Cycle Troubleshooting Guide
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: over the rated
current
Temp. difference
: over 8°C
Temp. Difference
Operating Current
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
High
Defective compressor
Current is low.
Normal
Excessive amount of
High pressure does not quickly
refrigerant
rise at the beginning of operation.
Insufficient amount of
Current is low.
Lower
Higher
refrigerant(Leakage)
Clogging
Current is low.
Higher
Service Manual 33
Содержание T2UC182FAA
Страница 15: ...Service Manual Electronic Control Device Outdoor Unit 15 ...
Страница 16: ...Multi Air Conditioner Electronic Control Device Display P C B ASM 16 ...
Страница 18: ...Schematic Diagram 18 Multi Air Conditioner ...
Страница 25: ...25 Service Manual Operation Details Remote Control Operations ...
Страница 40: ...Multi Air Conditioner Installation 40 ...
Страница 51: ...P No December 2007 Printed in China ...