Installation Manual
23
ENGLISH
How to Set E.S.P?
URNU763B8A2, URNU963B8A2
(Unit;cmm (cfm))
Note: 1. The above table shows the correlation between the air rates and E.S.P.
Setting Value
60
40.5(1430)
-
-
-
-
-
-
-
-
65
52.7(1861)
-
-
-
-
-
-
-
-
70
63.7(2249) 47.1(1663)
-
-
-
-
-
-
-
75
71.1(2511) 56.9(2009) 44.7(1578)
-
-
-
-
-
-
80
76.3(2694) 69.7(2461) 55.2(1949)
-
-
-
-
-
-
85
83.3(2941) 78.6(2775) 67.4(2380) 55.9(1974)
-
-
-
-
-
91
89.7(3167) 87.1(3076) 78.9(2786) 67.6(2387) 54.2(1914)
-
-
-
-
95
93.4(3298) 91.4(3227) 86.1(3040)
77(2719) 66.4(2345) 50.6(1787)
30(1059)
-
-
100
93.4(3298) 91.4(3227) 88.3(3118) 84.9(2998) 75.9(2680) 69.5(2454) 60.8(2147) 43.1(1522)
-
105
93.2(3291) 91.3(3224) 88.3(3118) 84.9(2998) 81.1(2864) 77.4(2733) 69.2(2443) 67.9(2398) 51.3(1811)
6(0.23)
9(0.35)
12(0.47)
15(0.59)
18(0.71)
20(0.79)
22(0.86)
23(0.90)
25(0.98)
Static Pressure(mmAq (in.Aq))