3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
4. Cooling or Heating Mode with Sleep Mode Auto Operation
• When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the
operation diagram is as following.
Cooling Mode with the Sleep Mode
• The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Heating Mode with the Sleep Mode.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
More than
More than
3 minutes
3 minutes
INDOOR FAN
Low
Low
Low
Low
Low
COMPRESSOR
ON
OFF
ON OFF
ON
30 minutes
30 minutes
1°C
1°C
–14–
Setting Temp. +3°C
(Compressor OFF)
Setting Temp.
(Compressor ON)
Indoor Fan
Low.
Low.
Low.
Low.
Low.
Low.
Compressor
ON
OFF
ON
OFF
ON
OFF
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
More than
More than
3 minutes
3 minutes
Selecting
Selecting
Selecting
fan speed
fan speed
fan speed
COMPRESSOR
ON
OFF
ON OFF
ON
INDOOR FAN
Low Low