3. Installation of outdoor unit
41
_ Heat pump
60Hz/R410A
Part 3 Design and installation
3.1.5 Before installation
• During product unpacking and removing it from the packing case, be sure to lift it without exerting any pressure
on other parts, especially, horizontal flaps, the refrigerant piping, drain piping, and other resin parts.
• Be sure to remove a cushion (corrugated paper) located between the heat exchanger and the right air filter.
• Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect refrigerant will pre-
vent normal operation of the unit.)
• The accessories needed for installation must be retained in your custody until the installation work is completed. Do not
discard them!
• Decide upon a line of transport.
• Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is unavoidable, use
a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
• For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.
• When using the wireless remote controller, refer to the installation manual attached to the wireless remote controller.
• Entrust installation to the place of purchase or an authorized serviceman. Improper installation could lead to leaks and in
worst cases, electric shock of fire.
• Use only parts provided with the unit or parts satisfying required specifications. Unspecified parts could cause the unit to
fall out of place, or could lead to leaks and, in the worst cases, electric shock or fire.
3.1.4 For the following items, take special care during construction and check
after installation is finished
1. Items to be checked after completion of work
• Install the indoor and outdoor units, power supply wiring and connecting wires at least 1m. away from televisions
or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1m. may not be sufficient enough to eliminate the noise.)
NOTE
Unit
Are the indoor and outdoor unit fixed firmly? The units may drop, vibrate or make noise.
Is the gas leak test finished? It may result in insufficient cooling.
Is the unit fully insulated? Condensate water may drip.
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage correspond to that The unit may malfunction or the components burn out.
shown on the name plate?
Are wiring and piping correct? The unit may malfunction or the components burn out.
Is the unit safely grounded? It may be dangerous at electric leakage.
Is wiring size according to specifications? The unit may malfunction or the components burn out.
Is something blocking the air outlet or inlet of It may result in insufficient cooling.
either the indoor or outdoor units?
Are refrigerant piping length and additional The refrigerant charge in the system is not clear.
refrigerant charge noted down?
Items to be checked If not properly done, what is likely to occur Check
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic
bag which was not torn apart, they face the risk of suffocation.
CAUTION
Содержание MULTI F A2UW16GFA0
Страница 1: ...Heat pump 60Hz R410A 6CIM 01A P No MFL67502703 ...
Страница 4: ...Part 1 General information 1 Model line up 2 Nomenclature 3 Appearance 4 Combination ...
Страница 10: ...Part 2 Product data n Outdoor units 1 Multiple piping type ...
Страница 164: ...Part 4 Special Part 1 Installation guide at the seaside 2 Seasonal wind and cautions in winter ...