Cycle Troubleshooting Guide
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power (About AC 220V, 60Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting
cable
• Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
• Connector related to CN-NI, RY-COMP NO.3
• Connector related to CN-MOTOR
• Connector contacting of Outdoor Fan/Compressor
• Display PCB Assembly Check
Check each load(Indoor/Outdoor Fan Motor,
Compressor, Stepping Motor) and contacting
condition of related connector
Main PCB Board Operation Check
Items
• SMPS Transformer
(Indoor unit)
- Input Voltage
- Output Voltage(C03D)
• IC01D(7805) Output
(Indoor/Outdoor unit)
• IC01A(KIA7036, Reset IC)
OSC01B(8MHz)
• Replace Trans
• Replace IC01D
• Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About DC12V
• DC +5V
• Voltage of IC No.1,
(DC +4.5V over) and Soldering condition.
Content
Remedy
NO
YES
(After 10 seconds)
34
Multi Air Conditioner
Содержание T2UC182FAA
Страница 15: ...Service Manual Electronic Control Device Outdoor Unit 15 ...
Страница 16: ...Multi Air Conditioner Electronic Control Device Display P C B ASM 16 ...
Страница 18: ...Schematic Diagram 18 Multi Air Conditioner ...
Страница 25: ...25 Service Manual Operation Details Remote Control Operations ...
Страница 40: ...Multi Air Conditioner Installation 40 ...
Страница 51: ...P No December 2007 Printed in China ...