22
OPERATION
MODE 4: Temperature Limiting
Press MODE until a 4 appears in the first digit of the display for
Temperature Limiting mode. Temperature Limiting can save
money by limiting the lowest temperature for cooling and the
highest temperature for heating. This temperature limiting is not
available with the Remote Wall Thermostat.
Press the
∨
or
∧
pad to change 2nd Digit number.
The default setting for Mode 4 is as follows:
Cooling : 0{54 °F(12.2 °C)~86 °F(30.0 °C)}
Heating : 0{54 °F(12.2 °C)~86 °F(30.0 °C)}
MODE 5: Unit Type
Press MODE until a 5 appears in the first digit of the display for
Unit Type mode.
Press the
∨
or
∧
pad to change 2nd Digit number.
The default setting for Mode 5 is Cooling, Electric Heater and
Heat Pump type.
MODE 6: Make Up Air Mode(Option)
Press MODE until a 6 appears in the first digit of the display for
Make Up Air mode.
Press the
∨
or
∧
pad to change 2nd Digit number.
The default setting for Mode 6 is off.
2nd Digit
Cooling
Heating
0
54°F(12.2°C)~86°F(30.0°C)
54°F(12.2°C)~86°F(30.0°C)
1
56°F(13.3°C)~86°F(30.0°C)
54°F(12.2°C)~84°F(28.9°C)
2
58°F(14.4°C)~86°F(30.0°C)
54°F(12.2°C)~82°F(27.8°C)
3
60°F(15.5°C)~86°F(30.0°C)
54°F(12.2°C)~80°F(26.7°C)
4
62°F(16.6°C)~86°F(30.0°C)
54°F(12.2°C)~78°F(25.5°C)
5
64°F(17.7°C)~86°F(30.0°C)
54°F(12.2°C)~76°F(24.4°C)
6
66°F(18.9°C)~86°F(30.0°C)
54°F(12.2°C)~74°F(23.3°C)
7
68°F(20.0°C)~86°F(30.0°C)
54°F(12.2°C)~72°F(22.2°C)
C
Electric
Heat Pump
C
Electric Heater
Off
On
Cooling Only
Heat Pump Only
Cooling : 0{54 °F(12.2 °C)~86 °F(30.0 °C)}
Heating : 0{54 °F(12.2 °C)~86 °F(30.0 °C)}
Cooling : 5{64 °F(17.7 °C)~86 °F(30.0 °C)}
Heating : 5{54 °F(12.2 °C)~76 °F(24.4 °C)}