STORAGE BEFORE USE 

Liberty pumps are shipped from the factory ready for installation and use.  They should be held in storage if the 

pump station is not complete.  If storage is necessary, the pump should remain in its shipping container.  It should 

be stored in a warehouse or storage shed that has a clean, dry temperature-stable area where the pump and its 

container should be covered to protect it from water, dirt, dust, etc.  The ends of the cables  - (plugs) must be 

protected against moisture. 

 

AT NO TIME SHOULD THE PUMP BE STORED WITHIN AN INCOMPLETE WET PIT.  THE PUMP 

SHOULD NOT BE PLACED INTO THE PIT UNTIL IT CAN BE FULLY OPERATED. 

 

LONG TERM STORAGE 

1. 

If  it  is  necessary  to  store  a  pump  for  a  long  period  of  time,  it  should  be  stored  indoors  in  a  clean,  dry 

temperature-stable environment.  The pump should be covered to protect it from dust, dirt and water.  The 

plug end of the cable must be protected against moisture. 

 

2. 

Do not allow the pump to freeze.  

 

3. 

Prior to installation, the pump motor should be rotated to ensure the seals and cutters are free spinning. 

 

4. 

Installed  pumps  which  are  idle  for  long  periods  of  time  should  be  manually  operated  through  the  breaker 

panel once a month to lubricate the seals.  Turn off the breaker, unplug the piggyback switch, and plug the 

pump directly into the wall socket.  Turn the breaker on for 30 seconds.  Turn the breaker off, and then plug 

the piggyback switch back in. 

 

4. x 

The Basin                                     

x                                        

 

 

The  basin  required  for  both  effluent  and  sewage  applications  must  be  sealed  and  vented  to  meet  health  and 

plumbing  code  requirements.    These  pumps  are  not  to  be  installed  in  locations  classified  as  hazardous  in 

accordance  with  the  National  Electric  Code,  ANSI/NFPA  70.    The  diameter  should  be  a  minimum  of  18"  and  the 

depth a minimum of 24".  (These are minimum requirements.  A larger basin may be required in both effluent and 

sewage applications depending on local codes and the number of fixture units entering the system.  Check with the 

local  authorities or contact Liberty Pumps if  you are  unsure of the proper basin size.)  Installation should  be at a 

sufficient depth to ensure that all plumbing is below the frost line.  If this is not feasible, remove the check valve and 

size the basin and/or adjust pump differential to accommodate the additional backflow volume.  

A. 

Excavation:

 Excavate the hole as small as possible, with a minimum recommended 8" diametrical clearance 

around the tank. Never place the basin directly in contact with rocks or other sharp objects.  Place only fine, 

1/8" to 3/4"  pea gravel or  1/8" to 1/2"  washed, crushed stone as  bedding  between the  basin and the  hole 

walls.  Do not use sand or native soil as backfill.  Properly compact underneath the basin to provide a solid, 

level base that can support the weight of the filled basin. 

 

B. 

Inlet Connection & Initial Backfill:

 Only fine, 1/8" to 3/4" pea gravel or 1/8" to 1/2" washed, crushed stone 

should be used around the bottom of the basin to hold it in place.  Do not use sand or native soil as backfill.  

Make the inlet connection as required for your basin. 

Liberty P380, & P680:

 The Liberty Pro Series basins have a 4" inlet molded to the side of the tank.  This inlet 

is sized to accept a 4" no-hub type coupling.  Connect the gravity drainage line from 

the fixtures to this hub. 

Other Basins:

 

Other  Liberty  basins  provide  a  4"  caulking  hub  or  pipe  grommet  inlet.    Hubs  utilize 

caulking  material  or  rubber  donuts;  grommets  are  a  simple  slip-fit.    Connect  the 

gravity drainage line from the fixtures to this opening.  (Other inlet sizes available  – 

consult factory.) 

C. 

Final Backfill: 

Large rocks, clods, and foreign objects should be kept out of the backfill material.  Only fine, 

1/4" to 3/4" pea gravel, or 1/8" to 1/2" washed, crushed stone is recommended.  Do not use sand or native 

soil as backfill.  Mound the backfill slightly and allow for natural settling.  Provide access to the basin cover for 

maintenance and service. 

 

 

Do not exert heavy pressure or run heavy equipment on the backfill material as this could cause 

the tank to collapse. 

Содержание ProVore PRG101A

Страница 1: ...r cord PRG102M 2 1 hp 230V 1 phase 25 Power cord Do not throw away or lose this manual Contents General Information Introduction Mechanical Installation Electrical Connection Operation Troubleshooting...

Страница 2: ...adequate protective clothing when working on a used pump or piping Never enter a pump basin after it has been used Sewage and effluent can emit several gases which are poisonous Keep clear of suction...

Страница 3: ...l type cartridge seal with two silicon carbide faces 4 The impeller and volute are designed for efficient flow characteristics and clog free operation The hardened cutters grind solids and fibrous mat...

Страница 4: ...ending on local codes and the number of fixture units entering the system Check with the local authorities or contact Liberty Pumps if you are unsure of the proper basin size Installation should be at...

Страница 5: ...ent plug To reduce the risk of electric shock be certain that the grounding conductor is connected only to a properly grounded control panel or if equipped with a grounding type plug that it is connec...

Страница 6: ...switch cord to the discharge pipe NOTE A minimum cord length of 3 5 from the tether point to the top surface of the float is required for proper switch operation If using a differential other than th...

Страница 7: ...Refer to panel or switch instructions for proper electrical connection FLOAT SEQUENCE PIGGY BACK SWITCH AUTOMATIC MODELS 1 As the liquid level in the wet well rises the float tilts closing the switch...

Страница 8: ...ump Off Factory set Float tether 3 5 Pump On Factory set Float tether 3 5 SIMPLEX PUMP STATION 3 Float System Pump Off Level to top of motor housing Pump On Minimum 1 1 2 ft above Pump Off Level High...

Страница 9: ...IFY THE LIBERTY PRODUCT SERVICE DEPARTMENT IMMEDIATELY DO NOT SWITCH THE POWER SUPPLY LEADS DO NOT OPERATE THE PUMP ALWAYS ENSURE THAT THE PUMP IS FREE OF WIRES OR OTHER OBSTRUCTIONS THAT MAY CAUSE HA...

Страница 10: ...ischarge line passes through or into cold areas Check valve is stuck closed or installed backwards Remove check valve s and examine for freedom of operation and proper installation Gate or ball valve...

Страница 11: ...installed if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been reduced in size if the pump has been used i...

Страница 12: ...sica cord n el ctrico de 10 pies 3 m PRG102M 2 1 hp 230 V monof sica cord n el ctrico de 25 pies 8 3 m No tire ni pierda este manual Manual de instalaci n 2399000B Bombas trituradoras residenciales Pr...

Страница 13: ...grese a una cubeta de bomba despu s que haya sido usada Los sistemas de efluentes y de alcantarillado pueden emitir diferentes tipos de gases t xicos Mant ngase alejado de la entrada de succi n y de l...

Страница 14: ...de carburo de silicio 4 El rotor y la voluta est n dise ados para producir un caudal ptimo y funcionar sin obstrucciones Los discos endurecidos trituran la materia s lida y fibrosa hasta convertirla...

Страница 15: ...undidad suficiente como para que todas las ca er as queden por debajo de la l nea de penetraci n de la helada Si esto no fuera posible desmonte la v lvula de retenci n y modifique el tama o de la cube...

Страница 16: ...conectado debidamente a un panel de control a tierra o si cuenta con un enchufe a tierra tendr que enchufarse a un tomacorriente conectado a tierra NO derive los cables de puesta a tierra ni retire l...

Страница 17: ...lotador para que el interruptor funcione correctamente Si se va a utilizar un diferencial distinto al de f brica se deber ajustar de forma que la bomba se apague cuando queden 15 24 cm 6 pulg como m n...

Страница 18: ...OS 1 El flotador se va inclinando a medida que sube el nivel del sumidero inundado con lo que cierra el interruptor Esto hace arrancar la bomba 2 La bomba seguir funcionando hasta que el nivel de l qu...

Страница 19: ...pulg ESTACI N DE BOMBA SIMPLE sistema de 3 flotadores Bomba apagada Nivel hasta la parte superior del chasis Bomba encendida M nimo 45 72 cm 1 5 pies por arriba del nivel de la bomba apagada Alarma de...

Страница 20: ...MENTE NO CAMBIE LOS HILOS DE ALIMENTACI N NO ENCIENDA LA BOMBA COMPRUEBE SIEMPRE QUE NO HAYA CABLES SUELTOS Y OTRAS OBSTRUCCIONES QUE PUDIERAN CAUSAR LESIONES PERSONALES O DESPERFECTOS MANTENIMIENTO Y...

Страница 21: ...edado cerrada o est instalada al rev s Saque la v lvula de retenci n y aseg rese de que funciona sin impedimentos y que haya sido instalada correctamente La v lvula de compuerta o la de bola est cerra...

Страница 22: ...instalado correctamente si ha sido desmontado modificado abusado o forzado si el cable el ctrico se ha cortado da ado o empalmado si se redujo el tama o de la descarga de la bomba si la bomba se us co...

Страница 23: ...230V monophas e cordon d alimentation de 3 m 10 pi PRG102M 2 1 hp 230V monophas e cordon d alimentation de 3 m 25 pi Ne pas jeter ni perdre ce manuel Table des mati res Renseignements g n raux Introd...

Страница 24: ...tuyauterie ayant d j servi Ne jamais p n trer dans le r servoir de pompage apr s qu il ait servi Les gouts et effluents peuvent mettre des gaz toxiques Demeurer l cart des orifices d aspiration et d...

Страница 25: ...h it m canique comportant deux c t s en carbure de silicium 4 Le compresseur et la sortie sont con us pour une utilisation sans obstruction et comportent des caract ristiques d coulement efficaces Les...

Страница 26: ...iberty Pumps en cas de doute au sujet de la taille du bassin qui convient L installation doit tre suffisamment profonde pour assurer que toute la plomberie se trouve sous la profondeur maximale de la...

Страница 27: ...rrectement mis la terre ou s il est muni d une fiche avec mise la terre qu elle est correctement mise la terre NE PAS d vier les fils de mise la terre ou retirer les broches de mise la terre des fiche...

Страница 28: ...n minimum de 8 9 cm 3 5 po entre le point d attache et le haut du flotteur est n cessaire au bon fonctionnement de l interrupteur Lorsqu on utilise un intervalle diff rent de celui qui est r gl en usi...

Страница 29: ...sure que le niveau de liquide monte dans la b che d aspiration le flotteur bascule et ferme l interrupteur Cela fait d marrer la pompe 2 La pompe tourne jusqu ce que le niveau de liquide descende au n...

Страница 30: ...ngle de 3 5 po STATION DE POMPAGE SIMPLE Syst me 3 flotteurs Pompe arr t e niveau du sommet du bo tier du moteur Pompe en marche au moins 46 cm 1 pi au dessus du niveau de pompe arr t e Alarme de nive...

Страница 31: ...NVERSER LES BORNES D ALIMENTATION LECTRIQUE NE PAS FAIRE FONCTIONNER LA POMPE TOUJOURS S ASSURER QUE LA POMPE EST LIBRE DE TOUTE OBSTRUCTION PAR DES C BLES OU AUTRES L MENTS POUVANT PROVOQUER DES DOMM...

Страница 32: ...lisation d vacuation se trouve dans des zones froides ou les traverse Clapet antiretour bloqu en position ferm e ou incorrectement install Retirer tout clapet antiretour et v rifier qu il fonctionne l...

Страница 33: ...usage abusif ou endommag si le cordon lectrique a t coup endommag ou ligatur si la taille du tuyau d vacuation de la pompe a t r duite si la pompe a t utilis e pour pomper de l eau d une temp rature...

Отзывы: