3. Installation of outdoor unit
51
_ Heat pump
60Hz/R410A
Part 3 Design and installation
3. Installation of outdoor unit
3.8 Outdoor unit installation requirements
3.8.1 Piping elevation and length
Installaton irrespective of indoor,
outdoor elevation
Max 15m
Max 7.5m
A
B
C
D
E
Standard length
A,B,C,D
A
B
C
D
E
50m(A+B+C)
7.5
25
25
25
7.5
25
25
25
25
25
-
-
75m(A+B+C+D+E)
Max piping length each indoor unit
Model
[Outdoor unit]
Max total
piping length
7.5
25
25
25
25
25
85m(A+B+C+D+E)
A3UW21GFA0
30m(A+B)
7.5
20
20
-
-
-
A2UW16GFA0
A5UW40GFA0
A5UW30GFA0
[Unit : m]