Outdoor unit Connection
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
≤
22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
≤
28.0(95,900)
Ø9.52(3/8)
Ø22.2(7/8)
WARNING
• In case of pipe diameter B connected after first branch is bigger than the main pipe diame-
ter A, B should be of the same size with A.
!
36
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
CAUTION
• Bending radius should be at least twice the
diameter of the pipe.
• Bend pipe after 500mm or more from
branch(or header).
Do not bend U type.
It may cause Performance unsatisfactory or
noise.
!
500mm or more
500mm or more
1,MFL67798026,영영 19. 3. 14. 영영 4:49 Page 36
Содержание MULTI V S ARUV025GSR0
Страница 70: ...70 ENGLISH 1 MFL67798026 영영 19 3 14 영영 4 49 Page 70 ...
Страница 71: ...1 MFL67798026 영영 19 3 14 영영 4 48 Page 100 ...