ROTARY SWITCH SETTING
33
ENGLISH
Function of each Dip switch
No
Switch name
ON
OFF
Function
1
AHU type (1)
For 100%
Fresh Air
For cooling/
heating
ON: Dehumidification/automatic ven-
tilation impossible
2
Outside air tempera-
ture/humidity sensor
Applied
Not applied
OFF: dehumidification/power saving
impossible
3
Mixing air
temperature sensor
Applied
Not applied
Preheating is not possible for cool-
ing/heating
4
Return
temperature/humidity
sensor
Applied
Temperature
sensor applied
OFF: Dehumidification/humidificat-
ion/power saving not possible
(temperature sensor applied)
5
Supply air temperature
/ Humidity sensor
Applied
Temperature
sensor applied
OFF: Temperature sensor applied
6
CO
2
sensor
Applied
Not applied
OFF : Automatic ventilation impossi-
ble
7
Return/supply air flow
sensor
Applied
Not applied
OFF: Retufn fan inverter not possible
8
Filter pressure
difference sensor
Applied
Not applied
ON: Sensor value is the base for filter
cleaning alarm
9
Supply static pressure
sensor
Applied
Not applied
OFF: Supply fan fan inverter not pos-
sible
10
Humidifier
Applied
Not applied
OFF: Humidification not possible
11
Preheating coil
Applied
Not applied
OFF: Preheating is not possible
12
Preheating coil types
Electric
heater
Hot
water/steam
-
13
Dry contact operation
selection
Applied
Not applied
ON: Operate in dry contact operation
mode
14
Central control com-
munication selection
ModBus
LGAP
ON: Use ModBus Protocol
15
Outdoor unit set
temperature control
Applied
Not applied
ON: During Thermal On/Off, outdoor
unit operates with time difference