background image

8

PARTS AND INSTALLING THE CONTROLLER

NOTE

  Failure to follow the guidelines may result in part 

damage due to interference with the mechanical.
Be careful not to let the cable pass over the 
wireless equipment.

  You can arrange the lines more easily while placing 

the top cover and fastening as shown in the figure 
2.

Top cover

7

Place top cover on back cover and gently press 
to close.

8

Fasten a screw to assemble top and bottom 
cover.

Using Group control

Control by connecting 2 to 16 air conditioner indoor 
units 6 to one wired remote controller.

GND

GND

DC 12 V

Signal wire

Signal wire

NOTE

  Connect using the group control cable. 

(Model : PZRCWRCG3)

   When using the group control, some advanced 

functions (excluding basic operation setting, fan 
speed, lock, and  time setting) may be limited.

1

Set one indoor unit to master and the remaining 
to slave.

#3 switch OFF: 

Master (Factory

default setting)

#3 switch ON: 

Slave

  For ceiling type cassette and duct product, 

change the switch setting of the indoor PCB.

  For wall-mount type and stand type product, 

change the master/slave setting with the 
Wireless remote controller

2

After completing the master/slave setting, turn 
Off the power of the indoor unit, and turn On the 
power after 1 minute.

  2-Remo function is not supported.

Содержание PREMTA200

Страница 1: ...ht 2021 LG Electronics Inc All rights reserved MFL71781801 Rev 01_030421 Read this owner s manual thoroughly before operating the appliance and keep it handy for reference at all times TYPE WIRED REMOTE CONTROLLER AIR CONDITIONER EN ENGLISH FR FRANÇAIS ES ESPAÑOL ...

Страница 2: ...YOUR RECORDS 7 PARTS AND INSTALLING THE CONTROLLER 7 Parts 7 Installing the controller 9 STANDARD OPERATION 9 Installation wizard 10 View Screen 11 Standard Operation 14 ADVANCED FUNCTION 16 SCHEDULE 19 ENERGY 20 SETTINGS 20 General setting 21 Air conditioner Ventilator setting 23 SVC Contents 24 INSTALLER SETTING 28 USING LG THINQ APPLICATION 29 SPECIFICATIONS ...

Страница 3: ... including the following Installation or repairs done by unauthorized persons can pose hazards to you and others Installation MUST conform to the local building codes or in the absence of local codes the National Electrical Code NFPA 70 ANSI C1 1003 or current edition and Canadian Electrical Code Part 1 CSA C22 1 The information contained in this manual is intended for use by a qualified service t...

Страница 4: ...aning or maintenance There is a risk of water leakage electric shock or serious injury Take care to ensure that the power cable cannot be pulled out or damaged during operation There is a risk of fire or electric shock Do not touch operate the product with wet hands There is a risk of electrical shock Operation Be sure to use only those parts which are listed in the SVC parts list Never attempt to...

Страница 5: ...ot install the unit in potentially explosive atmospheres Operation The appliance is not intended for use by young children or infirm persons without supervision Do not press the screen using powerful pressure There is a risk of product break down or malfunction Maintenance Contact the dealer for repair or maintenance Do not wipe the controller operation panel with benzine thinner chemical dust clo...

Страница 6: ...hnician for repair or maintenance of this unit Contact an installation specialist for installation of this unit The air conditioner is not intended for use by young children or disabled individuals without supervision Young children should be supervised to ensure that they do not play with the air conditioner When the power cord needs to be replaced replacement work should be performed by authoriz...

Страница 7: ...e screw terminals for field wiring Extension cable PZCWRC1 is required The green Molex connector of connector of this cable connects to the indoor unit The white Molex connector of this cable is removed and connect the wires to the Remote controller as described below 1 Pull the cable from the wall and check the cable direction to install 2 Align the back cover and check location of two mounting h...

Страница 8: ...d remote controller GND GND DC 12 V Signal wire Signal wire NOTE Connect using the group control cable Model PZRCWRCG3 When using the group control some advanced functions excluding basic operation setting fan speed lock and time setting may be limited 1 Set one indoor unit to master and the remaining to slave 3 switch OFF Master Factory default setting 3 switch ON Slave For ceiling type cassette ...

Страница 9: ...ation Wizard menu is confirmed 4 The Finish button will be activated after all the Installation Wizard menus are confirmed 5 The installation is finished once the Complete button is tapped NOTE If the installation of wizard is not complete it will run at every booting After completing the installation of Wizard you can check a list of items of installation of Wizard at Setting SVC Contents Setup R...

Страница 10: ...nformation 2 Air Quality Level 3 System Monitoring NOTE Swipe left or right to switch between screens Please check the detailed description of each screen in the detailed description page The Operating Information screen displays the following according to the indoor unit connected 1 Air conditioner 2 General ventilation 3 DX ventilation 4 Interlocking operation of air conditioner ventilation ...

Страница 11: ...e differences Ventilation Auto General DX Sense the indoor and outdoor temperature and automatically operate in optimum ventilation mode OFF O O Product operation is stopped Emergency Heater O After the emergency heater is set up for use the operation mode can be selected in the emergency heating operation condition using the heater Air purify O Single operation of an air purifier Power Heat O Inc...

Страница 12: ...an operation cannot set desired temperature The setting temperature may vary depending on the type of indoor unit Fan speed setting Select the fan speed icon to select the desired fan speed from the options list Option Low Med Med High Power Auto NOTE Depending on the product some functions cannot be set Auto can only be used when installing CO2 sensors when using ventilation products Advanced fun...

