background image

4

ENGLISH

INSTALLATION PROCESS

The foundation must be level even

Outdoor unit foundation work

Avoid short circuits and ensure 
sufficient space is allowed for service

Installation of outdoor unit

Refer to automatic addressing flowchart

Automatic addressing of indoor unit 

In the final check for 24hours at 3.8 MPa(38.7 kgf/cm

2

) there 

must be no drop in pressure.

Airtight test

Multiple core cable must not be used.
(suitable cable should be selected)

Electrical work

(connection circuits and drive circuits)

Make sure no gaps are left where 
the insulating materials are joined

Heat insulation work

Make sure airflow is sufficient

Duct work

Adjust to downward gradient

Drain pipe work

Special attention to dryness, 
cleanness and tightness

Refrigerant piping work

Check model name to 
make sure the fitting 
is made correctly

Installation of indoor unit

Take account of gradient 
of drain piping

Sleeve and insert work

Make connection clearly between outdoor, indoor, 
remote controller and option.

Preparation of contract drawings

Indicate clearly who will be responsible for switch setting.

Determination of division work

The vacuum pump used must have a capacity of reaching at least 
5 torr, more than 1 hour

Vacuum drying

Recharge correctly as calculated in this manual. and record the 
amount of added refrigerant

Additional charge of refrigerant

Make sure there are no gaps left between the facing materials 
used on the ceiling 

Fit facing panels

Run each indoor unit in turn to make sure the pipe work 
has been fitted correctly

Test run adjustment

Explain the use of the system as clearly as possible to your customer and
make sure all relevant documentation is in order

Transfer to customer with explanation

Preheat the crank case with the electrical  heater for more than 6 hours.

CAUTION

• The above list indicates the order in which the individual work

operations are normally carried out but this order may be varied
where local conditions warrants such change.

• The thickness of the piping should comply with the relevant

local and national regulations for the designed pressure 3.8MPa.

• Since R410A is a mixed refrigerant, the required additional

refrigerant must be charged in its liquid state.(If the refrigerant
is charged in its gaseous state, its composition changes and the
system will not work properly.)

!

CAUTION

Notes : * We can guarantee the operation only within 130%

Combination. If you want to connect more than 130%
combination, please contact us and discuss the
requirement like below.

• If the operation of indoor unit is more than 130%, the airflow is

operated as low in the all indoor units.

• The number of (    ) means the number of Max. connectable

indoor units, when the connected capacity of indoor units is in
the table above.

Combination Ratio(50~200%)

Outdoor Number

Connection Ratio

Single outdoor units

200%

Double outdoor units

160%

Triple outdoor units

130%

!

OUTDOOR UNITS INFORMATION

Power Supply : 460 V3~ 60Hz
Model Name : ARUN***DTS4

Number of outdoor units

1 Outdoor Unit

Capacity(HP)

8

10

12

Model

Combination Unit

ARUN080DTS4

ARUN100DTS4

ARUN120DTS4

Independent

Unit

ARUN080DTS4

ARUN100DTS4

ARUN120DTS4

Dimensions

mm

(920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1

Net Weight

kg

195 × 1

201 × 1

201 × 1

Refrigerant
Precharged amount

kg

6.5

6.5

6.5

Pipe
Connections

Liquid mm (inch)

9.52(3/8)

9.52(3/8)

12.7(1/2)

Gas

mm (inch)

19.05(3/4)

22.2(7/8)

28.58(1 1/8)

Number of maximum connectable indoor units

13(20)

16(25)

20(30)

Number of outdoor units

2 Outdoor Unit

Capacity(HP)

22

24

26

Model

Combination Unit

ARUN220DTS4

ARUN240DTS4

ARUN260DTS4

Independent

Unit

ARUN120DTS4

ARUN120DTS4

ARUN140DTS4

ARUN100DTS4

ARUN120DTS4

ARUN120DTS4

Dimensions

mm

(920×1,680×760)×2 (920×1,680×760)×2

(1,240×1,680×760)×1

+ (920×1,680×760)×1

Net Weight

kg

201 × 2

201 × 2

235 × 1 + 201 × 1

Refrigerant
Precharged amount

kg

6.5 × 2

6.5 × 2

8.5 + 6.5

Pipe
Connections

Liquid mm (inch)

