THE INDOOR UNIT INSTALLATION
ENGLISH
• Normal conditions: Temperature of 30 °C, relative humidity of 85 %
• Unfavorable conditions: Temperature of 30 °C, relative humidity of 90 % (humid places such as
bathrooms, swimming pools, etc.: air supply and exhaust fan installation)
applies to
Insulation material standard
(mm)
(besides normal conditions for
residential use)
Insulation material standard (mm) - residential
Insulation material
standard (mm)
(unfavorable
conditions)
If installed in an air-conditioned
place (CASE 1)
(ex: bedroom, living room, etc.)
If installed in a non-air
conditioned place (CASE 2)
(ex: hallway, outdoors, etc.)
Refrigerant piping
dimensions (mm)
EPDM
EPDM
EPDM
EPDM
Gas piping
6.35
9.52
12.7
15.88
19.05
22.22
25.40
28.58
31.75
38.1
44.45
19
19
19
19
19
19
19
19
19
25
25
13
13
13
13
13
13
19
19
19
19
19
19
19
19
19
19
19
19
19
19
25
25
19
25
25
25
25
32
32
32
32
32
32
Liquid
piping
6.35
9.52
9
9
9
9
12.7~44.45
13
13
13
13
HEAT INSULATION
- Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance
(over 120 °C).
- Precautions in high humidity circumstance:
This air conditioner has been tested according to the "KS Standard Conditions with Mist" and
confirmed that there is not any default. However, if it is operated for a long time in high humid
atmosphere (dew point temperature: more than 23 °C), water drops are liable to fall. In this case,
add heat insulation material according to the following procedure:
- Heat insulation material to be prepared... Adiabatic EPDM or NBR with thickness 10 to 20 mm.
- Stick glass wool on all air conditioners that are located in ceiling atmosphere.
Indoor
unit
Thermal insulator
(accessory)
Fastening band
(accessory)
Refrigerant
piping