- 46 -
Check Point
1. Check the power source.(230V ±15%)
2. Check the fan operation is right.
3. Check the current.
4. Check the install condition.
5. Check the CT Sensor Output signal
(AHUW096A3 - Check output the CT Sensor : DC 2.5±0.2V
AHUW146A2/AHUW126A3/AHUW146A3/AHUW166A3 - Check output pin 2.3 of the CT Sensor : DC 2.5±0.2V
AHUW128A3/AHUW148A3/AHUW168A3 - Check input_current_T_PFC and R_PFC of the CT sensor : DC 2.5±0.2V)
IN/I
GND
<CT Sensing Check Point>