15.88(5/8)

15.88(5/8)

19.05(3/4)

Gas

mm (inch)

28.58(1 1/8)

34.9(1 3/8)

34.9(1 3/8)

Number of maximum connectable indoor units

35(44)

39(48)

42(52)

Number of outdoor units

2 Outdoor Unit

Capacity(HP)

28

30

32

Model

Combination Unit

ARUN280DTS4

ARUN300DTS4

ARUN320DTS4

Independent

Unit

ARUN160DTS4

ARUN180DTS4

ARUN200DTS4

ARUN120DTS4

ARUN120DTS4

ARUN120DTS4

Dimensions

mm

(1,240×1,680×760)×1

+ (920×1,680×760)×1

(1,240×1,680×760)×1

+ (920×1,680×760)×1

(1,240×1,680×760)×1

+ (920×1,680×760)×1

Net Weight

kg

235 × 1 + 201 × 1

270 × 1 + 201 × 1

280 × 1 + 201 × 1

Refrigerant
Precharged amount

kg

8.5 + 6.5

8.5 + 6.5

10 + 6.5

Pipe
Connections

Liquid mm (inch)

19.05(3/4)

19.05(3/4)

19.05(3/4)

Gas

mm (inch)

34.9(1 3/8)

34.9(1 3/8)

34.9(1 3/8)

Number of maximum connectable indoor units

45(56)

49(60)

52(64)

Number of outdoor units

1 Outdoor Unit

Capacity(HP)

14

16

Model

Combination Unit

ARUN140DTS4

ARUN160DTS4

Independent

Unit

ARUN140DTS4

ARUN160DTS4

Dimensions

mm

(1,240×1,680×760)×1

(1,240×1,680×760)×1

Net Weight

kg

235 × 1

235 × 1

Refrigerant
Precharged amount

kg

8.5

8.5

Pipe
Connections

Liquid mm (inch)

12.7(1/2)

12.7(1/2)

Gas

mm (inch)

28.58(1 1/8)

28.58(1 1/8)

Number of maximum connectable indoor units

23(35)

26(40)

Number of outdoor units

1 Outdoor Unit

Capacity(HP)

18

20

Model

Combination Unit

ARUN180DTS4

ARUN200DTS4

Independent

Unit

ARUN180DTS4

ARUN200DTS4

Dimensions

mm

(1,240×1,680×760)×1

(1,240×1,680×760)×1

Net Weight

kg

270 × 1

280 × 1

Refrigerant
Precharged amount

kg

8.5

10

Pipe
Connections

Liquid mm (inch)

15.88(5/8)

15.88(5/8)

Gas

mm (inch)

28.58(1 1/8)

28.58(1 1/8)

Number of maximum connectable indoor units

29(45)

32(50)

Содержание multi V ARUV100DTS4

Страница 1: ... the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly your set and retain it for future reference P NO MFL67221422 460 V3 60Hz ENGLISH ESPAÑOL PORTUGUESE ...

Страница 2: ...ified on the unit If a different refrigerant or air is mixed with the original refrigerant the refrigerant cycle may malfunction and the unit may be damaged Do not reconstruct to change the settings of the protection devices If the pressure switch thermal switch or other protection device is shorted and operated forcibly or parts other than those specified by LGE are used fire or explosion may res...

Страница 3: ...n the unit base Also support the outdoor unit at four points so that it cannot slip sideways Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging bags so that children may not play with them If children play with a plastic bag which was not torn apart they face the risk ...

Страница 4: ...all indoor units The number of means the number of Max connectable indoor units when the connected capacity of indoor units is in the table above Combination Ratio 50 200 Outdoor Number Connection Ratio Single outdoor units 200 Double outdoor units 160 Triple outdoor units 130 OUTDOOR UNITS INFORMATION Power Supply 460 V3 60Hz Model Name ARUN DTS4 Number of outdoor units 1 Outdoor Unit Capacity HP...

Страница 5: ... 4 Gas mm inch 41 3 1 5 8 41 3 1 5 8 Numberofmaximumconnectableindoorunits 64 64 Number of outdoor units 4 Outdoor Unit Capacity HP 62 64 66 Model Combination Unit ARUN620DTS4 ARUN640DTS4 ARUN660DTS4 Independent Unit ARUN180DTS4 ARUN180DTS4 ARUN180DTS4 ARUN160DTS4 ARUN180DTS4 ARUN180DTS4 ARUN140DTS4 ARUN140DTS4 ARUN160DTS4 ARUN140DTS4 ARUN140DTS4 ARUN140DTS4 Dimensions mm 1 240 1 680 760 4 1 240 1...

Страница 6: ...el Combination Unit ARUV420DTS4 ARUV440DTS4 ARUV460DTS4 Independent Unit ARUV180DTS4 ARUV200DTS4 ARUV200DTS4 ARUV140DTS4 ARUV140DTS4 ARUV160DTS4 ARUV100DTS4 ARUV100DTS4 ARUV100DTS4 Dimensions mm 1 240 1 680 760 920 1 680 760 2 1 240 1 680 760 920 1 680 760 2 1 240 1 680 760 2 920 1 680 760 1 Net Weight kg 270 1 201 1 195 x 1 270 1 201 1 195 x 1 270 1 235 1 195 1 Refrigerant Precharged amount kg 8 ...

Страница 7: ...4 ARUV200DTS4 Dimensions mm 1 240 1 680 760 3 1 240 1 680 760 3 Net Weight kg 270 3 270 3 Refrigerant Precharged amount kg 8 5 x 3 8 5 x 3 Pipe Connections Liquid mm inch 19 05 3 4 19 05 3 4 Gas mm inch 41 3 1 5 8 41 3 1 5 8 Numberofmaximumconnectableindoorunits 64 64 ALTERNATIVE REFRIGERANT R410A The refrigerant R410A has the property of higher operating pressure in comparison with R22 Therefore ...

Страница 8: ... C D A E B A B E A E B F C D A E B F D E C A B F C D A E B F C D 240 or more 50 or more 45 or more The height of the wall on the front side must be 1500mm or less The height of the wall on the inlet side must be 500mm or less There is no limit to the wall on the side If the height of the walls on the front and the side are higher than the limit there must be additional space on the front and the s...

Страница 9: ...gust Use the H beam support as a base support Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part depending on installation sta tus Thus use anti vibration materials cushion pad fully The base pad shall be more than 200mm At least 200mm Unit mm 200 75 75 200 100 Ⓐ The corner part must be fixed firmly Otherwise the support for the instal...

Страница 10: ...enches in combination When connecting the piping always use a spanner and torque wrench in combination to tighten the flare nut When connecting a flare nut coat the flare inner and outer faces with oil for R410A PVE and hand tighten the nut 3 to 4 turns as the initial tightening Union Insulation of shutoff valve 1 Use the heat insulation material for the refrigerant piping which has an excellent h...

Страница 11: ...l operation of the compressor In order to avoid this problem Welding should be done after replacing air by nitrogen gas When welding plumbing pipe the work is required Regulator Nitrogen gas Pressure 0 02MPa less Auxiliary valve Taping Should not contain air Welding Point Note should not block the outlet side When the internal pressure in pipe is abo ve the atmospheric pressure pinhole is o ccurre...

Страница 12: ...emoving burr after Knock Out work Perform sleeve work to prevent damage to the wire when con necting wires using Knock Out PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT Remove leakage prevention cap Remove the leakage prevention cap attached to the outdoor unit service valve before pipe work Proceed the leakage prevention cap removal as follows Verify whether the liquid gas pipes are locked Ext...

Страница 13: ...ndoor Unit Ⓔ Connection branch pipe be tween Outdoor units ARCNN31 Ⓕ Connection branch pipe be tween Outdoor units ARCNN21 10m or less L150m 200 m Conditional application ODU Capacity Master Slave1 Slave 2 l 40m 90 m Conditional application H 110m Slave2 Slave1 Master h 40m h1 4 Outdoor Units Example 5 Indoor Units connected Ⓐ Outdoor Unit Ⓑ 1st branch Y branch Ⓒ Indoor Units Ⓓ Downward Indoor Uni...

Страница 14: ...7 1 2 Ø 25 4 1 Ø 12 7 1 2 not increased 12 14 Ø 12 7 1 2 Ø 28 58 1 1 8 Ø 15 88 5 8 not increased Ø 15 88 5 8 not increased 16 Ø 12 7 1 2 Ø 28 58 1 1 8 Ø 15 88 5 8 Ø 31 8 1 1 4 Ø 15 88 5 8 not increased 18 22 Ø 15 88 5 8 Ø 28 58 1 1 8 Ø 19 05 3 4 Ø 31 8 1 1 4 Ø 19 05 3 4 not increased 24 Ø 15 88 5 8 Ø 34 9 1 3 8 Ø 19 05 3 4 not increased Ø 19 05 3 4 not increased 26 34 Ø 19 05 3 4 Ø 34 9 1 3 8 Ø 22...

Страница 15: ...pe Therefore pipe diameter B connected after first branch would be Ø34 9 gas pipe Ø15 88 liquid pipe which is same with main pipe diameter Example Do not choose the main pipe diameter by downward indoor unit total capacity but its outdoor unit model name Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit model name EX Where connecting the indo...

Страница 16: ...0 26 2 0 24 4 2 12 kg Toward indoor unit Toward indoor unit Pipe inclination 2 or more Toward indoor unit Toward indoor unit Toward indoor unit Toward indoor unit Example 1 Example 2 Example 3 Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2m Otherwise the unit may not oper ate properly Example 1 Toward indoor unit Toward indoor unit 2m 2m 2m 0 2m ...

Страница 17: ...from the floor Wall mounted type Cassette type Adoption of ventilation system choose ordinary ventilation system or building ventilation sys tem Limitation in piping work Prepare for earthquake and thermal stress Gas pipe Liquid pipe Ⓐ Manifold Gauge Ⓑ Low pressure side Handle Ⓒ High pressure side Handle WARNING Pipe to be vacuumed gas pipe liquid pipe If the refrigerant amount is not exact it may...

Страница 18: ... that the branch pipes are attached horizontally or vertically see the diagram below There is no limitation on the joint mounting configuration If the diameter of the refrigerant piping selected by the procedures described is different from the size of the joint the connecting sec tion should be cut with a pipe cutter Branch pipe should be insulated with the insulator in each kit Ⓐ To Outdoor Unit...

Страница 19: ... 44 48 I D38 1 I D41 3 I D 44 48 I D38 1 I D41 3 I D 53 98 420 490 134 1 2 3 3 2 3 3 3 3 2 O D 19 05 I D 12 7 I D 15 88 O D12 7 I D6 35 I D9 52 X2 110 110 I D25 4 I D22 2 I D 19 05 I D 19 05 I D 22 2 I D 25 4 I D 25 4 I D 22 2 346 379 96 2 3 3 2 3 unit mm unit mm Leak test Leak test should be made by pressurizing nitrogen gas to 3 8 MPa 38 7kgf cm2 If the pressure does not drop for 24 hours the sy...

Страница 20: ...d hence there is no leakage in pipe oc curred CAUTION To prevent the nitrogen from entering the refrigeration system in the liquid state the top of the cylinder must be at higher position than the bottom when you pressurize the system Usually the cylinder is used in a vertical standing position WARNING Use a vacuum pump or Inert nitrogen gas when doing leakage test or air purge Do not compress air...

Страница 21: ...n part with steel plate so that the insulation material will not be caved in For this part use incom bustible materials for both insulation and covering Vinyl covering should not be used Inner wall concealed Outer wall Outer wall exposed Floor fireproofing Penetrating portion on fire limit and boundary wall Roof pipe shaft Caution Follow ordinance of your governmental organization for technical st...

Страница 22: ...citor Make sure that the power unbalance ratio is not greater than 2 If it is greater the units lifespan will be reduced Control box and connecting position of wiring Remove all of the screws at front panel and remove the panel by pulling it forward Connect communication cable between main and sub outdoor unit through the terminal block Connect communication cables between outdoor unit and indoor ...

Страница 23: ...ys a risk of electric shocks the earthing of the apparatus must be carried out by a qualified person Wiring of main power supply and equipment capacity Use a separate power supply for the Outdoor Unit and Indoor Unit Bear in mind ambient conditions ambient temperature direct sunlight rain water etc when proceeding with the wiring and connections The cable size is the minimum value for metal condui...

Страница 24: ...oor unit to outdoor unit Abnormal operation can be caused by communication de fect when connection of com munication cable is installed like below figure STAR type Master Outdoor Unit SODU B SODU A IDU B IDU A CEN B CEN A DRY1 DRY2 GND 12V 3 4 3 4 3 4 Between Indoor and Master Outdoor unit The GND terminal at the main PCB is a terminal for day contact it is not the point to make ground connection ...

Страница 25: ... can check the setting values of the Master outdoor unit from the 7 segment LED The dip switch setting should be changed when the power is OFF Checking the initial display The number is sequentially appeared at the 7 segment in 5 seconds after applying the power This number represents the setting condition Initial display order Example ARUN620DTS4 Master Unit Slave Unit Order No Mean 8 20 Master m...

Страница 26: ...80 8F No 9 group 90 9F No A group A0 AF No B group B0 BF No C group C0 CF No D group D0 DF No E group E0 EF No F group F0 FF Cool Heat selector Mode setting method Master unit PCB DIP switch on No 5 Select the mode using Button Func Push the button Select the Function using Button Fn1 Push the button Select the Option using Button oFF op1 op2 Push the button Cool Heat Selection mode is set Functio...

Страница 27: ...ter unit PCB DIP switch on No 5 Select the mode using Button Func Push the button Select the Function using Button Fn3 Push the button Select the Option using Button op1 op12 Push the button Start the Night low noise function Save the selected option value in EEPROM Step Judgment Time Hr Operation Time Hr op1 8 9 op2 6 5 10 5 op3 5 12 op4 8 9 op5 6 5 10 5 op6 5 12 op7 8 9 op8 6 5 10 op9 5 12 op10 ...

Страница 28: ...ode is set CAUTION Ask an authorized technician to setting a function If do not use a function set an off mode Mode setting Step Mode oFF Not setting op1 Snow removal mode op2 Rapid defrost mode op3 Snow removal mode Rapid defrost mode IDU capacity adjusting If the operation of indoor unit is more than 130 the air flow is oper ated as low in the all indoor units Mode setting method Master unit PCB...

Страница 29: ... sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short 0 9 Indoor EEPROM Error In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF 1 0 Poor fan motor operation Disconnecting the fan motor connector Failure of indoor fan motor lock Outdoor unit related error 2 1 Master Outdoor Unit Inverter Compressor IPM Fault Master Outdoor Unit Inverter Co...

Страница 30: ...sive connection of indoor units compared to capacity of Out door Unit 5 2 Communication error inverter PCB Main PCB Failing to receive inverter signal at main PCB of Master Outdoor Unit 5 3 Communication error indoor unit Main PCB of Outdoor Unit Failing to receive indoor unit signal at main PCB of Outdoor Unit 5 7 Communication error Main PCB inverter PCB Failing to receive signal main PCB at inv...

Страница 31: ...xtent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room Limiting concentration CAUTION FOR REFRIGERANT LEAK Outdoor unit related error 1 0 4 Communication Error Between Master Outdoor Unit and Other Outdoor Unit Failing to receive Slave Unit signal at main PCB of Master Out door Unit 1 0 5 Master Outdoor Unit Fan PCB Communication Err...

Страница 32: ...nt can stay since refrigerant is heavier than air CAUTION Air conditioners should not be installed in areas where corrosive gases such as acid or alkaline gas are produced Do not install the product where it could be exposed to sea wind salty wind directly It can result corrosion on the product Corrosion particularly on the condenser and evaporator fins could cause product malfunction or inefficie...

Страница 33: ......

Отзывы: