INSTALLER’S SETTING OPTIONS
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
At the Code field select operation master / slave setting code value ‘08’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
Operation master / slave setting
(air conditioner / General, DX type ventilator)
This function sets the indoor unit to either slave or master mode depending on the input code
value.
Remote controller
Function
Master
During the group control, the indoor units are operated based on the remote con-
troller. (It is set as master at as shipped.)
Slave
During the group control, all remote controllers except 1 master remote con-
troller are set as slaves.
h
If no buttons are pressed for about 60 seconds after the setting, it automatically exits from the
setting mode.
INSTALLER’S SETTING OPTIONS
h
Remote controller setting value
- 00: slave
- 01: master
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
At the Code field select remote controller master / slave setting code value ‘07’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
At the Value 1 field, press the ‘
▲
’, ‘
▼
’ button to select remote controller setting value, and
press ‘Done’ button to apply the remote controller master / slave selection input.
- If you do not press ‘Done’ button, your settings will not be applied.
Remote controller master / slave setting
(air conditioner / Gerneral, DX type ventilator)
This function sets configuration for the master/slave setting through the remote controller.