3
4
ENGLISH
Display
Title
Cause of Error
Outside unit
related error
1
0
4
*
1
1
3
*
1
1
5
*
1
1
6
*
1
4
5
*
1
5
1
*
1
8
0
*
1
8
1
*
1
8
2
*
Communication Error Between Master Outside Unit
and Other Outside Unit
Master Outside Unit Liquid pipe Temperature Sen-
sor Error
Master Outside Unit Subcooling Outlet Temperature
Sensor Error
Master Outside Unit Oil Level Sensor Error
Master outside unit Main Board - External Board
communication Error
Failure of operation mode conversion at Master Out-
side Unit
Plate type heat exchanger freeze prevention
Water temperature sensor error
Communication error between MICOMs of external
pcb
Failing to receive Slave Unit signal at main PCB of Master Outside
Unit
Liquid pipe temperature sensor of Master Outside Unit is open or
short
Master Outside Unit Subcooling Outlet Temperature Sensor open
or short
Oil Level Sensor of Master Outside Unit is open or short
Master outside unit Main Board - External Board communication
Error
Failure of operation mode conversion at Master Outside Unit
Plate type heat exchanger freeze prevention error
Water temperature sensor open/short
Communication error between main MICOM and sub MICOM of
external pcb
Checking procedure of limiting concentration
Check limiting concentration along following steps and take appropri-
ate measure depending on the situation.
Calculate amount of all the replenished refrigerant (kg) per each refrig-
erant system.
Calculate minimum room capacity
Calculate room capacity by regarding a portion as one room or the
smaller room.
- With partition and with opening
which serve as passage of air to
adjoining room
- Without partition
Limiting concentration is the limit of Freon gas concentration
where immediate measures can be taken without hurting human
body when refrigerant leaks in the air. The limiting concentration
shall be described in the unit of kg/m
3
(Freon gas weight per unit
air volume) for facilitating calculation.
Limiting concentration: 0.44kg/m
3
(R410A)
Amount of additional
replenished refrigerant
Total amount of replenished
refrigerant in refrigerant
facility (kg)
+
=
Note : In case one refrigerant facility is
divided into 2 or more refrigerant
systems and each system is
independent, amount of replenished
refrigerant of each system shall be
adopted.
Amount of replenished
refrigerant per one outside
unit system
Amount of replenished
refrigerant at factory shipment
Amount of additionally
replenished refrigerant
depending on piping
length or piping
diameter at customer
Outside unit
Indoor unit
Outside unit
Indoor unit
Opening
Partition
In the case of opening
without door , or 0.15
% or more openings
(to floor space) both
above and below door)
Outside unit
(No.1 system)
Flow of
refrigerant
Indoor unit
Room where refrigerant leaks
(Refrigerant of the whole No.1
system flows out.)
The installer and system specialist shall secure safety against leakage
according to local regulations or standards.
The following standards may be applicable if local regulations are not
available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself ,
the room to equip the air conditioner should be large to such an extent
that the refrigerant gas will not exceed the limiting concentration even
if the refrigerant gas leaks in the room.
Limiting concentration
CAUTION FOR REFRIGERANT LEAK
- With partition and without opening which serve as passage of air to
adjoining room
Calculate refrigerant concentration
Total amount of replenishedrefrigerant
in refrigerant facility (kg)
Capacity of smallest room
whereindoor unit is installed (m
3
)
- In case the result of calculation exceeds the limiting concentration, perform
the same calculations by shifting to the second smallest, and the third small-
est rooms until at last the result is below the limiting concentration.
= Refrigerant concentration(kg/m
3
)
(R410A)
Outside unit
Indoor unit
Smallest
room
Содержание Multi V ARWN Series