6

ENGLISH

SELECT THE BEST LOCATION

Select space for installing outside unit , which will meet the following
conditions:

• With strength which bears weight of unit

• With space for air passage and service work

Don't install the unit at the space where generation, inflow, stagna-
tion, and leak of combustible gas is expected.

• Avoid unit installation in a place where acidic solution and spray (sul-

fur) are often used.

• Location with no leakage of combustible gas

• Recommend the outside unit to be installed within 0~40°C.

• Location with installation or service work space (Refer to required

space)

• Do not use the outside unit under any special environment where oil,

steam and sulfuric gas exist. 

• Install in a separate machine room not exposed to external air

- Establish an anti-freeze plan for the water supply when the product
is stopped during the winter.
- Install the product so that the noise from the machine room is not
transferred outsides

• The floor of the machine room must be water proof.

• Drainage must be installed in the machine room to process the water

drainage. 

• Install a floor slope to make the drainage smooth. 

• Avoid installing the outside unit in the location with following condi-

tions.

• Location where corrosive gas such as acidic gas is generated. 

(It may cause the refrigerant leakage by corrosion of the pipe.)

• Location where electromagnetic waves happen. 

(It may cause the abnormal operation by control parts disorder.)

• Location to be able to leak the combustible gas

• Location with carbon fiber or combustible dust.

• Location with the combustible material like thinner or gasoline. 

(It may cause a fire by leaking the gas near the product.)

ALTERNATIVE REFRIGERANT R410A

The refrigerant R410A has the property of higher operating pressure in
comparison with R22.  
Therefore, all materials have the characteristics of higher resisting
pressure than R22 ones and this characteristic should be also consid-
ered during the installation. 
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone
depletion potential (ODP) of R410A is 0. 
These days the developed countries have approved it as the environ-
ment-friendly refrigerant and encouraged to use it widely to prevent
environment pollution.

CAUTION

• The wall thickness of the piping should comply with the relevant

local and national regulations for the designed pressure 3.8MPa

• Since R410A is a mixed refrigerant, the required additional

refrigerant must be charged in its liquid state. 
If the refrigerant is charged in its gaseous state, its composition
changes and the system will not work properly.

• Do not place the refrigerant container under the direct rays of

the sun to prevent it from exploding.

• For high-pressure refrigerant, any unapproved pipe must not be

used.

• Do not heat pipes more than necessary to prevent them from

softening.

• Be careful not to install wrongly to minimize economic loss

because it is expensive in comparison with R22.

!

CAUTION

• Do not install Multi V water outside. Always install indoor like

machine room.

• Inverter product may generate electric noise. Keep the body

from computer, stereo etc. at enough distance. Specially leave
space from indoor remote controller to shoes electric devices at
the above 3m in weak electric wave area. Insert the power
cable and other wire into separate conduit.

!

Unit

4 Unit

System Capacity (HP)

Model

Combination Unit

Independent Unit

Refrigerant Precharged Amount

kg

Maximum Connectable Number of Indoor Units

Net Weight  

kg  

lbs  

Dimensions(WxHxD)  

mm  
inch  

Refrigerant
Connecting Pipes  

Liquid   mm(inch)  
Gas  

mm(inch)  

Water Connect-
ing Pipes  

Inlet  

mm  

Outlet  

mm  

Drain Outlet

mm  

Temp. range of
Circulation water

Cooling
Heating

74

76

ARWN740LAS4

ARWN760LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN180LAS4

ARWN140LAS4

ARWN180LAS4

3.0 + 3.0 + 3.0 + 5.8

3.0 + 3.0 + 3.0 + 3.0

64

64

(140 x 3) + (127 x 1)

140 x 4

(309 x 3) + (280 x 1)

309 x 4

(755 × 997 × 500) x 4

(755 × 997 × 500) x 4

(29-23/32 x 39-1/4 x 19-11/16) x 4 (29-23/32 x 39-1/4 x 19-11/16) x 4

22.2(7/8)  

22.2(7/8)  

53.98(2-1/8)

53.98(2-1/8)

PT 40  + PT 40 + PT 40 + PT 40

PT 40  + PT 40 + PT 40 + PT 40

PT 40  + PT 40 + PT 40 + PT 40

PT 40  + PT 40 + PT 40 + PT 40

20

20

10°C ~ 45°C(50°F ~ 119°F)

10°C ~ 45°C(50°F ~ 120°F)

-5°C ~ 45°C(23°F ~ 119°F)

