54
ENGLISH
Compressor Input Current Limit
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn20” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~”op10” Push the ‘
●
’ button
Compressor Input Current Limit mode is set
Mode
Compressor Input Current Limit
oFF
100 %
op1
95 %
op2
90 %
op3
85 %
op4
80 %
op5
75 %
op6
70 %
op7
65 %
op8
60 %
op9
55 %
op10
50 %
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn16” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“Fn19” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on”,“oFF” Push the ‘
●
’ button
Central Control Connection at Indoor
Unit side Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn23” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“on” Push the ‘
●
’ button
Base pan Heater operation mode is set
Base pan Heater operation (Fn 23)
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn21” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn22” Push the ‘
●
’ button
Overall Defrost Operating in Low Mode is set
Setting
Detail of function
Defualt
OFF
Setting
ON/OFF Control
Overall Defrost Operating in Low temperature
(Heating) (Fn 22)
Mode setting method
Compressor Input Current Limit Mode (Fn 20)
System Input Current Control
Mode setting method
Central Control Connection at Indoor Unit side (Fn 19)
Mode setting method
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
CAUTION
!
• Function to prevent freezing of ODU base pan in a cold area.