ENGLISH
192
INSTALLER’S SETTING OPTIONS
h
Dry contact setting value
- 00: manual
- 01: automatic
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
Select dry contact mode setting code value ‘09’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
At the Value 1 field, press the ‘
▲
’, ‘
▼
’ button to select dry contact setting value, and press
‘Done’ button to apply the dry contact mode setting.
- If you do not press ‘Done’ button, your settings will not be applied.
Dry contact mode setting (air conditioner / DX type ventilator)
What is a dry contact?
It refers to the contact point signal input such as a hotel card key, human body detection sensor,
etc. is used with the air conditioner.
h
If no buttons are pressed for about 60 seconds after the setting, it automatically exits from the
setting mode.
NOTE
!
For detailed functions related to the dry contact mode, refer to the dry contact manual.
INSTALLER’S SETTING OPTIONS
h
Operation setting value
- 00: slave
- 01: master
●
At the Value 1 field, press the ‘
▲
’, ‘
▼
’ button to select operation setting value, and press
‘Done’ button to apply the master / slave setting.
- If you do not press ‘Done’ button, your settings will not be applied.
NOTE
!
Master/slave operation is not available with all products
h
If no buttons are pressed for about 60 seconds after the setting, it automatically exits from the
setting mode.
h
Operation master / slave selection function may not work in some products.
h
When the slave operation function is selected, 'linked control' is displayed in the remote con-
troller display window as in the figure below