32
ENGLISH
Service unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn8” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF “, “ op1 “ ~ “op7 “ Push the ‘
●
’ button
Target pressure is set
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“HEAT” , “COOL” Push the ‘
●
’ button
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
Target pressure adjusting
Mode setting method
Mode
Low Pressure (kpa)
High pressure (kpa)
oFF
804
2990
op1
699
3121
op2
739
2827
op3
843
2696
op4
908
2565
op5
961
2435
op6
1026
2304
op7
804
2990
1,MFL69717904,영영 18. 8. 29. 영영 2:50 Page 32