Descriptions for operation and functions 

16

Ventilation System 

1

2

3

4

5

6

7

8

Models: LZ-H1506BA0 / LZ-H1502BA0 / LZ-H2006BA0 / LZ-H2002BA0

(Ventilation System remote controller ZCON-BS2) remote controller is a separate purchase. 

1. Maintenance Cover 
2. Air Filter 

It prevents dust from clogging in Total Heat Exchanger. 

3. Total Heat Exchanger 

It changes temperature and humidity between
Supplying Air  and exhausted air. 

4. Blower for Exhausting Air 

It is a fan for discharging the contaminated air to
outdoor. 

5. Control box 
6. Blower for Supplying Air 

It is a fan for inhaling exterior air into an indoor space. 

7. Damper plate(board) 

It converts exchanging mode between total heat
ventilation and general ventilation. 

8. Total Heat Exchanger holder 

It is used in guiding for the installation of Total Heat
Exchanger.

The form of Total Heat Exchanger varies according to models. 

Some functions may not work depending on models. (according to models). 

LCD remote controller 

Program set

Room Temp

HI
MED
LO

Timer

On
Set no. Time

Off

01

03

05

07

09

11

13

15

17

19

21

23

Operation unit

ZONE

1 2 3 4

AUTO SWING

AUTO

JET

Heater
Defrost

Preheat
Humidify

Filter

Out door

Time

OPERATION

SET TEMP

FAN SPEED

SUB FUNCTION

Timer

Program

Hour

Cancel

Week

Holiday

Set/Clr

PLASMA

RESET

Min

1

2

5

6
7

8
9

10
11
12

13

3

4

When the cover is open, 

1.

Display Screen 

2.

Heater Button 

3.

Button for time setting/ canceling, and weekend
setting/date selecting/ weekend selecting 

4. 

Play/ Stop Button 

5. 

Delaying time Button 

6. 

Quick ventilation Button 

7. 

Ventilating Mode Button 

8. 

Air flow selection Button 

9. 

Humidification Button 

10. 

Power-saving/filter cleaning Button 

11. 

Plasma Button 

12. 

Time Reset Button 

Содержание LZ-H0106BA0

Страница 1: ...e com BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORIZED SERVICE PERSONNEL MODELS LZ H0106BA0 LZ H0156BA0 LZ H0256BA0 LZ H0506BA0 LZ H0502BA0 LZ H0806BA0 LZ H0802BA0 LZ H1006BA0 LZ H1002BA0 LZ H1506BA0 LZ H1502BA0 LZ H2006BA0 LZ H2002BA0 ...

Страница 2: ...r Model 6 Product Standards 7 Descriptions for operation and functions 14 How to disassemble 17 Disassemble Diagram Deal Drawing and SVC Parts List 22 Wiring Diagram 32 Control Part Detailed Drawing 36 Descriptions for Control Circuit 38 Troubleshooting 40 Feature Dimensions Diagram 47 Accessaries Option 52 ...

Страница 3: ...chased the product If you disassemble of repair arbitrarily it may cause fire or electric shock Install in a place capable of the product s weight If the product is installed in a place incapable of its weight it may cause an accident by its dropping Do not arbitrarily disassemble repair or modify the product It may cause fire or electric shock Be sure to undertake grounding work If you do not und...

Страница 4: ...all electric leakage circuit breakers ELB and exclusive switch switch for electrics If not it may cause fire and electric shock Do not keep flammable materials or volatile gas near the product It may cause fire and breakdown Be sure to keep the product out of water It may cause electric shock and breakdown Use a fuse in standardized capacity Use a standardized capacity fuse It may cause fire and e...

Страница 5: ...o not connect grounding line to window frame chassis and tap It has a danger of electric shock Do not carry the product alone Otherwise it may cause physical damage Do not use for special purposes and places including animals and plants sensitive equipment and art pieces Otherwise it may cause physical damage Do not use strong detergent such as wax or thinner in case of cleaning instead use soft c...

Страница 6: ...G Low Static Moter Serial No Marking in a developed order Serial No Marking in a developed order Grade S Standard D Deluxe Additional Functions B Base Model M possible to connect Multi V Product Name ZCON Controller Ventilation Capacity Ventilating Ability Excluding the first digit of ventilating capacity per hour 50 500CMH Heat Exchange Mode H Total heat including humidity T Sensible heat tempera...

Страница 7: ... 32 0 3 0 28 68 60 50 100 100 70 40 35 30 78 78 80 68 68 70 58 58 60 28 26 20 Non woven fabric filter 24 590 W x 590 D x 204 H Item format Unit LZ H0156BA0 Power Ø V Hz Ventilation Mode Wind velocity Electric current A Electricity consumption W Airflow m3 h External static press Pa Temperature efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 240 50...

Страница 8: ...8 64 64 68 32 28 21 Non woven fabric filter 27 596 W x 640 D x 320 H Item format Unit LZ H0506BA0 Power Ø V Hz Ventilation Mode Wind velocity Electric current A Electricity consumption W Airflow m3 h External static press Pa Temperature efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 240 50 Total heat ventilation General ventilation Super High Hig...

Страница 9: ... 200 70 28 200 70 28 82 82 86 79 79 83 76 76 80 34 32 25 34 32 25 Non woven fabric filter 45 988 W x 1 014 D x 273 H Item format Unit LZ H0806BA0 Power Ø V Hz Ventilation Mode Wind velocity Electric current A Electricity consumption W Airflow m3 h External static press Pa Temperature efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 240 50 Total hea...

Страница 10: ...110 60 200 110 60 79 79 82 70 70 75 65 65 70 36 34 30 36 34 30 Non woven fabric filter 67 1 062 W x 1 140 D x 365 H Item format Unit LZ H1006BA0 Power Ø V Hz Ventilation Mode Wind velocity Electric current A Electricity consumption W Airflow m3 h External static press Pa Temperature efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 240 50 Total heat...

Страница 11: ...10 60 200 110 60 75 75 78 66 66 71 61 61 66 37 35 31 37 35 31 Non woven fabric filter 67 1 062 W x 1 140 D x 365 H Item format Unit LZ H1506BA0 Power Ø V Hz Ventilation Mode Wind velocity Electric current A Electricity consumption W Airflow m3 h External static press Pa Temperature efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 240 50 Total heat ...

Страница 12: ... 160 90 50 200 110 60 75 75 78 66 66 71 61 61 66 42 38 33 42 38 33 Non woven fabric filter 146 1 313 W x 1 140 D x 737 H Item format Unit LZ H1502BA0 Power Ø V Hz Ventilation Mode Wind velocity Electric current A Electricity consumption W Airflow m3 h External static press Pa Temperature efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 60 Total hea...

Страница 13: ...e efficiency Enthalpy efficiency Heating Cooling Noise dB A Air Filter Weight kg Dimensions mm 1 220 60 Total heat ventilation General ventilation Super High High Low Super High High Low 7 0 6 8 5 8 7 0 6 8 5 8 1 344 1 306 1 122 1 344 1 306 1 122 2 000 2 000 1 600 2 000 2 000 1 600 200 110 70 200 110 70 75 75 78 66 66 71 61 61 66 42 38 33 42 38 33 Non woven fabric filter 146 1 313 W x 1 140 D x 73...

Страница 14: ...ly air and exhaust air 6 Air Filter Prevents clogging of the Total heat exchanger due to The figure of Total heat Exchanger can be different by the Product Model The figure of Total heat Exchanger can be different by the Product Model 1 5 4 6 2 3 1 Air Filter Prevents clogging of the Total heat exchanger due to dust 2 Total Heat Exchanger Exchanges temperature and moisture between air supply air a...

Страница 15: ...ed in guiding for the installation of Total Heat Exchanger The form of Total Heat Exchanger varies according to models The form of Total Heat Exchanger varies according to models 1 5 6 7 8 2 3 4 Models LZ H0806BA0 LZ H0802BA0 LZ H1002BA0 LZ H1006BA0 1 Maintenance Cover 2 Air Filter It prevents dust from clogging in Total Heat Exchanger 3 Total Heat Exchanger It changes temperature and humidity bet...

Страница 16: ... holder It is used in guiding for the installation of Total Heat Exchanger The form of Total Heat Exchanger varies according to models Some functions may not work depending on models according to models LCD remote controller Program set Room Temp HI MED LO Timer On Set no Time Off 01 03 05 07 09 11 13 15 17 19 21 23 Operation unit ZONE 1 2 3 4 AUTO SWING AUTO JET Heater Defrost Preheat Humidify Fi...

Страница 17: ...l Heat Exchanger Filter Take the Maintenance Cover off and take them out in case that the Maintenance Cover is screwed up unscrew it first Be careful of sharp area when taking the Air Filter out Be careful not to drop the Total Heat Exchanger from the main body when detaching Fan Take the fan out after taking the Maintenance Cover off in case that the Maintenance Cover is screwed up unscrew it fir...

Страница 18: ...lter out Be careful not to drop the Total Heat Exchanger from the main body when detaching Fan Take the fan out after taking the Maintenance Cover off in case that the Maintenance Cover is screwed up unscrew it first Be careful of sharp area when taking the fan out Screw Control box cover Maintenance Cover Main Body Setting Knob Total Heat Exchanger Clamp Cord In case of service operate through in...

Страница 19: ...hen taking the Air Filter out Be careful not to drop the Total Heat Exchanger from the main body when detaching Fan Take the fan out after taking the Maintenance Cover off in case that the Maintenance Cover is screwed up unscrew it first Be careful of sharp area when taking the fan out Control box cover Screw Maintenance Cover Main body Main body In case of service operate through inspecting tool ...

Страница 20: ...f sharp area when taking the Air Filter out Be careful not to drop the Total Heat Exchanger from the main body when detaching Fan Take the fan out after taking the Maintenance Cover off in case that the Maintenance Cover is screwed up unscrew it first Be careful of sharp area when taking the fan out Control box cover Screw Maintenance Cover Main body Main body In case of service operate through in...

Страница 21: ...sharp area when taking the Air Filter out Be careful not to drop the Total Heat Exchanger from the main body when detaching Fan Take the fan out after taking the Maintenance Cover off in case that the Maintenance Cover is screwed up unscrew it first Be careful of sharp area when taking the fan out Control box cover Screw Maintenance Cover Main body Main body In case of service operate through insp...

Страница 22: ...mble Diagram Deal Drawing and SVC Parts List 22 Ventilation System Disassemble Diagram Deal Drawing and SVC Parts List Models LZ H0106BA0 LZ H0156BA0 W0CZZ 268714 263230 2 152312 359012 546810 263230 1 340090 ...

Страница 23: ... 4681A20068H 2 R 268714 PCB ASSEMBLY MAIN 6871A10118E 1 1 R W0CZZ CAPACITOR FILM BOX 3H00660P 2 2 R 263230 1 THERMISTOR NTC 6323A30004L 1 1 R Indoor 263230 2 THERMISTOR NTC 6323A30004M 1 1 R Outdoor 152312 FILTER ASSEMBLY AIR CLEANER 5231A30003E 2 2 R 340090 EXCHANGER ASSEMBLY 4009A20002D 1 1 R Location No Item Remarks Part No SVC Quantity Volume Amount LZ H0106BA0 LZ H0156BA0 ...

Страница 24: ...Disassemble Diagram Deal Drawing and SVC Parts List 24 Ventilation System Models LZ H0256BA0 268714 W0CZZ 359012 546810 152312 340090 263230 2 263230 1 ...

Страница 25: ...OOR 4681A20068M 2 R 268714 PCB ASSEMBLY MAIN 6871A10118E 1 R W0CZZ CAPACITOR FILM BOX 3H00660P 2 R 263230 1 THERMISTOR NTC 6323A30004L 1 R Indoor 263230 2 THERMISTOR NTC 6323A30004M 1 R Outdoor 152312 FILTER ASSEMBLY AIR CLEANER 5231A30003C 2 R 340090 EXCHANGER ASSEMBLY 4009A20002B 1 R Location No Item Remarks Part No SVC Quantity Volume Amount LZ H0256BA0 ...

Страница 26: ...Disassemble Diagram Deal Drawing and SVC Parts List 26 Ventilation System Models LZ H0506BA0 LZ H0502BA0 340090 152312 546810 1 546810 2 359012 W0CZZ 268714 146812 263230 2 263230 1 ...

Страница 27: ...N 1 R Oudoor 263230 1 THERMISTOR NTC 6323A30004G 1 R Indoor 263230 2 THERMISTOR NTC 6323A30004H 1 R Outdoor 268714 PCB ASSEMBLY MAIN 6871A10118A 1 R W0CZZ CAPACITOR FILM BOX 3H00660Z 2 R 340090 EXCHANGER ASSEMBLY 4009A20001A 2 R 152312 FILTER ASSEMBLY AIR CLEANER 5231A30003A 2 R 146812 MOTOR ASSEMBLY AC SYNCHRONOUS 4681A20120A 1 R Location No Item Remarks Part No SVC Quantity Volume Amount LZ H050...

Страница 28: ...sassemble Diagram Deal Drawing and SVC Parts List 28 Ventilation System Models LZ H0806BA0 LZ H0802BA0 LZ H1006BA0 LZ H1002BA0 W0CZZ 268714 346810 1 346810 2 349011 263230 2 263230 1 359012 152312 340090 ...

Страница 29: ... 4681A20139C 2 2 R 263230 1 THERMISTOR NTC 6323A30004J 1 1 1 1 R Indoor 263230 2 THERMISTOR NTC 6323A30004K 1 1 1 1 R Outdoor 349011 DAMPER ASSEMBLY 4901A20002A 1 1 1 1 R 268714 PCB ASSEMBLY MAIN 6871A10118C 1 1 R 6871A10118B 1 1 R W0CZZ CAPACITOR FILM BOX 3H00660W 2 2 2 2 R 152312 FILTER ASSEMBLY AIR CLEANER 5231A30003B 2 2 2 2 R 340090 EXCHANGER ASSEMBLY 4009A20002A 2 2 2 2 R Location No Item Re...

Страница 30: ...sassemble Diagram Deal Drawing and SVC Parts List 30 Ventilation System Models LZ H1506BA0 LZ H1502BA0 LZ H2006BA0 LZ H2002BA0 152312 340090 346810 2 346810 1 359012 349011 567480 2 567480 1 W0CZZ 268711 ...

Страница 31: ... 4681A20139C 4 4 R 263230 1 THERMISTOR NTC 6323A30004J 2 2 2 2 R Indoor 263230 2 THERMISTOR NTC 6323A30004K 2 2 2 2 R Outdoor 349011 DAMPER ASSEMBLY 4901A20002A 2 2 2 2 R 268714 PCB ASSEMBLY MAIN 6871A10118C 2 2 R 6871A10118B 2 4 R W0CZZ CAPACITOR FILM BOX 3H00660W 4 4 4 4 R 152312 FILTER ASSEMBLY AIR CLEANER 5231A30003B 4 4 4 4 R 340090 EXCHANGER ASSEMBLY 4009A20002A 4 4 4 4 R Location No Item Re...

Страница 32: ...2 Ventilation System Wiring Diagram Models LZ H0106BA0 LZ H0156BA0 LZ H0256BA0 This product has different wiring method by system configuration Perform the wiring work electric working on several necessary parts areas ...

Страница 33: ...Wiring Diagram Service Manual 33 Models LZ H0506BA0 LZ H0502BA0 This product has different wiring method by system configuration Perform the wiring work electric working on several necessary parts areas ...

Страница 34: ...tral Controller Indoor Thermistor Outdoor Thermistor Main PCB CO2 Sensor Prepare a circuit breaker on separate purchase Factory wiring Field wiring on the spot wiring WARNING Information Be sure to install electric leakage circuit breaker and switch Be sure to undertake grounding work Note BR Brown BL Blue BK Black WT white RD Red GN Green YL Yellow OR Orange Single Phase 220V 50 60Hz Power Supply...

Страница 35: ...or Thermistor CO2 Sensor CO2 Sensor Main PCB Main PCB Note BK Black BR Brown RD Red YL Yellow BL Blue OR Orange GN YL Green Yellow Single Phase 220V 50 60Hz Power Supply BR BL GN YL Indoor Unit of Air conditioner Link to Ventilation Wired remote controller connection BR BR BL BR BL YL RD Capacitor BR BR YL YL Capacitor SA Fan Motor EA Fan Motor BK BK OR OR Damper Motor BK RD BR BR YL Normal Total ...

Страница 36: ...MPER CN CC CN SPARE CN IN CN OUT CN CO2 OPTION SWITCH CN REMO FUSE CN POWER Descriptions of symbols marking Marking Name CN POWER Power Code Connector FUSE Fuse CN MOTOR SA Fan motor connector Supplying Air CN MOTOR EA Fan motor connector Exhausted air CN DAMPER Synchronous Motor connector CN SPARE Heater connector CN CC Central controller connector Marking Name CN IN Thermistor indoor connector C...

Страница 37: ...ndoor connector CN OUT Thermistor outdoor connector CN CO2 CO2 Sensor connector OPTION SWITCH Option Switch CN REMO Remote controller terminal block Models LZ H0506BA0 LZ H0502BA0 LZ H0806BA0 LZ H0802BA0 LZ H1006BA0 LZ H1002BA0 LZ H1506BA0 LZ H1502BA0 LZ H2006BA0 LZ H2002BA0 This product has different wiring method by system configuration Perform the wiring work electric working on several necessa...

Страница 38: ...tion S W No 7 ON Total heat SA EA OFF OFF Total heat SA OFF EA WEAK Operating mode setting for remote controller and exterior air conditioner Air flow setting for supply exhaust by Remote Controller and Exterior air conditioner Abnormal condition Normal condition Intermittent Operation Total Heat Total heat operation Weak operation Strong operation Quick operation Power Saving operation Extremely ...

Страница 39: ...ion S W No 7 ON Total heat SA EA OFF OFF Total heat SA OFF EA WEAK Operating mode setting for remote controller and exterior air conditioner Air flow setting for supply exhaust by Remote Controller and Exterior air conditioner Abnormal condition Normal condition Intermittent Operation Weak operation Strong operation Quick operation Power Saving operation Extremely Strong Operation STRONG QUICK Pow...

Страница 40: ...r to PCB Isn t it in defrosting operation Re construct the power Wire in accordance with power wiring diagram Replace FUSE Convert the function into Total heat exchange mode Check whether damper is operating while repeating total heat exchange and normal ventilating alternately Wire in accordance with power wiring diagram Wire in accordance with power wiring diagram Re wire for capacitor separatio...

Страница 41: ...ength of transmission wire Check the delay mode setting of remote controller Check the interlocking mode setting of remote controller Check the wiring length of signal wire Check the external equipment Release the interlocking setting Check the connection of transmission line Check the wiring length of transmission line Check the connection of transmission line Check the wiring length of transmiss...

Страница 42: ...kdown 3 Breakdown timing 4 presence of contract drawing Equipment including separate purchase control equipment wiring piping setting Breakdown mode1 system does not start normally Breakdown mode2 Abnormal failure code is displayed on remote controller LED is flickering on the circuit panel of ventilation system Breakdown mode 3 Remote controller does not work It works abnormally Breakdown mode 4 ...

Страница 43: ... than 200m total extension of less than 500m 4 Is the prescribed transmission line used type of line diameter of line 5 Are the transmission line and power line wired at more than 5cm interval 6 Aren t there any multiple transmission line or signal line in the same wire pipe 7 Aren t multiple transmission lines wired as multicable 8 Does the connecting terminal plate of transmission have trouble f...

Страница 44: ...ity to power line Connecting failure of transmission line Longer wiring length of transmission line than prescribed more than 500m Checking No Details Possible Causes Necessary actions Check the connection of circuit connector and lead line connecting connector Check the connection of circuit connector and lead line connecting connector With electric wires place each transmission line at intervals...

Страница 45: ...panel Check the power in ventilation system Check the power Check the wiring length of transmission line With exclusive wires wire each transmission line at intervals Wire transmission line and power line at more than 5cm intervals Replace remote controller No error Activate the ventilation stop in air conditioner to stop ventilating Stop the ventilation system with remote controller and temporari...

Страница 46: ... by this company by interlocking the air conditioner stops in case of defrosting Displayed power saving operation Displayed intermittent operation No Details Possible Causes Necessary actions Check the connection of control circuit connector and lead line connecting connector Check the power Check LOCK of central control and address of ventilation system Check the connection of external control te...

Страница 47: ... Air Filter Blower for Supplying Air Blower for Exhausting Air EA Exhaust Air SA Supply Air RA Return Air OA Outdoor Air A D C F J G H Unit mm It necessary to secure sufficient space for maintenance more than the dimensions described in the product service Model Nominal Diameter Weight Duct Connection Flange Figure Pitch of Suspension Fixture A B C D E F G H J K L Duct Pitch LZ H0106BA0 LZ H0156BA...

Страница 48: ...ir A G K D C F L B E H J EA Exhaust Air SA Supply Air RA Return Air OA Outdoor Air LZ H0256BA0 640 596 320 568 636 2 55 150 140 160 70 430 84 27 Unit mm It necessary to secure sufficient space for maintenance more than the dimensions described in the product service Model Nominal Diameter Weight Duct Connection Flange Figure Pitch of Suspension Fixture A B C D E F G H J K L Duct Pitch ...

Страница 49: ... Filter F RA Return Air SA Supply Air OA Outdoor Air EA Exhaust Air LZ H0502BA0 1 014 988 273 938 8 1024 8 135 200 194 252 95 8 590 198 3 52 LZ H0506BA0 Unit mm It necessary to secure sufficient space for maintenance more than the dimensions described in the product service Model Nominal Diameter Weight Duct Connection Flange Figure Pitch of Suspension Fixture A B C D E F G H J K L Duct Pitch ...

Страница 50: ...ement Air Filter F RA Return Air SA Supply Air OA Outdoor Air EA Exhaust Air 1062 1140 365 987 1176 180 250 242 253 98 513 481 67 Unit mm It necessary to secure sufficient space for maintenance more than the dimensions described in the product service Model Nominal Diameter Weight Duct Connection Flange Figure Pitch of Suspension Fixture A B C D E F G H J K L Duct Pitch LZ H0806BA0 LZ H0802BA0 LZ ...

Страница 51: ...A Supply Air OA Outdoor Air EA Exhaust Air Total Heat Exchange Element F Suspension Fixture 1313 1140 737 987 1176 150 242 253 98 340 350 130 350 253 410 482 146 513 146 Unit mm Model Figure Pitch of Suspension Fixture Duct Connection Flange Nominal Diameter Duct Pitch Weight A B C D E F G H J K L M EA SA N O P Q kg LZ H1506BA0 LZ H1502BA0 LZ H2006BA0 LZ H2002BA0 ...

Страница 52: ...AUTO JET Heater Defrost Preheat Humidify Filter Out door Time OPERATION SET TEMP FAN SPEED SUB FUNCTION Timer Program Hour Cancel Week Holiday Set Clr PLASMA RESET Min 1 2 5 6 7 8 9 10 11 12 13 3 4 When the cover is open 1 Display Screen 2 Heater Button 3 Button for time setting canceling and weekend setting date selecting weekend selecting 4 Play Stop Button 5 Delaying time Button 6 Quick ventila...

Страница 53: ...se E C B A Ø F D Model Capacity W Connecting Caliber Ø PEH Z4P0 400 100 PEH Z8P0 800 100 Product Standard PEH Z4P0 203 291 134 117 100 97 5 202 2 5 PEH Z8P0 203 291 134 117 100 147 202 2 5 Unit mm Model Nominal Diameter Weight Duct Connection Flange Figure Pitch of Suspension Fixture A B C D E F ...

Страница 54: ...P No 3828A20320D December 2005 Printed in Korea ...

Отзывы: