background image

14

LG MultiSITE

TM

 E10 Controller

Due to our policy of continuous product innovation, some specifications may change without notification.  

©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.

INSTALLATION

0V U5 U4 0V U3 U2 0V U1

0-10

Vdc

+

1

4

2

3

1.  Use shielded, twisted cable (1) 61m (200 ft) max.
2.  Cut and tape back shield wire (2) at sensor (3) end.
3.  Connect the other end of shield wire to ground (4) (for example, use a stud in an enclosure).

4-20 mA UI Wiring

The inputs support self-powered 4–20 mA sensors. Input accuracy is ±2% of span, without user calibration. Use a 499 ohm resistor 

wired across the input terminals.

NOTE: When using an externally powered 4–20 mA sensor, be sure to de-energize its power supply before making or 

changing any wiring connections to the MS-E10 Controller. 

This is in addition to removing power from the MS-E10 Controller. 

DO NOT apply external power to the UI inputs without the 499 ohm 

resistor in place. Otherwise, even a momentary application of power (for example, 24 Vdc) to the UI terminals without the resistor may damage 

circuitry on the MS-E10 Controller. Only after completing all input wiring should you restore power to such external power supplies. 

0 V   U 5   U 4   0 V   U 3   U 2   0 V   U 1

i

+

-

1

4

5

2

3

4.  De-energize the 4-20 mA sensor (3) and remove any power from the MS-E10. See Note, above. 
5.  Use shielded, twisted cable (1) 61m (200 ft) max.
6.  Cut and tape back shield wire (2) at sensor (3) end.
7.  Connect the other end of shield wire to ground (4) (for example, use a stud in an enclosure).
8.  Wire the supplied 499 Ohm resistor (5) across input terminals. See Note, above.

Binary Input UI Wiring

The universal inputs support normal dry (equipment status) contacts. Standard dry contacts must have a 1 Hz (or less) COS frequency, 

with minimum dwell time > 500 ms (contacts must remain open at least 500 ms and be closed at least 500 ms). Dry contacts support 11 

Vdc open circuits or 733 µA short-circuit current.

Содержание PBASE10

Страница 1: ...INSTALLATION MANUAL LG MultiSITETM E10 CONTROLLER Model Number PBASE10 ...

Страница 2: ...or proper installation For more technical materials such as submittals engineering databooks and catalogs visit www lghvac com For continual product development LG Electronics U S A Inc reserves the right to change specifications without notice LG Electronics U S A Inc This document as well as all reports illustrations data information and other materials are the property of LG Electronics U S A I...

Страница 3: ...ty Instructions 4 Introduction 7 Description 8 Default Login Credentials 8 Installation 9 Environmental Requirements 9 Mounting On DIN Rail 9 Connector Locations 10 Wiring 10 Daisy Chain and Network Device Limits 12 Using DHCP 12 Using Rapid Spanning Tree Protocol RSTP 12 Types of Input Wiring 13 Types of Output Wiring 15 Power up and Checkout 17 Article 33 Communication 19 Agency Certifications 1...

Страница 4: ...in death or serious injury WARNING This symbol indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION This symbol indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury Note This symbol indicates situations that may result in equipment or property damage accidents only This symbol indicates a...

Страница 5: ... controlled environment relatively free of contaminants There is risk of electric shock and physical injury or death Secure all field wiring connections with appropriate wire strain relief Improperly securing wires will create undue stress on equipment power lugs Inadequate connections may generate heat cause a fire and physical injury or death Ensure the system is connected to a dedicated power s...

Страница 6: ...o not allow water dirt or animals to enter the controller There is risk of unit failure or degraded performance Do not spill water or other liquid on the inside of the controller Do not drop the controller into water If the unit is immersed in water or other liquid contact your local authorized LG distributor for support There is risk of unit failure or degraded performance Remove all power to con...

Страница 7: ... generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment ...

Страница 8: ...connector for analog outputs Eight position connector for Universal inputs Two position power connector and a grounding wire 499 Ohm resistors Qty 5 for universal input use This MS E10 Controller Installation Manual Material Tools Required One of the following UL listed Class 2 24 Vac transformer rated at minimum of 7 VA A dedicated transformer is re quired cannot power additional equipment or Use...

Страница 9: ...ing temperature upper limit Any other mounting orientation reduces this upper limit Mounting On DIN Rail 1 Pull the controller s locking clip 1 down 2 Tilt the controller to hook over the DIN rail 2 3 Push down and in on the unit to fasten to the rail 3 4 Push locking clip 4 up and click into place to secure 5 Carefully secure both ends of the final assembly with DIN rail end clips 5 provided by t...

Страница 10: ... 45 connectors with integrated LEDs 8 DEBUG port for serial debug communication Wiring Refer to Connector Locations and the following images to locate connectors and other components Descriptions are provided for wiring to ground to power RS 485 Ethernet Inputs and Ouputs Wiring Earth Ground Power 24 VAC DC GND FACTORY RESET DEBUG SEC PRI 24 Vac 50 60Hz 24 Vdc 4 2 DC AC 1 3 5 NOTE Because the MS E...

Страница 11: ... are permanently connected There is no built in termination resistor Maximum total cable length is 1 000 feet 304 8 meters Connect the shield wire to earth ground at the MS E10 Controller end only The following image shows example wiring UNIVERSAL INPUTS 1 U V 0 U2 U3 U4 U5 0V 0V ANALOG OUTPUT RS485 0V 0V AO2 AO1 S A A 24 VAC DC GND FACTORY RESET DEBUG DIGITAL OUTPUTS A B B A B A D3 D2 D1 SEC PRI ...

Страница 12: ...S A B B A B A D3 D2 D1 UNIVERSAL INPUTS 1 U V 0 U2 U3 U4 U5 0V 0V ANALOG OUTPUTS RS485 0V 0V AO2 AO1 S A A 24 VAC DC SEC PRI GND FACTORY RESET DEBUG DIGITAL OUTPUTS A B B A B A D3 D2 D1 Using DHCP Upon first startup when IP connectivity is detected the MS E10 Controller initially requests an IP address via DHCP If a DHCP ad dress is not found the controller reverts to a static IP address based on ...

Страница 13: ...ature sensors You can also edit and export for reuse customized thermistor curve xml files See the NRIO Driver Guide for details 0 V U 5 U 4 0 V U 3 U 2 0 V U 1 1 2 4 3 1 Use shielded twisted cable 1 61m 200 ft max 2 Cut and tape back shield wire 2 thermistor 3 end 3 Connect the other end of shield wire to ground 4 for example use a stud in an enclosure Resistive 0 100K ohms UI Wiring The inputs c...

Страница 14: ... the MS E10 Controller DO NOT apply external power to the UI inputs without the 499 ohm resistor in place Otherwise even a momentary application of power for example 24 Vdc to the UI terminals without the resistor may damage circuitry on the MS E10 Controller Only after completing all input wiring should you restore power to such external power supplies 0V U5 U4 0V U3 U2 0V U1 i 1 4 5 2 3 4 De ene...

Страница 15: ...le for AC only DC loads and dry contacts require an intermediate relay NOTE Never use a controller s power transformer to power I O loads Using the controller s transformer introduces potentially damaging switching transients into the unit A B B A B A D3 D2 D1 1 2 3 1 24 VAC 1 Each digital triac output 1 is rated at 24 Vac 15 50 60Hz at 0 5 A max Outputs are normally open floating and do not share...

Страница 16: ...ts are suitable for AC only DC loads and dry contacts require an intermediate relay NOTE Never use a controller s power transformer to power I O loads Using the controller s transformer introduces potentially damaging switching transients into the unit A B B A B A D3 D2 D1 1 2 3 1 24 VAC 1 Each digital triac output 1 is rated at 24 Vac 15 50 60Hz at 0 5 A max Outputs are normally open floating and...

Страница 17: ...erial debug communications 7 FACTORY RESET Pushbutton switch to return the controller to factory default settings Power Up and Initial Checkout 3 Apply power by inserting the 2 position 24 V power connector plug 1 4 Check that the green STAT 2 and yellow BEAT 3 LEDs are flashing as described below Status LED indications When power is applied the green STAT LED illuminates This indicates the system...

Страница 18: ...ler Use a serial terminal program for example PuTTY to access the controller system shell menu This provides access to some basic platform settings Default DEBUG port settings are 115200 8 N 1 baud rate data bits parity stop bits For details on using a serial connection to the DEBUG port see the MS E10 Install and Startup Guide Tab Mounting option 1 6 71 in 170 5 mm 4 33in 115mm 6 38 in 162 mm 7 0...

Страница 19: ...nce meeting the criteria in Article 57 and identified in accordance with Article 59 1 in a concentration above 0 1 weight by weight w w shall provide the consumer with sufficient information available to the supplier to allow safe use of the article including as a minimum the name of that substance Our duty is to inform you that the substance s listed below may be contained in these products above...

Страница 20: ...LG Electronics U S A Inc Air Conditioning Technologies 4300 North Point Parkway Alpharetta Georgia 30022 www lghvac com IM_MultiSITE_E10_Controller_03_21 ...

Отзывы: