15
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
INSTALLATION
0 V U 5 U 4 0 V U 3 U 2 0 V U 1
1
4
3
2
1. Wire the shielded, twisted cable (1), 61m (200 ft) max, to Binary Input, dry contacts (2).
2. Cut and tape back shield wire (3) at sensor end (2).
3. Connect the other end of shield wire to ground (4) (for example, use a stud in an enclosure).
Types of Output Wiring
MS-E10 provides 3 triac digital outputs and 2 0-10 Vdc analog outputs. Triacs are not powered by the controller.
Binary Triac Output Wiring
NOTE: Triac outputs are suitable for AC only. DC loads and dry contacts require an intermediate relay.
NOTE: Never use a controller’s power transformer to power I/O loads. Using the controller’s transformer introduces
potentially damaging switching transients into the unit.
A
B
B
A
B
A
D3
D2
D1
1
2
3
1
! 24 VAC
1
Each digital triac output (1) is rated at 24 Vac +/- 15%, 50/60Hz, at 0.5 A max. Outputs are normally open, floating and do not share
a common pin.
Analog Output Wiring
Analog outputs (AO) are referenced by the terminals labeled AO
n
and 0 V. Each AO can supply a maximum of 4 mA over the entire
0 to 10 Vdc range. The minimum input impedance of a device controlled by an AO must be greater than 2500 ohms.
Accuracy of the AO is specified at +/- 2% of full scale, with a max load of 4 mA. If the AO is operated with a load that is within spec,
the deviation will be less than 2% of full scale (200 mV) over the specified operating temperature range.