Heat Pump
60Hz/R410A
_
7
1. Multiple piping type MULTI F
Part 2 Product data_Outdoor units
Heating
7 - - 7 2.3 - - 7,560 2.2 8,000 2.3 8,800 2.6 210 570 907
1Unit
9 - - 9 2.9 - - 7,560 2.2 10,000 2.9 10,900 3.2 378 733 1,166
12 - - 12 3.9 - - 7,920 2.3 13,200 3.9 14,500 4.2 504 977 1,554
18 - - 18 5.8 - - 11,880 3.5 19,800 5.8 21,800 6.4 756 1,466 2,331
7 7 - 14 2.5 2.5 - 10,080 3.0 16,800 4.9 18,500 5.4 588 1,140 1,813
7 9 - 16 2.5 3.2 - 11,520 3.4 19,200 5.6 21,100 6.2 672 1,303 2,072
9 9 - 18 3.2 3.2 - 12,960 3.8 21,600 6.3 23,700 6.9 756 1,466 2,331
7 12 - 19 2.5 4.2 - 13,680 4.0 22,800 6.7 25,000 7.3 798 1,547 2,461
2Unit 9 12 - 21 3.0 4.0 - 15,120 4.4 24,000 7.0 26,500 7.8 882 1,710 2,720
12 12 - 24 3.5 3.5 - 15,840 4.6 24,000 7.0 26,500 7.8 882 1,710 2,720
7 18 - 25 2.0 5.1 - 16,680 4.9 24,000 7.0 26,500 7.8 882 1,710 2,720
9 18 - 27 2.3 4.7 - 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
12 18 - 30 2.8 4.2 - 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
18 18 - 36 3.5 3.5 - 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
7 7 7 21 2.3 2.3 2.3 15,120 4.4 24,000 7.0 26,500 7.8 882 1,710 2,720
7 7 9 23 2.1 2.1 2.8 16,560 4.9 24,000 7.0 26,500 7.8 882 1,710 2,720
7 9 9 25 2.0 2.5 2.5 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
7 7 12 26 1.9 1.9 3.2 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
9 9 9 27 2.3 2.3 2.3 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
3Unit 7 9 12 28 1.8 2.3 3.0 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
9 9 12 30 2.1 2.1 2.8 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
7 12 12 31 1.6 2.7 2.7 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
7 7 18 32 1.5 1.5 4.0 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
9 12 12 33 1.9 2.6 2.6 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
12 12 12 36 2.3 2.3 2.3 17,280 5.1 24,000 7.0 26,500 7.8 882 1,710 2,720
Combination
(kBtu/h)
Each capacity
(kW)
Total Capacity (kW)
Heating
Min
Rated
Max
Input
(W)
Unit-A Unit-B Unit-C Total Unit-A Unit-B Unit-C Btu/h
kW
Btu/h
kW
Btu/h
kW
Min
Rated
Max
Operation
Note :
1. Cooling Capacity is based on : indoor temp.27°CDB, 19°CWB
; outdoor temp. 35°CDB, 24°CWB
2. Heating Capacity is based on : indoor temp.20°CDB, 15°CWB
; outdoor temp. 7°CDB, 6°CWB
3. Maximum total capacity index of connected indoor units is 36 kBtu/h.
4. At least two indoor units should be connected to outdoor unit.
5. Total capacity of indoor units connected should be minimum 40%
of outdoor unit rated capacity.
Содержание MULTI F A2UW16GFA0
Страница 1: ...Heat pump 60Hz R410A 6CIM 01A P No MFL67502703 ...
Страница 4: ...Part 1 General information 1 Model line up 2 Nomenclature 3 Appearance 4 Combination ...
Страница 10: ...Part 2 Product data n Outdoor units 1 Multiple piping type ...
Страница 164: ...Part 4 Special Part 1 Installation guide at the seaside 2 Seasonal wind and cautions in winter ...