![LG PRCKD21E Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/lg/prckd21e/prckd21e_installation-manual_211973029.webp)
AHU SENSOR CONNECTION
29
ENGLISH
- CO
2
sensor(option)
313
G0
G
DC 0~10 V (U)
Ground (G0)
AC 24 V (G)
Terminal block #2
Detail
Ⓕ
*Option SW101 : Dip S/W No. 6 ON
CONTROL KIT inside
Example) CO
2
sensor connection
1. For details of CO
2
sensor installation, work by referring to the enclosed manual when you
purchased CO
2
sensor.
2. All cables shall be finished with flexible pipes.
Item
Specification
Remark
CO
2
sensor
- Power: AC 24 V
- output signal: DC 0~10 V
- boundary: 0~2 000 ppm
Option
CAUTION
• Due to wrong connection of the sensor, AHU Main PCB and sensor may be burnt.
Before supplying the power, make sure to check whether there is a wrong connection.
!