-5°C ~ 45°C(23°F ~ 120°F)

Unit

4 Unit

System Capacity (HP)

Model

Combination Unit

Independent Unit

Refrigerant Precharged Amount

kg

Maximum Connectable Number of Indoor Units

Net Weight  

kg  

lbs  

Dimensions(WxHxD)  

mm  
inch  

Refrigerant
Connecting Pipes  

Liquid   mm(inch)  
Gas  

mm(inch)  

Water Connect-
ing Pipes  

Inlet  

mm  

Outlet  

mm  

Drain Outlet

mm  

Temp. range of
Circulation water

Cooling
Heating

78

80

ARWN780LAS4

ARWN800LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN180LAS4

ARWN200LAS4

3.0 + 3.0 + 3.0 + 3.0

3.0 + 3.0 + 3.0 + 3.0

64

64

140 x 4

140 x 4

309 x 4

309 x 4

(755 × 997 × 500) x 4

(755 × 997 × 500) x 4

(29-23/32 x 39-1/4 x 19-11/16) x 4 (29-23/32 x 39-1/4 x 19-11/16) x 4

22.2(7/8)  

22.2(7/8)  

53.98(2-1/8)

53.98(2-1/8)

PT 40  + PT 40 + PT 40 + PT 40

PT 40  + PT 40 + PT 40 + PT 40

PT 40  + PT 40 + PT 40 + PT 40

PT 40  + PT 40 + PT 40 + PT 40

20

20

10°C ~ 45°C(50°F ~ 121°F)

10°C ~ 45°C(50°F ~ 122°F)

-5°C ~ 45°C(23°F ~ 121°F)

-5°C ~ 45°C(23°F ~ 122°F)

Unit

4 Unit

System Capacity (HP)

Model

Combination Unit

Independent Unit

Refrigerant Precharged Amount

kg

Maximum Connectable Number of Indoor Units

Net Weight  

kg  

lbs  

Dimensions(WxHxD)  

mm  
inch  

Refrigerant
Connecting Pipes  

Liquid   mm(inch)  
Gas  

mm(inch)  

Water Connect-
ing Pipes  

Inlet  

mm  

Outlet  

mm  

Drain Outlet

mm  

Temp. range of
Circulation water

Cooling
Heating

68

70

72

ARWN680LAS4

ARWN700LAS4

ARWN720LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN200LAS4

ARWN140LAS4

ARWN160LAS4

ARWN180LAS4

ARWN140LAS4

ARWN140LAS4

ARWN140LAS4

3.0 + 3.0 + 5.8 + 5.8

3.0 + 3.0 + 3.0 + 5.8

3.0 + 3.0 + 3.0 + 5.8

64

64

64

(140 x 2) + (127 x 2)

(140 x 3) + (127 x 1)

(140 x 3) + (127 x 1)

(309 x 2) + (280 x 2)

(309 x 3) + (280 x 1)

(309 x 3) + (280 x 1)

(755 × 997 × 500) x 4 (755 × 997 × 500) x 4 (755 × 997 × 500) x 4

(29-23/32 x 39-1/4 x 19-11/16) x 4 (29-23/32 x 39-1/4 x 19-11/16) x 4 (29-23/32 x 39-1/4 x 19-11/16) x 4

22.2(7/8)  

22.2(7/8)  

22.2(7/8)  

53.98(2-1/8)

53.98(2-1/8)

53.98(2-1/8)

PT 40  + PT 40 + PT 40 + PT40 PT 40  + PT 40 + PT 40 + PT40 PT 40  + PT 40 + PT 40 + PT40
PT 40  + PT 40 + PT 40 + PT40 PT 40  + PT 40 + PT 40 + PT40 PT 40  + PT 40 + PT 40 + PT40

20

20

20

10°C ~ 45°C(50°F ~ 116°F) 10°C ~ 45°C(50°F ~ 117°F) 10°C ~ 45°C(50°F ~ 118°F)

-5°C ~ 45°C(23°F ~ 116°F) -5°C ~ 45°C(23°F ~ 117°F) -5°C ~ 45°C(23°F ~ 118°F)

Содержание Multi V ARWN Series

Страница 1: ...etely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly your set and retain it for future reference MODELS ARWN Series ENGLISH ...

Страница 2: ...ified on the unit If a different refrigerant or air is mixed with the original refrigerant the refrigerant cycle may malfunction and the unit may be damaged Do not reconstruct to change the settings of the protection devices If the pressure switch thermal switch or other protection device is shorted and operated forcibly or parts other than those specified by LGE are used fire or explosion may res...

Страница 3: ...transportation Only one person should not carry the product if it weighs more than 20 kg Some products use PP bands for packaging Do not use any PP bands for a means of transportation It is dangerous Do not touch the heat exchanger fins Doing so may cut your fingers When transporting the outside unit suspending it at the specified positions on the unit base Also support the outside unit at four po...

Страница 4: ... unit s 130 OUTSIDE UNITS INFORMATION Power Supply 3Φ 380 415V 50Hz Model Name ARWN LAS4 Unit 1 Unit System Capacity HP 8 10 12 Model Combination Unit ARWN080LAS4 ARWN100LAS4 ARWN120LAS4 Independent Unit ARWN080LAS4 ARWN100LAS4 ARWN120LAS4 RefrigerantPrechargedAmount kg 5 5 3 4 3 5 MaximumConnectableNumberofIndoorUnits 13 16 20 Net Weight kg 127 x 1 127 x 1 127 x 1 lbs 280 x 1 280 x 1 280 x 1 Dime...

Страница 5: ...AS4 ARWN120LAS4 3 0 3 5 3 4 3 0 3 5 3 5 3 0 5 8 3 5 64 64 64 140 x 1 127 x 2 140 x 1 127 x 2 140 x 1 127 x 2 309 x 1 280 x 2 309 x 1 280 x 2 309 x 1 280 x 2 755 997 500 x 3 755 997 500 x 3 755 997 500 x 3 29 23 32 x 39 1 4 x 19 11 16 x 3 29 23 32 x 39 1 4 x 19 11 16 x 3 29 23 32 x 39 1 4 x 19 11 16 x 3 19 05 3 4 19 05 3 4 19 05 3 4 41 3 1 5 8 41 3 1 5 8 41 3 1 5 8 PT 40 PT 40 PT 40 PT 40 PT 40 PT ...

Страница 6: ...y generate electric noise Keep the body from computer stereo etc at enough distance Specially leave space from indoor remote controller to shoes electric devices at the above 3m in weak electric wave area Insert the power cable and other wire into separate conduit Unit 4 Unit System Capacity HP Model Combination Unit Independent Unit RefrigerantPrechargedAmount kg MaximumConnectableNumberofIndoorU...

Страница 7: ...th the pump before dropping the tempera ture Keep the normal temperature by boiler When the cooling tower is not operated for a long time drain the water in the cooling tower Use an anti freeze For using an anti freeze change the DIP switch on main PCB in outside unit Refer to the additive amount about freezing temperature as in the table given below In addition to anti freeze it may cause the cha...

Страница 8: ...water temperature is 40 C or above or when un coated iron is exposed to the water it can result in corrosion Therefore adding anti corrosion agent or removing the air can be very effective In case of using the closed type cooling tower the cooling water and supplementing water must satisfy the water quality criteria of closed type system in the table Supplementing water and supplied water must be ...

Страница 9: ...the cable 1 5m longer than the pipe length Pipe Reamer Point down Copper tube 90 Slanted Uneven Rough Preparation of Piping Burrs removal Completely remove all burrs from the cut cross section of pipe tube Put the end of the copper tube pipe to downward direction as you re move burrs in order to avoid to let burrs drop in the tubing Flaring work Carry out flaring work using flaring tool as shown b...

Страница 10: ...rant pipe EPDM heat insulation material thickness Classification Air conditioned location Non air conditioned location Note1 General location Note2 Special location Note3 General location Note4 Negative condition Liquid pipe Ø6 35 Above t9 Above t9 Above t9 Above t9 Ø9 52 Above Ø12 7 Above t13 Above t13 Above t13 Above t13 Gas pipe Ø9 52 Above t13 Above t19 Above t19 Above t25 Ø12 7 Ø15 88 Ø19 05 ...

Страница 11: ...n dioxide and a Chevron gas Please use the following nitrogen pressure 0 02MPa Oxygen Promotes oxidative degradation of refrigerant oil Because it is flammable it is strictly prohibited to use Carbon dioxide Degrade the drying characteristics of gas Chevron Gas Toxic gas occurs when exposed to direct flame 2 Always use a pressure reducing valve 3 Please do not use commercially available antioxidan...

Страница 12: ...rant piping differs use a pipe cutter to cut the connecting section and then use an adapter for connecting different diameters to connect the piping 7 Always observe the restrictions on the refrigerant piping such as rated length difference in height and piping diameter Failure to do so can result in equipment failure or a decline in heat ing cooling performance 9 The Multi V will stop due to an a...

Страница 13: ...ROTECTION UNIT Upper graph is a theoretical value for selection and it may be different according to specification of strainer To protect the water cooling type product you must install a strainer with 50 mesh or more on the heat water supply pipe If not installed it can result in damage of heat exchanger by the follow ing situation 1 Heat water supply within the plate type heat exchanger is com p...

Страница 14: ... heat exchanger When the product operates while the flow switch touches the contact point at the flow rate range out of the permitted range it can cause product performance deterioration or serious prod uct problem Must use the normal closed type flow switch Circuit of outside unit is normal closed type Y branch method Combination of Y branch header method Header method Ⓐ Outside Unit Ⓑ 1st branch...

Страница 15: ...ave 1 Slave 2 Slave 3 C C C C C C Pipe Connection Method between outside unit indoor unit h See Table 2 A Refrigerant pipe diameter from outside unit to first branch E Refrigerant pipe diameter for outside unit capacity Slave 1 Slave 2 Slave 3 F Refrigerant pipe diameter for outside unit capacity Slave 2 Slave 3 G Refrigerant pipe diameter for outside unit capacity Slave 3 L1 L2 L3 L4 H1 E G F Sla...

Страница 16: ...ipe connection between outside unit s General Case The maximum pipe length after the first branching between the outside unit is 10m or les Pipes between outside unit s are 2m or less 2m or less Pipes between outside unit s are 2m or longer Oil Trap Oil Trap Oil Trap 2m or less 2m or less 2m or less 0 2m or more 2m or longer 2m or longer 2m or longer Oil trap application method between outside unit...

Страница 17: ...oward indoor unit Oil Trap Example 3 The amount of Refrigerant The calculation of the additional charge should take into account the length of pipe and CF correction Factor value of indoor unit Total liquid pipe Ø25 4 mm Additional charge kg Total liquid pipe Ø22 2 mm Total liquid pipe Ø19 05 mm Total liquid pipe Ø15 88 mm Total liquid pipe Ø12 7 mm Total liquid pipe Ø9 52 mm Total liquid pipe Ø6 ...

Страница 18: ...stribution Method WARNING Regulation for refrigerant leakage the amount of refrigerant leakage should satisfy the following equation for human safety If the above equation can not be satisfied then follow the follow ing steps Selection of air conditioning system select one of the next Installation of effective opening part Reconfirmation of Outside Unit capacity and piping length Reduction of the ...

Страница 19: ...n taped as described above Insulate the header using the insulation material attached to the branch pipe kit as shown in the figure Insulator Insulator of field pipe Tape Tape Cap pipe Insulator for cap pipe Y branch pipe Models Gas pipe Liquid pipe ARBLN 01621 I D19 05 O D15 88 I D12 7 I D15 88 I D12 7 I D15 88 I D15 88 I D12 7 292 281 74 70 I D12 7 O D9 52 I D6 35 I D9 52 I D 9 52 I D 6 35 I D9 52...

Страница 20: ...ture at the time of pressurization 3 8 MPa is 27 C 24 hour later 3 73 MPa 20 C In this case the pressure drop of 0 07 is because of tem perature drop And hence there is no leakage in pipe oc curred CAUTION To prevent the nitrogen from entering the refrigeration system in the liquid state the top of the cylinder must be at higher position than the bottom when you pressurize the system Usually the c...

Страница 21: ...r unit PCB Vacuum Mode DIP SWITCH 7 Segment SW01C confirm SW02C backward forward SW04C X cancel SW01D reset SW03C ȭ ȯ Ɨ Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with enough thickness heat resistant poly ethylene so that no gap is observed in the joint between indoor unit and insulating material and insulating materials themselves When in ...

Страница 22: ...re shield cable for communication cable O mark in the figure below If communication cable of different systems are wired with the same multiplecore cable the resultant poor transmitting and re ceiving will cause erroneous operations mark in the figure below Only the communication cable specified should be connected to the terminal block for Outside Unit communication CAUTION Be sure to correct the...

Страница 23: ...in the signal wiring caused by electrostatic and electro magnetic coupling The tables below indicates our recommendation as to appropriate spacing of communication and power cables where these are to be run side by side Current capacity of power cable Spacing 100V or more 10A 300mm 50A 500mm 100A 1000mm Exceed 100A 1500mm Main PCB Noise Filter External PCB Take care of the phase sequence of 3 phas...

Страница 24: ... firmly it may cause heating or fire Make sure to use the appropriate type of overcurrent protection switch Note that generated overcurrent may include some amount of direct current Field Wiring Single outside unit R S T N Switch Fuse L N Communication cable 2 Wires Cable Power cable 4 Wires Cable Communication cable 3 Wires Cable Power cable 2 Wires Cable Power cable 2 Wires Cable Power cable 2 W...

Страница 25: ...round wires are required for preventing electrical shock accident during current leakage Communication disorder by noise effect and motor current leakage without connection to pipe Don t install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply Install the main switch that can interrupt all the power sources in an integrated manner because...

Страница 26: ... on 7 segment LED after completing setting Indoor address number is displayed on wired remote control or indoor unit display window It is not an error message will disappeared when on off button is pressed on remote control ex Display of 01 02 15 means connection of 15 indoor units and Automatic addressing is completed normally Automatic addressing start Waiting 3 minutes Power On Press RED Button...

Страница 27: ...s set Function setting Switch control Function Switch Phase Switch Bottom OFF op1 mode op2 mode Right Left Not operate Cooling Cooling Right Right Not operate Heating Heating Left Not operate Fan mode Off CAUTION Request the function settings to the installation specialist during the outside unit installation When the function is not used set it to OFF If use a function first install a Cool Heat s...

Страница 28: ...220V output It is the function to select 220V output when you want solenoid valve control How to set the mode Geothermal mode setting If you want to use the product with heat source water of the low tem perature such as ground heat it is the function that enables the use of ground heat mode How to set the mode Mode setting ON Set to operate in geothermal mode OFF Set to operate in general mode Tur...

Страница 29: ...power consumption 2 5 C 4 C op4 Decrease power consumption Decrease power consumption 4 5 C 6 C CAUTION Request the function settings to the installation specialist during the outside unit installation When the function is not used set it to OFF If the temperature of the outside unit installation place is 0 C or less we recommend the connection and usage of Sump Heater Use Sump Heater It is the fu...

Страница 30: ... outside units Execute the test of water supply system without operating the product Check whether outside unit inlet outlet flow rate complies to the product specification Standard Water volume is 96LPM based on 10HP and 196LPM based on 20HP Check the water supply temperature whether is OK After checking the normal condition of the water supply execute the test run of the product To prevent the fre...

Страница 31: ...checking can be required depending on the oper ating condition water quality condition When cleaning the heat exchanger make sure to take parts out or lock the value so that chemical detergent does not penetrate into the pressure gauge etc When cleaning the heat exchanger check the connecting part of the water pipes prior to cleaning so that the chemical detergent does not leak After sufficiently ...

Страница 32: ...er compressor operation failure error Master outside unit inverter DC link over voltage error Master outside unit inverter compressor overcurrent Master outside unit inverter compressordischarge temperature over rise Master outside unit high pressure over rise Air temperature sensor of indoor unit is open or short Inlet pipe temperature sensor of indoor unit is open or short Failing to receive wir...

Страница 33: ...under low Compression limit for 3 minutes Master Outside unit inverter compressor current detection CT sen sor disconnection or short circuit Master outside unit inverter compressor current detection CT sen sor disconnection or short circuit Master outside unit inverter compressor discharge temperature sensor disconnection or short circuit Master Outside Unit Low Pressure Sensor open or short Mast...

Страница 34: ...scribed in the unit of kg m3 Freon gas weight per unit air volume for facilitating calculation Limiting concentration 0 44kg m3 R410A Amount of additional replenished refrigerant Total amount of replenished refrigerant in refrigerant facility kg Note In case one refrigerant facility is divided into 2 or more refrigerant systems and each system is independent amount of replenished refrigerant of ea...

Страница 35: ...ning effective to ventilation Indoor unit Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air WATER SOLENOID VALVE CON TROL COOLING TOWER APPLIED METHOD Central Control Use DDC Port Individual Control Use 220V Output Port Water In BMS Building Management System Water Out Solenoid Valve CN_18 220 V Out CN_22 to DDC PI 485 DDC ...

Страница 36: ...ls the requirement above If necessary the user can ask the public power supply com pany for the system impedance at the interface point The below Installation guide is limited applicable only for model Model ARWN200LAS4 ARWN180LAS4 ARWN160LAS4 Installation Guide for Harmonics EN 61000 3 2 EN 61000 3 12 Installation Guide for Flicker EN 61000 3 3 EN 61000 3 11 This equipment complies with IEC EN 61...

Страница 37: ......

Отзывы: