17
ENGLISH
Y branch, Header and HR unit connection pattern
Pattern 1
Pattern 2
Pattern 3
HR1
HR1
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
1
1
2
2
3
4
5
6
7
HR2
2.1kW
(7kBtu/h)
2.1kW
(7kBtu/h)
2.1kW
(7kBtu/h)
2.1kW
(7kBtu/h)
2.1kW
(7kBtu/h)
7.25kW
(24kBtu/h)
7.25kW
(24kBtu/h)
3
4
B
HR1
1
2
3
4
Pattern 4
1
2
3
4
• The maximum total capacity of indoor
units is 58kW(192 kBtu/h).
• The maximum total capacity of a branch
pipe of HR unit is 14.5kW(48 kBtu/h).
• Impossible installation : Head branch pipe
→
HR unit
• Impossible installation : HR unit
→
Head branch
pipe
→
Y and Head branch pipe.
HR1
B
B
A
14.5kW
(48kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
Pattern 5
HR1
HR1
A
B
1
2
HR2
3
4
Pattern 6
A
A
A
1
2
3
4
5
14.5kW
(48kBtu/h)
7.25kW
(24kBtu/h)
7.25kW
(24kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
7.25kW
(24kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
Pattern 7
Pattern 8
HR1
A
A
A
1
2
• * : Serial connection of HR units : Capacity sum of indoor units
≤
192 kBtu/h
• * : Maximum indoor units per a branch are 8 indoor units
HR2
3
4
HR3
5
6
*
HR1
1
2
HR2
*
B
3
4
5
6
7
8
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
14.5kW
(48kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
3.63kW
(12kBtu/h)
7.25kW
(24kBtu/h)
7.25kW
(24kBtu/h)
• Pipe installation from outdoor units to HR units
: 3 pipes(Low pressure Gas pipe, High pressure Gas pipe, Liquid pipe)
• Pipe installation from HR units to indoor units
: 2 pipes(Gas pipe, Liquid pipe)
B
A
1
HR1
Outdoor
Unit
Indoor Unit
Y Branch pipe
Low pressure Gas pipe
High pressure Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Head Branch pipe
Indoor
Unit