51
ENGLISH
Time Settings
Step
Judgment Time(Hr)
Operation Time(Hr)
op1
8
9
op2
6.5
10.5
op3
5
12
op4
8
9
op5
6.5
10.5
op6
5
12
op7
8
9
op8
6.5
10
op9
5
12
op10
Continuous operation
op11
Continuous operation
op12
Continuous operation
Noise
Step
Noise(dBA)
op1 ~ op3, op10
-3
op4 ~ op6, op11
-6
op7 ~ op9, op12
-9
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn4” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on” ~ “oFF” Push the ‘
●
’ button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- off: Operate partial defrost
Mode setting
setting
Mode
oFF
Not setting
op1
Snow removal mode
op2
Rapid defrost mode
op3
Snow removal mode. + Rapid defrost mode.
Snow removal & rapid defrost (Fn 6)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn6” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1” ~ “op3” Push the ‘
●
’ button
Mode is set
Setting the ODU address (Fn 5)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn5” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“0” ~ “255” Push the ‘
●
’ button
ODU address is set
Overall HEX defrost mode (Fn 4)
Mode setting method
CAUTION
!
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
CAUTION
!
• Ask an authorized technician to setting a function.
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.