Installation
6RMI0-02A
70
Inverter Single
Inverter Single
Inverter Single
2. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
3. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrow on the wrench.
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side piping
(Smaller diameter)
Torque wrench
Outdoor unit
1. Remove the tubing cover from the unit by
loosening the screw.
Tubing cover
mm inch kgf.m lbf.ft
Ø6.35 1/4 1.8~2.5 13~18
Ø9.52 3/8 3.4~4.2 24.6~30.4
Ø12.7 1/2 5.5~6.6 39.8~47.7
Ø15.88 5/8 6.3~8.2 45.6~59.3
Ø19.05 3/4 9.9~12.1 71.6~87.5
Outside diameter
Torque
Inverter Single