Piping Length and Elevation
Capacity is based on standard length and maximum allowable length is on the basis of reliability.
Additional refrigerant must be charged after 7.5m(25ft).
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
24k/36k
Ø15.88
5/8
Ø9.52
3/8
7.5(25)
15(50)
30(99)
35
Pipe Size
Capacity
(Btu/h)
GAS
LIQUID
mm
inch
mm
inch
Additional
Refrigerant (g/m)
Standard
Length
m (ft)
Max.
Elevation
B m(ft)
Max.
Length
A m(ft)