38
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19 100)
Ø 6.35(1/4)
Ø 12.7(1/2)
< 16.0(54 600)
Ø 9.52(3/8)
Ø 15.88(5/8)
≤
22.4(76 400)
Ø 9.52(3/8)
Ø 19.05(3/4)
< 36.4(124 200)
Ø 9.52(3/8)
Ø 22.2(7/8)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity(HP)
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
4
Ø 9.52(3/8)
Ø 15.88(5/8)
5
Ø 9.52(3/8)
Ø 15.88(5/8)
6
Ø 9.52(3/8)
Ø 19.05(3/4)
8
Ø 9.52(3/8)
Ø 19.05(3/4)
10
Ø 9.52(3/8)
Ø 22.2(7/8)
12
Ø 12.7(1/2)
Ø 28.58(11/8)
Outdoor unit Connection
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19 100)
Ø 6.35(1/4)
Ø 12.7(1/2)
< 16.0(54 600)
Ø 9.52(3/8)
Ø 15.88(5/8)
≤
22.4(76 400)
Ø 9.52(3/8)
Ø 19.05(3/4)
≤
28.0(95 900)
Ø 9.52(3/8)
Ø 22.2(7/8)
WARNING
!
• In case of pipe diameter B connected after first branch is bigger than the main pipe
diameter A, B should be of the same size with A.
CAUTION
• Bending radius should be at least twice the
diameter of the pipe.
• Bend pipe after 500 mm or more from
branch(or header).
Do not bend U type.
It may cause Performance unsatisfactory or
noise.
!
500 mm or more
500 mm or more