Страница 13: ...e air purifying icon on the home screen NOTE The air purifying icon is only displayed when air purifying is on and operating The total index shows the worst of the 3 dust state values as representative values You can go to the air purifying display screen by flipping the screen on the home screen Monitoring information The monitoring information can be checked by swiping left or right from the hom...

Страница 14: ...ring cooling operation On Off It s only possible when you re operating with cooling Can t be used simultaneously with smart mode and refresh mode Fan Auto O O This function is set for the indoor fan operation when the indoor unit thermal is off On Off If set to ON fan operation keeps on after thermal operation of indoor units Comfort Cooling O DX The product will continue to operate even after the...

Страница 15: ...zone control function and be equipped with damper controls device Set Zone type and number first Tab the zone to use and control to set it on off Additional operation O Set advanced operation of ventilation products Off Fast Energy save Ventilate quickly by quick setting It effectively ventilates and performs savingpower function Wind direction O Select the wind direction you want Smart mode Smart...

Страница 16: ... When the start time is in the afternoon PM and the end time is in the morning AM the schedule after midnight will be set as a schedule in the following day Please set the day of the week for which the schedule is to be operated in Editing of the schedule will be completed and returned to the schedule status screen NOTE Only one schedule mode can be set for any given time period The schedule can b...

Страница 17: ...ill be initialized Vacation Event 1 Set the date time and product operation standards to use vacation mode Select Back to complete the setup 2 On the set date the setup information is displayed at the top and the registered schedule operation is hold NOTE During vacation mode the vacation mode may be disabled if operation mode or desired temperature is changed Switch season 1 You can set a differe...

Страница 18: ...ion schedule 3 Schedule hold temporary schedule The currently running schedule is temporarily suspended and is temporarily operating in another mode Displays the types of schedule hold Displays the schedule hold function duration and the time can be set when tapped Schedule hold will end immediately when tapped NOTE When the setting is changed for one of the three items Operating mode Desired Temp...

Страница 19: ...heck the trend of outdoor unit operation rate indoor temperature and desired temperature information during the day Usage graph You can compare energy usage time power usage on a weekly monthly annual basis You can check by usage time wattage NOTE Depending on the units selected the accumulated energy usage power over a day week month is displayed ...

Страница 20: ...for air conditioner and ventilation products by Home Sleep Away Awake schedule mode of the current season Refer to the content of Schedule setting Edit schedule mode Date Time Set the date time and summer time to display on the screen Vacation event You can use the product by temporarily changing the schedule operation Select by toggling on off of the function usage and set the setting period and ...

Страница 21: ...Vanes are controlled as standard movements for each product each product each product Elevation Grill O When cleaning the indoor unit filter move the elevation grill up and down move the elevation grill up and down Up Stop Down Robot Cleaning O After using the air conditioner for a certain period of time it is the cleaning function of the kit attached to the product Available after 30 seconds of o...

Страница 22: ... My Favorite Temperature O This function remembers the desired temperature that the user frequently sets and automatically sets it during the initial operation On off CO2 Fan Control O This function sets the FAN operating standards based on the CO2 concentration of ventilation products Fan Control During Operation On Fan Control During Operation Off Off Low Periodic Off Periodic Human Detection Mo...

Страница 23: ...ter possible contact number Model Information You can check the connected indoor outdoor unit product information Model Name Check the model information of the wired remote controller in use SW version The version information of the SW you are using is displayed Control History Error history and information can be checked Open Source License Open source information is displayed Setup Various setti...

Страница 24: ...sword If SW version is 1 00 0a password is 1000 Tap the Magnifier icon in the upper right corner making it easy to find what you want Auto complete items are displayed based on the characters you enter You can also search by the code number of installer setting Various settings can be made during the installation step before using air conditioner ventilation products ...

Страница 25: ... Contact Mode O O This function activates inactivates the dry contact auto function Automatic Manual Fixed Air Volume O O This function sets the fan speed mode of the indoor unit to variable fixed Variable Operate to set fan speed at COMP ON Operate to low fan speed at COMP OFF Fixed Operate to set fan speed at COMP ON Operate to set fan speed at COMP OFF Zone type O This function sets the type of...

Страница 26: ... CN EXT O O This function determines the use of the CN_EXT port of the indoor unit Not use Use simple dry contact setting Simple operation control Simple operation On Off Single emergency stop Indoor unit single emergency stop Occupied Unoccupied Occupied Unoccupied All emergency stop Indoor unit all emergency stop It can be set only when there is indoor unit emergency stop function Window contact...

Страница 27: ...unit Indoor unit Physical address O Set the physical address of the indoor unit Thermopile sensor O Set whether to use the floor thermopile sensor On off Air supply ESP O It is the function to set the air supply fan speed value Fan Speed RPM Low High Turbo 0 255 Air Discharge ESP O It is the function to set the exhaust fan speed value Fan Speed RPM Low High Turbo 0 255 Product Direction O It is th...

Страница 28: ...to set remote controller exclusive functions such as schedules NOTE Bluetooth function is not supported Even when the Wired Remote Controller ThinQ App is connected the image of the connected indoor unit will be displayed on the ThinQ App screen Please change the name displayed in the App to differentiate it from the Indoor Unit ThinQ App connection The Wired Remote Controller ThinQ App connection...

Страница 29: ...installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on...

Страница 30: ...f the device IC Radiation Exposure Statement This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment This equipment should be installed and operated with a minimum distance of 20 cm 7 8 inches between the antenna and your body NOTE THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY RADIO OR TV INTERFERENCE CAUSED BY UNAUTHORIZED MODIFICATIONS TO THIS EQUIPMENT ...

Отзывы: