INSTALLATION
19
ENGLISH
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the Unit’s
legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
At least 100mm
At l
east 100
mm
At least 100m
m
At least 100mm
At least 100mm
At least 100mm
Center of the Unit
For outdoor units should not
be supported only by the
corner supports.
Center of the Unit
a
b
e
e
c
d
ARUV025GSR0
ARUV030GSR0
ARUV040GSR0
ARUV050GSR0
ARUV060GSR0
a
920
1,090
b
618
700
c
330
380
d
360
401
e
151
195
INSTALLATION
[Unit : mm]