Installation Manual
11
ENGLISH
Installation
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon the
evaporator.
• Ensure that water flows drain hose of indoor
unit without any leakage.
Checking the Drainage
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
THERMAL INSULATION
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for refrigerant pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose crip for thermal insulator(Local supply)
Union for liquid pipe
Refrigerant pipe and thermal
insulator(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe
(Local supply)
Hose crip for thermal insulator
(Local supply)
WARNING : Loose wiring may cause the terminal to overheat or result in unit
malfunction.
A fire hazzard may also exist.
Therefore, be sure all wiring is tightly connected.
Connection method of the connecting cable(Example)
Lock nut
Conduit
mounting
plate
Conduit
1(L1) 2(L2)
3(A)
4(B)
Power Supply
High Voltage
(208/230V)
Transmission