Installation/Owner's Manual
2-33
ENGLISH
2. Installing ACP
Setting the functions of the ACP
The following functions can be set by using the menu of the ACP:
• Select Peak or Demand
• Select the web display language
• Set the schedule to use
• Set the wattage display to use
The function setting of the ACP should be changed depending on the case that only the ACP is used
or the case that the ACP is interconnected with the external devices such as AC Manager, Wattmeter
and Demand controller.
In general, the function of the ACP should be set and used as follows:
Before setting the functions of the ACP
ACP only
ACP interconnected
with AC Manager
ACP interconnected
with Demand controller
Set to Peak function
Set to Demand function
Set to Demand
function
Set the schedule
Set the schedule
Set the schedule
function to use
function not to use
function to use
Set to use if interconnected woth the wattmeter or set not to use if not.
Select Peak or Demand
Schedule
Wattage display
Caution: Setting the wattage display to use
If the ACP and the wattmeter are not connected, the wattage display function should
be set not to use. If it is set to use, be careful of it because the control speed of the
ACP is getting slow.