbide faces 4 The impeller and volute are designed for efficient flow characteristics and clog free operation The hardened cutters grind solids and fibrous mat...

Страница 4: ...ending on local codes and the number of fixture units entering the system Check with the local authorities or contact Liberty Pumps if you are unsure of the proper basin size Installation should be at...

Страница 5: ...ent plug To reduce the risk of electric shock be certain that the grounding conductor is connected only to a properly grounded control panel or if equipped with a grounding type plug that it is connec...

Страница 6: ...switch cord to the discharge pipe NOTE A minimum cord length of 3 5 from the tether point to the top surface of the float is required for proper switch operation If using a differential other than th...

Страница 7: ...Refer to panel or switch instructions for proper electrical connection FLOAT SEQUENCE PIGGY BACK SWITCH AUTOMATIC MODELS 1 As the liquid level in the wet well rises the float tilts closing the switch...

Страница 8: ...ump Off Factory set Float tether 3 5 Pump On Factory set Float tether 3 5 SIMPLEX PUMP STATION 3 Float System Pump Off Level to top of motor housing Pump On Minimum 1 1 2 ft above Pump Off Level High...

Страница 9: ...IFY THE LIBERTY PRODUCT SERVICE DEPARTMENT IMMEDIATELY DO NOT SWITCH THE POWER SUPPLY LEADS DO NOT OPERATE THE PUMP ALWAYS ENSURE THAT THE PUMP IS FREE OF WIRES OR OTHER OBSTRUCTIONS THAT MAY CAUSE HA...

Страница 10: ...ischarge line passes through or into cold areas Check valve is stuck closed or installed backwards Remove check valve s and examine for freedom of operation and proper installation Gate or ball valve...

Страница 11: ...installed if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been reduced in size if the pump has been used i...

Страница 12: ...sica cord n el ctrico de 10 pies 3 m PRG102M 2 1 hp 230 V monof sica cord n el ctrico de 25 pies 8 3 m No tire ni pierda este manual Manual de instalaci n 2399000B Bombas trituradoras residenciales Pr...

Страница 13: ...grese a una cubeta de bomba despu s que haya sido usada Los sistemas de efluentes y de alcantarillado pueden emitir diferentes tipos de gases t xicos Mant ngase alejado de la entrada de succi n y de l...

Страница 14: ...de carburo de silicio 4 El rotor y la voluta est n dise ados para producir un caudal ptimo y funcionar sin obstrucciones Los discos endurecidos trituran la materia s lida y fibrosa hasta convertirla...

Страница 15: ...undidad suficiente como para que todas las ca er as queden por debajo de la l nea de penetraci n de la helada Si esto no fuera posible desmonte la v lvula de retenci n y modifique el tama o de la cube...

Страница 16: ...conectado debidamente a un panel de control a tierra o si cuenta con un enchufe a tierra tendr que enchufarse a un tomacorriente conectado a tierra NO derive los cables de puesta a tierra ni retire l...

Страница 17: ...lotador para que el interruptor funcione correctamente Si se va a utilizar un diferencial distinto al de f brica se deber ajustar de forma que la bomba se apague cuando queden 15 24 cm 6 pulg como m n...

Страница 18: ...OS 1 El flotador se va inclinando a medida que sube el nivel del sumidero inundado con lo que cierra el interruptor Esto hace arrancar la bomba 2 La bomba seguir funcionando hasta que el nivel de l qu...

Страница 19: ...pulg ESTACI N DE BOMBA SIMPLE sistema de 3 flotadores Bomba apagada Nivel hasta la parte superior del chasis Bomba encendida M nimo 45 72 cm 1 5 pies por arriba del nivel de la bomba apagada Alarma de...

Страница 20: ...MENTE NO CAMBIE LOS HILOS DE ALIMENTACI N NO ENCIENDA LA BOMBA COMPRUEBE SIEMPRE QUE NO HAYA CABLES SUELTOS Y OTRAS OBSTRUCCIONES QUE PUDIERAN CAUSAR LESIONES PERSONALES O DESPERFECTOS MANTENIMIENTO Y...

Страница 21: ...edado cerrada o est instalada al rev s Saque la v lvula de retenci n y aseg rese de que funciona sin impedimentos y que haya sido instalada correctamente La v lvula de compuerta o la de bola est cerra...

Страница 22: ...instalado correctamente si ha sido desmontado modificado abusado o forzado si el cable el ctrico se ha cortado da ado o empalmado si se redujo el tama o de la descarga de la bomba si la bomba se us co...

Страница 23: ...230V monophas e cordon d alimentation de 3 m 10 pi PRG102M 2 1 hp 230V monophas e cordon d alimentation de 3 m 25 pi Ne pas jeter ni perdre ce manuel Table des mati res Renseignements g n raux Introd...

Страница 24: ...tuyauterie ayant d j servi Ne jamais p n trer dans le r servoir de pompage apr s qu il ait servi Les gouts et effluents peuvent mettre des gaz toxiques Demeurer l cart des orifices d aspiration et d...

Страница 25: ...h it m canique comportant deux c t s en carbure de silicium 4 Le compresseur et la sortie sont con us pour une utilisation sans obstruction et comportent des caract ristiques d coulement efficaces Les...

Страница 26: ...iberty Pumps en cas de doute au sujet de la taille du bassin qui convient L installation doit tre suffisamment profonde pour assurer que toute la plomberie se trouve sous la profondeur maximale de la...

Страница 27: ...rrectement mis la terre ou s il est muni d une fiche avec mise la terre qu elle est correctement mise la terre NE PAS d vier les fils de mise la terre ou retirer les broches de mise la terre des fiche...

Страница 28: ...n minimum de 8 9 cm 3 5 po entre le point d attache et le haut du flotteur est n cessaire au bon fonctionnement de l interrupteur Lorsqu on utilise un intervalle diff rent de celui qui est r gl en usi...

Страница 29: ...sure que le niveau de liquide monte dans la b che d aspiration le flotteur bascule et ferme l interrupteur Cela fait d marrer la pompe 2 La pompe tourne jusqu ce que le niveau de liquide descende au n...

Страница 30: ...ngle de 3 5 po STATION DE POMPAGE SIMPLE Syst me 3 flotteurs Pompe arr t e niveau du sommet du bo tier du moteur Pompe en marche au moins 46 cm 1 pi au dessus du niveau de pompe arr t e Alarme de nive...

Страница 31: ...NVERSER LES BORNES D ALIMENTATION LECTRIQUE NE PAS FAIRE FONCTIONNER LA POMPE TOUJOURS S ASSURER QUE LA POMPE EST LIBRE DE TOUTE OBSTRUCTION PAR DES C BLES OU AUTRES L MENTS POUVANT PROVOQUER DES DOMM...

Страница 32: ...lisation d vacuation se trouve dans des zones froides ou les traverse Clapet antiretour bloqu en position ferm e ou incorrectement install Retirer tout clapet antiretour et v rifier qu il fonctionne l...

Страница 33: ...usage abusif ou endommag si le cordon lectrique a t coup endommag ou ligatur si la taille du tuyau d vacuation de la pompe a t r duite si la pompe a t utilis e pour pomper de l eau d une temp rature...

Отзывы: